| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| System Voltage | Voc | 480 V | Line-to-line; LV model (≤ 600 V) |
| Bolted Fault Current | Ibf | 35 kA | Three-phase symmetrical rms |
| Arc Duration (full I<sub>arc</sub>) | T | 100 ms | Clearing time at the full arcing current |
| Arc Duration (reduced I<sub>arc</sub>) | Tmin | 100 ms | Clearing time at the reduced arcing current |
| Electrode Configuration | VCB | Vertical conductors/electrodes inside a metal box/enclosure | |
| Conductor Gap | G | 32 mm | 1.26 in |
| Working Distance | D | 610 mm | 24.0 in |
| Enclosure Height | H | 508 mm | Enclosure opening |
| Enclosure Width | W | 508 mm | Enclosure opening |
| Enclosure Depth | 508 mm | typical box |
Where: • I_bf = 35.000 kA (bolted fault current) • G = 32.0 mm (conductor gap) • k_1 … k_10 = Table 1 coefficients for VCB at 600 V, 2700 V and 14 300 V I_arc,600 = 26,890 A
Where: • V_oc = 0.480 kV • I_arc,600 = 26.890 kA • I_bf = 35.000 kA I_arc = 24,242 A (69.3% of the bolted fault current)
The arcing current varies about its average; the reduced current can take longer to clear and so can release more energy. Both cases are evaluated and the worse governs. • k_1 … k_7 = Table 2 coefficients for VCB • V_oc = 0.480 kV • VarC_f = 0.2465 • 1 − 0.5 VarC_f = 0.8767 I_arc,min = 21,254 A
Box type: typical (Eq 14) • Equivalent width W_1 = 20.000 in (Eq 11-12, Table 6) • Equivalent height H_1 = 20.000 in • EES = 20.000 in (Eq 13) • b_1, b_2, b_3 = Table 7 coefficients for VCB, typical box CF = 0.9999
Eq 6 (systems at or below 600 V), with T in ms, D in mm, currents in kA, E in J/cm². • k_1 … k_13 = Table 3 (600 V) coefficients for VCB • The k_3 term uses the full I_arc,600; the k_13 term uses the arcing current of the case Full arcing current: I_arc = 24,242 A, T = 100 ms → E = 16.918 J/cm² = 4.044 cal/cm² Reduced arcing current: I_arc,min = 21,254 A, T = 100 ms → E = 14.917 J/cm² = 3.565 cal/cm²
• D = 609.6 mm, k_12 = -1.598 (distance exponent, Table 3) • 1.2 cal/cm² = 5.0208 J/cm² (the "20/T" of Eq 7-10) Full arcing current: AFB = 1,304 mm Reduced arcing current: AFB = 1,205 mm
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Arcing Current (full) | Iarc | 24.2 kA | 69.3% of bolted fault |
| Arcing Current (reduced) | Iarc,min | 21.3 kA | VarC_f = 0.2465 |
| Enclosure Correction Factor | CF | 1 | typical |
| Incident Energy | E | 4.04 cal/cm² | full case at 609.6 mm |
| Arc Flash Boundary | AFB | 1.3 kmm | 51.3 in / 1.30 m |
| Minimum PPE Arc Rating | 4.1 cal/cm² | NFPA 70E Table 130.5(G); equivalent category 2 (8 cal/cm²) |