Cable Volt Drop Table

Maximum cable length reference matrix based on running voltage drop per AS/NZS 3008.1.1:2017.

1. Input Parameters

System parameters for voltage drop matrix:
Parameter Symbol Value Notes
Cable Insulation XLPE (X-90) Rated conductor temperature 90 °C selects the Vc column
System Voltage V 415 V Line-to-line voltage
Max Voltage Drop Vd% 5 % Running voltage drop limit
Parallel Cables P 1 0.9 derating if > 1
Max Display Length L_max 10 km Display cap for matrix

2. Voltage Drop Formula

Maximum cable length for a given motor and cable combination: Where: L = max cable length (m), Vd% = voltage drop as decimal, V = system voltage (V), P = parallel cables, I = full load current at V (A) = I_415 × 415 / V, Vc = three-phase voltage drop factor (mV/A.m), AS/NZS 3008.1.1:2017 Table 42 Column 8 (Cu multicore circular, 90 °C, maximum value)

Formula: $$ \begin{aligned} L &= \frac{V_{d\%} \times V \times 1000 \times P}{I \times V_c} \\ &= \frac{0.05 \times 415 \times 1000 \times 1}{I \times V_c} \end{aligned} $$

3. Cable Data Reference (Cu Multicore, 3-Phase)

Voltage drop factors from AS/NZS 3008.1.1:2017 Table 42 Column 8 (Cu multicore circular, 90 °C, maximum value) and the indicative derated current ratings:
Parameter Symbol Value Notes
2.5 mm² Vc 16.4 mV/A.m CCC: 33 A
4 mm² Vc 10.2 mV/A.m CCC: 44 A
6 mm² Vc 6.8 mV/A.m CCC: 56 A
10 mm² Vc 4.05 mV/A.m CCC: 74 A
16 mm² Vc 2.55 mV/A.m CCC: 98 A
25 mm² Vc 1.61 mV/A.m CCC: 131 A
35 mm² Vc 1.17 mV/A.m CCC: 162 A
50 mm² Vc 868 mmV/A.m CCC: 197 A
70 mm² Vc 609 mmV/A.m CCC: 251 A
95 mm² Vc 450 mmV/A.m CCC: 302 A
120 mm² Vc 366 mmV/A.m CCC: 349 A
150 mm² Vc 307 mmV/A.m CCC: 393 A
185 mm² Vc 259 mmV/A.m CCC: 454 A
240 mm² Vc 216 mmV/A.m CCC: 532 A
300 mm² Vc 190 mmV/A.m CCC: 601 A
400 mm² Vc 171 mmV/A.m CCC: 686 A
500 mm² Vc 158 mmV/A.m CCC: 780 A

4. Summary Statistics

Total combinations: 578 Valid combinations: 282 N/A (cable undersized): 224 Exceeds max display: 72

5. Notes

- Vc per AS/NZS 3008.1.1:2017 Table 42 Column 8 (Cu multicore circular, 90 °C, maximum value): every cable is taken at the 90 °C rated temperature of XLPE (X-90) insulation (fully loaded) - Current screen uses the component's indicative derated ratings (one fixed installation condition) - 0.9 parallel derating factor applied when cables > 1 - Running voltage drop only (not startup) - Motor FLC values are tabulated at 415 V, 3-phase, and scaled by 415 / V to the system voltage - Full 34×17 matrix available in interactive view

Approval:

This calculation has been reviewed and approved by:
Created By
Engineer Name
Date: ..........................
Checked
By: .............................
Date: ..........................
Approved
By: .............................
Date: ..........................
Client Approved
By: .............................
Date: ..........................