Cable Permissible Load Calculation

The seven checks of the load cable sizing method (AS/NZS 3008.1.1:2017 for current-carrying capacity, voltage drop, short-circuit withstand and earth fault loop impedance; AS/NZS 3000:2018 Clause 2.5.3.1 for overload coordination and Table 5.1 for the earth conductor size; the adiabatic equation for the earth conductor withstand) are worked backwards for the selected cable and installation to find the largest load the cable may supply and the largest protective device it may be protected by. The load-type label used for sizing (control panel, distribution board, VSD, ...) does not change the permissible load; only its current, power factor and design factor do.

1.1 Supply and Load Basis

Supply voltage, power factor and design factor of the loads to be supplied:
Parameter Symbol Value Notes
AS/NZS 3008 Edition 2017 The only supported edition
Power Factor Direction lagging Controls the sign of the reactive voltage component
Supply Voltage Vpp 400 V Phase-to-phase voltage
Design Factor kdesign 1 Design margin multiplier
Cable Length L 100 Meter Cable run length
Length Unit Meter Length measurement unit
Max Voltage Drop Vd,max 5 % Maximum allowable
Motor Efficiency η 95 % kW load table only: IEC 60072 ratings are shaft output, I = P / (√3 V PF η)

1.2 Cable Data

Cable construction and conductor specifications:
Parameter Symbol Value Notes
Cable Type Fixed Cable construction
Cable Formation Multicore Multicore or Singlecore
Conductor Size A 50 Phase conductor CSA
MC Arrangement Circular Conductor arrangement
Cable Insulation XLPE Insulation type
Conductor Material Material Cu Cu or Al
Earth Conductor 16 Earth conductor CSA

1.3 Cable Installation

Installation method and environmental conditions:
Parameter Symbol Value Notes
Installation Method Unenclosed
Unenclosed Type (MC) Spaced from Surface
Air Arrangement Perforated Trays Horizontal
Cables Per Tier 1
Ladder Spacing Spaced
Ladder Tiers 1Tier
Air Ambient Temp 40
Cables per Tier 1

1.4 Protection

Fault level, clearing time, instantaneous trip multiplier and source impedance:
Parameter Symbol Value Notes
Prospective Fault Current If 10 kA Maximum fault current
CB Clearance Time tprot 100 ms Protection device time
Earth Fault Clearing Time tef 40 ms Near-end earth fault (earth withstand)
Instantaneous Trip Multiplier kmag 5 Magnetic trip factor
Source Impedance Zsource 100 mΩ Upstream impedance

2. Limit 1: Current Carrying Capacity

Derated capacity of the cable from AS/NZS 3008 Tables with all applicable derating factors.
Parameter Symbol Value Notes
Table 24 $$F_{ladder}$$ 1 Table 24 (Col: Row 10, Row: 1)
Table 27(1) $$F_{temp}$$ 1 Table 27(1) (Col: Row 90, Row: 40)

2.2 Combined Derating Factor

Combined derating factor from applicable AS/NZS 3008 tables:

Formula: $$ \begin{aligned} F_{derating} &= F_{ladder} \times F_{temp} \\ &= 1.0 \times 1.0 \\ &= 1.000 \end{aligned} $$

2.3 Derated Cable Capacity

Base current rating adjusted for installation conditions: Ref: Table 14, Column 2, Row: 50mm²

Formula: $$ \begin{aligned} I_{derated} &= F_{derating} \times I_C \\ &= 1.000 \times 182.0 \\ &= 182.000 \; \text{A} \end{aligned} $$

2.4 Capacity-Limited Load Current

The design current (load current times the design factor) may not exceed the derated capacity:

Formula: $$ \begin{aligned} I_{L,CCC} &= \frac{I_Z}{k_{design}} \\ &= \frac{182}{1} \\ &= 182 \; \text{A} \end{aligned} $$

3. Limit 2: Voltage Drop

The three-phase voltage drop over 100 m may not exceed 5.0 % of 400 V. It is evaluated at the design current I_B = I_L × k_design, the same current the capacity and device limits use. Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).

3.1 Effective Impedance

Signed AS/NZS 3008 impedance for the load power factor (lagging adds the reactive term): Rc Ref: Table 35, Column 5, Row: 50mm². Xc Ref: Table 30, Column 10, Row: 50mm².

