| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| AS/NZS 3008 Edition | 2017 | The only supported edition | |
| Power Factor Direction | lagging | Controls the sign of the reactive voltage component | |
| Supply Voltage | Vpp | 400 V | Phase-to-phase voltage |
| Design Factor | kdesign | 1 | Design margin multiplier |
| Cable Length | L | 100 Meter | Cable run length |
| Length Unit | Meter | Length measurement unit | |
| Max Voltage Drop | Vd,max | 5 % | Maximum allowable |
| Motor Efficiency | η | 95 % | kW load table only: IEC 60072 ratings are shaft output, I = P / (√3 V PF η) |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Cable Type | Fixed | Cable construction | |
| Cable Formation | Multicore | Multicore or Singlecore | |
| Conductor Size | A | 50 | Phase conductor CSA |
| MC Arrangement | Circular | Conductor arrangement | |
| Cable Insulation | XLPE | Insulation type | |
| Conductor Material | Material | Cu | Cu or Al |
| Earth Conductor | 16 | Earth conductor CSA |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Installation Method | Unenclosed | ||
| Unenclosed Type (MC) | Spaced from Surface | ||
| Air Arrangement | Perforated Trays Horizontal | ||
| Cables Per Tier | 1 | ||
| Ladder Spacing | Spaced | ||
| Ladder Tiers | 1Tier | ||
| Air Ambient Temp | 40 | ||
| Cables per Tier | 1 |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Prospective Fault Current | If | 10 kA | Maximum fault current |
| CB Clearance Time | tprot | 100 ms | Protection device time |
| Earth Fault Clearing Time | tef | 40 ms | Near-end earth fault (earth withstand) |
| Instantaneous Trip Multiplier | kmag | 5 | Magnetic trip factor |
| Source Impedance | Zsource | 100 mΩ | Upstream impedance |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Table 24 | $$F_{ladder}$$ | 1 | Table 24 (Col: Row 10, Row: 1) |
| Table 27(1) | $$F_{temp}$$ | 1 | Table 27(1) (Col: Row 90, Row: 40) |
Combined derating factor from applicable AS/NZS 3008 tables:
Base current rating adjusted for installation conditions: Ref: Table 14, Column 2, Row: 50mm²
The design current (load current times the design factor) may not exceed the derated capacity:
Signed AS/NZS 3008 impedance for the load power factor (lagging adds the reactive term): Rc Ref: Table 35, Column 5, Row: 50mm². Xc Ref: Table 30, Column 10, Row: 50mm².
Largest load current whose design current keeps the drop within the limit:
k-factor = 143.0 for Cu XLPE
Minimum conductor size for the fault: S_min = 22.1 mm².
AS/NZS 3000:2018 Table 5.1 minimum for a 50 mm² phase conductor: 16 mm².
A fault at the supply end of the cable is limited only by the source impedance, so the near-end fault gives the largest earth-fault current:
Adiabatic equation with t_ef the earth-fault clearing time (input): k = 143 from AS/NZS 3008.1.1:2017 Table 52 (initial 90 °C, final 250 °C) for Cu XLPE. The earth is an integral core of the same cable, so it starts at the insulation's operating temperature and ends at the same final temperature as the phase conductors: it shares their k.
Withstand time of the earth conductor: t_max = (k S_earth / I_ef)² = 0.982 s against an earth-fault clearing time of 0.04 s.
Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).
Earth conductor 16 mm²: R_e from Tables 34/35 and X_e from AS/NZS 3008.1.1:2017 Table 30 at 16 mm² (multicore, circular), read with the phase cable's arrangement. Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).
The magnitudes are added arithmetically, an upper bound on the phasor sum.
The device must see at least its instantaneous trip current, I_fault >= I_N x k_mag:
Limited by the earth fault loop (I_N ≤ I_fault / k_mag). Largest preferred rating (AS/NZS 60898 / 60947.2 / AS 60269) not exceeding this: 125 A.
With the largest preferred device, the design current may not exceed the device rating:
Governing limit: Earth Fault Loop (I_N ≤ I_fault / k_mag). Design current at this load: 125.0 A.
Apparent power S_max = 86.6 kVA. Power loss at this load: 2,316 W (3.15 %).