Formula: $$ \begin{aligned} Z_{eff} &= R_c \cos\varphi + X_c \sin\varphi \\ &= 0.49400 \times 0.85 + 0.07510 \times 0.5268 \\ &= 0.45946 \; \Omega/\text{km} \end{aligned} $$

3.2 Voltage Drop per Ampere

Formula: $$ \begin{aligned} \frac{V_d}{I} &= \sqrt{3} \times L_{km} \times Z_{eff} \\ &= \sqrt{3} \times 0.10000 \times 0.45946 \\ &= 0.07958 \; \text{V/A} \end{aligned} $$

3.3 Voltage-Drop-Limited Load Current

Largest load current whose design current keeps the drop within the limit:

Formula: $$ \begin{aligned} I_{L,VD} &= \frac{V_{d,max}}{(V_d / I) \times k_{design}} \\ &= \frac{5\% \times 400}{0.07958 \times 1} \\ &= \frac{20.0}{0.07958} \\ &= 251 \; \text{A} \end{aligned} $$

4. Short Circuit Withstand

Independent of the load: the cable must withstand the prospective fault current for the clearing time (adiabatic equation, AS/NZS 3008 Table 52). A cable that fails this check has no permissible load with the entered protection.

4.1 Adiabatic Equation

k-factor = 143.0 for Cu XLPE

Formula: $$ \begin{aligned} t_{max} &= \frac{k^2 S^2}{I_f^2} \\ &= \frac{(143)^2 \times (50)^2}{(10000)^2} \\ &= 0.5112 \; \text{s} \end{aligned} $$

4.2 Short Circuit Verification

Minimum conductor size for the fault: S_min = 22.1 mm².

Formula: $$ \text{Check: } t_{max} \geq t_{prot} \quad 0.5112 \geq 0.1 \quad \text{PASS ✓} $$

5. Earth Conductor

Independent of the load: the protective earth conductor must be at least the AS/NZS 3000:2018 Table 5.1 minimum for the phase conductor size, and it must withstand the largest earth-fault current for the earth-fault clearing time t_ef (adiabatic equation). A near-end fault is far above the device's instantaneous threshold, so t_ef is the instantaneous clearing time, not the protection time of the short-circuit check; enter the upstream backup time if clearance relies on it. A cable that fails either check has no permissible load.

5.1 Earth Conductor Size (AS/NZS 3000 Table 5.1)

AS/NZS 3000:2018 Table 5.1 minimum for a 50 mm² phase conductor: 16 mm².

Formula: $$ \text{Check: } S_{earth} \geq S_{earth,min} \quad 16 \geq 16 \; \text{mm}^2 \quad \text{PASS ✓} $$

5.2 Largest Earth Fault Current

A fault at the supply end of the cable is limited only by the source impedance, so the near-end fault gives the largest earth-fault current:

Formula: $$ \begin{aligned} I_{ef} &= \frac{V}{\sqrt{3} \, Z_{source}} \\ &= \frac{400}{\sqrt{3} \times 0.10000} \\ &= 2309 \; \text{A} \end{aligned} $$

5.3 Minimum Earth Conductor Size for Withstand

Adiabatic equation with t_ef the earth-fault clearing time (input): k = 143 from AS/NZS 3008.1.1:2017 Table 52 (initial 90 °C, final 250 °C) for Cu XLPE. The earth is an integral core of the same cable, so it starts at the insulation's operating temperature and ends at the same final temperature as the phase conductors: it shares their k.

Formula: $$ \begin{aligned} S_{min} &= \frac{I_{ef} \sqrt{t_{ef}}}{k} \\ &= \frac{2309 \times \sqrt{0.04}}{143} \\ &= 3.23 \; \text{mm}^2 \end{aligned} $$

5.4 Earth Conductor Withstand Verification

Withstand time of the earth conductor: t_max = (k S_earth / I_ef)² = 0.982 s against an earth-fault clearing time of 0.04 s.

Formula: $$ \text{Check: } S_{earth} \geq S_{min} \quad 16 \geq 3.23 \; \text{mm}^2 \quad \text{PASS ✓} $$

6. Limit 3a: Earth Fault Loop Impedance

The earth fault current of this loop fixes the largest instantaneous trip setting, and so the largest device rating, that still disconnects on an earth fault at the far end.

6.1 Phase Conductor Impedance

Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).

Formula: $$ \begin{aligned} Z_{phase} &= L_{km} \sqrt{R_c^2 + X_c^2} \\ &= 0.10000 \times \sqrt{0.49400^2 + 0.07510^2} \\ &= 0.04997 \; \Omega \end{aligned} $$

6.2 Earth Conductor Impedance

Earth conductor 16 mm²: R_e from Tables 34/35 and X_e from AS/NZS 3008.1.1:2017 Table 30 at 16 mm² (multicore, circular), read with the phase cable's arrangement. Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).