P_max is electrical input; the largest motor (IEC 60072 shaft rating) it supplies is lower by the efficiency:
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| 1.5 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 2.7 A (1.6 kW input, 2 kVA), I_N 6 A, 1 % loaded, V_d 0.05 %, I_f 777/30 A |
| 2.2 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 3.9 A (2.3 kW input, 3 kVA), I_N 6 A, 2 % loaded, V_d 0.08 %, I_f 777/30 A |
| 3 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 5.4 A (3.2 kW input, 4 kVA), I_N 6 A, 3 % loaded, V_d 0.11 %, I_f 777/30 A |
| 4 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 7.1 A (4.2 kW input, 5 kVA), I_N 10 A, 4 % loaded, V_d 0.14 %, I_f 777/50 A |
| 5.5 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 9.8 A (5.8 kW input, 7 kVA), I_N 10 A, 5 % loaded, V_d 0.20 %, I_f 777/50 A |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| 7.5 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 13.4 A (7.9 kW input, 9 kVA), I_N 16 A, 7 % loaded, V_d 0.27 %, I_f 777/80 A |
| 11 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 19.7 A (11.6 kW input, 14 kVA), I_N 20 A, 11 % loaded, V_d 0.39 %, I_f 777/100 A |
| 15 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 26.8 A (15.8 kW input, 19 kVA), I_N 32 A, 15 % loaded, V_d 0.53 %, I_f 777/160 A |
| 18.5 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 33.1 A (19.5 kW input, 23 kVA), I_N 40 A, 18 % loaded, V_d 0.66 %, I_f 777/200 A |
| 22 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 39.3 A (23.2 kW input, 27 kVA), I_N 40 A, 22 % loaded, V_d 0.78 %, I_f 777/200 A |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| 30 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 53.6 A (31.6 kW input, 37 kVA), I_N 63 A, 29 % loaded, V_d 1.07 %, I_f 777/315 A |
| 37 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 66.1 A (38.9 kW input, 46 kVA), I_N 80 A, 36 % loaded, V_d 1.32 %, I_f 777/400 A |
| 45 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 80.4 A (47.4 kW input, 56 kVA), I_N 100 A, 44 % loaded, V_d 1.60 %, I_f 777/500 A |
| 55 kW | ✓ ✓ ✓ ✓ ✓ ✓ ✓ | PASS | 98.3 A (57.9 kW input, 68 kVA), I_N 100 A, 54 % loaded, V_d 1.96 %, I_f 777/500 A |
| 75 kW | ✓ ✓ ✓ ✗ ✓ ✓ ✓ | FAIL | 134.1 A (78.9 kW input, 93 kVA), I_N 160 A, 74 % loaded, V_d 2.67 %, I_f 777/800 A |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| 90 kW | ✓ ✓ ✓ ✗ ✗ ✓ ✓ | FAIL | 160.9 A (94.7 kW input, 111 kVA), I_N 200 A, 88 % loaded, V_d 3.20 %, I_f 777/1,000 A |
| 110 kW | ✗ ✓ ✓ ✗ ✗ ✓ ✓ | FAIL | 196.6 A (115.8 kW input, 136 kVA), I_N 200 A, 108 % loaded, V_d 3.91 %, I_f 777/1,000 A |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Cable | 50 mm² Cu XLPE | earth 16 mm², 100 m | |
| Derated Capacity | IZ | 182.0 | A |
| Capacity-Limited Load Current | IL,CCC | 182.0 | A, design factor 1 |
| Voltage-Drop-Limited Load Current | IL,VD | 251.3 | A, 5.0 % limit |
| Earth Fault Current | Ifault | 777 | A |
| Largest Device Rating | IN,max | 125 | A preferred rating; theoretical limit 155.4 A, earth fault loop (I_N ≤ I_fault / k_mag) |
| Protection-Limited Load Current | IL,prot | 125.0 | A |
| Short Circuit Withstand | tmax | 0.511 | s vs 0.1 s protection time: PASS |
| Earth Conductor Size | Searth | 16 | mm² vs Table 5.1 minimum 16 mm²: PASS |
| Earth Conductor Withstand | Smin | 3.23 | mm² for I<sub>ef</sub> 2,309 A in t<sub>ef</sub> 0.04 s (t<sub>max</sub> 0.982 s): PASS |
| Permissible Load Current | IL,max | 125.0 | A, governed by Earth Fault Loop (I_N ≤ I_fault / k_mag) |
| Permissible Load Power | Pmax | 73.6 | kW at PF 0.85 |
| Permissible Motor Output | Pmotor | 69.9 | kW shaft output at η 95 % |
| Permissible Apparent Power | Smax | 86.6 | kVA |
| Conforming Loads in Table | 14 of 17 | largest 55 kW |