Formula: $$ \begin{aligned} Z_{earth} &= L_{km} \sqrt{R_e^2 + X_e^2} \\ &= 0.10000 \times \sqrt{1.470^2 + 0.08050^2} \\ &= 0.14722 \; \Omega \end{aligned} $$

6.3 Total Loop Impedance

The magnitudes are added arithmetically, an upper bound on the phasor sum.

Formula: $$ \begin{aligned} Z_{loop} &= Z_{source} + Z_{phase} + Z_{earth} \\ &= 0.10000 + 0.04997 + 0.14722 \\ &= 0.29719 \; \Omega \end{aligned} $$

6.4 Earth Fault Current

Formula: $$ \begin{aligned} I_{fault} &= \frac{V_{ph}}{Z_{loop}} \\ &= \frac{231}{0.29719} \\ &= 777 \; \text{A} \end{aligned} $$

6.5 Largest Device Rating for Earth Fault Protection

The device must see at least its instantaneous trip current, I_fault >= I_N x k_mag:

Formula: $$ \begin{aligned} I_{N,EFL} &= \frac{I_{fault}}{k_{mag}} \\ &= \frac{777}{5} \\ &= 155 \; \text{A} \end{aligned} $$

7. Limit 3b: Overload Coordination

AS/NZS 3000:2018 Clause 2.5.3.1 requires I_B <= I_N <= I_Z: the device rating may not exceed the derated cable capacity and must cover the design current. The companion condition I_2 <= 1.45 I_Z is met by devices to AS/NZS 60898, AS/NZS 60947.2 or AS 60269.

7.1 Largest Permissible Device Rating

Limited by the earth fault loop (I_N ≤ I_fault / k_mag). Largest preferred rating (AS/NZS 60898 / 60947.2 / AS 60269) not exceeding this: 125 A.

Formula: $$ \begin{aligned} I_{N,max} &= \min(I_Z, I_{N,EFL}) \\ &= \min(182, 155) \\ &= 155 \; \text{A} \end{aligned} $$

7.2 Protection-Limited Load Current

With the largest preferred device, the design current may not exceed the device rating:

Formula: $$ \begin{aligned} I_{L,prot} &= \frac{I_{N,std}}{k_{design}} \\ &= \frac{125}{1} \\ &= 125 \; \text{A} \end{aligned} $$

8. Permissible Load Envelope

The permissible load current is the smallest of the three limits; the short-circuit check and both earth-conductor checks must also pass.

8.1 Permissible Load Current

Governing limit: Earth Fault Loop (I_N ≤ I_fault / k_mag). Design current at this load: 125.0 A.

Formula: $$ \begin{aligned} I_{L,max} &= \min(I_{L,CCC}, I_{L,VD}, I_{L,prot}) \\ &= \min(182, 251, 125) \\ &= 125 \; \text{A} \end{aligned} $$

8.2 Permissible Load Power

Apparent power S_max = 86.6 kVA. Power loss at this load: 2,316 W (3.15 %).

Formula: $$ \begin{aligned} P_{max} &= \sqrt{3} \times V \times I_{L,max} \times \cos\varphi / 1000 \\ &= \sqrt{3} \times 400 \times 125 \times 0.85 / 1000 \\ &= 73.6 \; \text{kW} \end{aligned} $$

8.3 Permissible Motor Output

P_max is electrical input; the largest motor (IEC 60072 shaft rating) it supplies is lower by the efficiency:

Formula: $$ \begin{aligned} P_{motor} &= P_{max} \times \eta \\ &= 73.6 \times 0.95 \\ &= 69.9 \; \text{kW} \end{aligned} $$

9. Permissible Loads

Series of preferred motor ratings (IEC 60072 kW shaft output, line current I = P / (√3 V PF η) at η = 95 %) checked with all seven checks; each load is protected by the smallest preferred device rating at or above its design current. CCC = current-carrying capacity, VD = voltage drop, SC = short-circuit withstand, EFL = earth fault loop, OVL = overload coordination, ESZ = earth conductor size, EWT = earth conductor withstand; the Symbol column shows the seven marks in that order.
Parameter Symbol Value Notes
1.5 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 2.7 A (1.6 kW input, 2 kVA), I_N 6 A, 1 % loaded, V_d 0.05 %, I_f 777/30 A
2.2 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 3.9 A (2.3 kW input, 3 kVA), I_N 6 A, 2 % loaded, V_d 0.08 %, I_f 777/30 A
3 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 5.4 A (3.2 kW input, 4 kVA), I_N 6 A, 3 % loaded, V_d 0.11 %, I_f 777/30 A
4 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 7.1 A (4.2 kW input, 5 kVA), I_N 10 A, 4 % loaded, V_d 0.14 %, I_f 777/50 A
5.5 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 9.8 A (5.8 kW input, 7 kVA), I_N 10 A, 5 % loaded, V_d 0.20 %, I_f 777/50 A
Parameter Symbol Value Notes
7.5 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 13.4 A (7.9 kW input, 9 kVA), I_N 16 A, 7 % loaded, V_d 0.27 %, I_f 777/80 A
11 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 19.7 A (11.6 kW input, 14 kVA), I_N 20 A, 11 % loaded, V_d 0.39 %, I_f 777/100 A
15 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 26.8 A (15.8 kW input, 19 kVA), I_N 32 A, 15 % loaded, V_d 0.53 %, I_f 777/160 A
18.5 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 33.1 A (19.5 kW input, 23 kVA), I_N 40 A, 18 % loaded, V_d 0.66 %, I_f 777/200 A
22 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 39.3 A (23.2 kW input, 27 kVA), I_N 40 A, 22 % loaded, V_d 0.78 %, I_f 777/200 A
Parameter Symbol Value Notes
30 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 53.6 A (31.6 kW input, 37 kVA), I_N 63 A, 29 % loaded, V_d 1.07 %, I_f 777/315 A
37 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 66.1 A (38.9 kW input, 46 kVA), I_N 80 A, 36 % loaded, V_d 1.32 %, I_f 777/400 A
45 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 80.4 A (47.4 kW input, 56 kVA), I_N 100 A, 44 % loaded, V_d 1.60 %, I_f 777/500 A
55 kW ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS 98.3 A (57.9 kW input, 68 kVA), I_N 100 A, 54 % loaded, V_d 1.96 %, I_f 777/500 A
75 kW ✓ ✓ ✓ ✗ ✓ ✓ ✓ FAIL 134.1 A (78.9 kW input, 93 kVA), I_N 160 A, 74 % loaded, V_d 2.67 %, I_f 777/800 A
Parameter Symbol Value Notes
90 kW ✓ ✓ ✓ ✗ ✗ ✓ ✓ FAIL 160.9 A (94.7 kW input, 111 kVA), I_N 200 A, 88 % loaded, V_d 3.20 %, I_f 777/1,000 A
110 kW ✗ ✓ ✓ ✗ ✗ ✓ ✓ FAIL 196.6 A (115.8 kW input, 136 kVA), I_N 200 A, 108 % loaded, V_d 3.91 %, I_f 777/1,000 A

10. Summary of Results

Permissible load envelope for the selected cable:
Parameter Symbol Value Notes
Cable 50 mm² Cu XLPE earth 16 mm², 100 m
Derated Capacity IZ 182.0 A
Capacity-Limited Load Current IL,CCC 182.0 A, design factor 1
Voltage-Drop-Limited Load Current IL,VD 251.3 A, 5.0 % limit
Earth Fault Current Ifault 777 A
Largest Device Rating IN,max 125 A preferred rating; theoretical limit 155.4 A, earth fault loop (I_N ≤ I_fault / k_mag)
Protection-Limited Load Current IL,prot 125.0 A
Short Circuit Withstand tmax 0.511 s vs 0.1 s protection time: PASS
Earth Conductor Size Searth 16 mm² vs Table 5.1 minimum 16 mm²: PASS
Earth Conductor Withstand Smin 3.23 mm² for I<sub>ef</sub> 2,309 A in t<sub>ef</sub> 0.04 s (t<sub>max</sub> 0.982 s): PASS
Permissible Load Current IL,max 125.0 A, governed by Earth Fault Loop (I_N ≤ I_fault / k_mag)
Permissible Load Power Pmax 73.6 kW at PF 0.85
Permissible Motor Output Pmotor 69.9 kW shaft output at η 95 %
Permissible Apparent Power Smax 86.6 kVA
Conforming Loads in Table 14 of 17 largest 55 kW

11. Overall Assessment

OVERALL STATUS: ✓ PASS - the cable may supply up to 125.0 A (73.6 kW at PF 0.85) protected by a device of up to 125 A

12. Warnings & Recommendations

Warnings: Power loss (3.15%) is significant Recommendations: The earth fault loop limits the device rating: a larger earth conductor or a lower instantaneous trip multiplier raises the permissible load Consider larger conductor to reduce energy losses

13. Standards Compliance

Selected cable-table basis: AS/NZS 3008.1.1:2017. Other referenced design standards: AS/NZS 3000:2018 (Clause 2.5.3.1, Table 5.1) and IEC 60364. Preferred device ratings per AS/NZS 60898, AS/NZS 60947.2 and AS 60269; preferred motor ratings per IEC 60072.

Approval:

This calculation has been reviewed and approved by:
Created By
Engineer Name
Date: ..........................
Checked
By: .............................
Date: ..........................
Approved
By: .............................
Date: ..........................