CURRENT TRANSFORMER (CT) SELECTION & SIZING

IEC 60044-1 / IEC 61869-2 - Current Transformer Suitability Assessment This calculation verifies CT suitability for protection applications through: 1. BURDEN ANALYSIS - VA load must not exceed CT rated burden 2. ALF VERIFICATION - Accuracy Limit Factor ensures accuracy during faults 3. SATURATION CHECK - Knee point voltage prevents core saturation 4. RATIO SELECTION - Optimal ratio for nominal current **Protection CT Classes:** * 5P/10P - 5% or 10% composite error at accuracy limit * ALF Suffix (5, 10, 20) - Current multiple maintaining accuracy * PX/TPX/TPS - Special classes for differential protection

1. INPUT PARAMETERS

System parameters and CT specifications for suitability assessment.
Parameter Symbol Value Notes
Nominal Primary Current Inom 50 A Load nominal current
Maximum Fault Current Ifault 5 kA From fault study
System Voltage VLL 415 V Line-to-line
CT Ratio 50:5 n = 10.0
CT Accuracy Class 5P10 ALF = 10x
CT Rated Burden VArated 10 VA CT nameplate rating
CT Knee Point Voltage Vk Not specified From datasheet
Cable Length L 20 m One-way distance
Conductor Area A 2.5 mm2 Cable cross-section
Relay Burden VArelay 500 mVA Relay/meter burden

2. CT TRANSFORMATION RATIO

The CT ratio determines the relationship between primary and secondary currents.

2.1 CT Ratio Calculation

CT Ratio: 50:5 CT Class: 5P10 (Accuracy Limit Factor = 10x) The ALF defines the current multiple at which the CT maintains specified accuracy. Beyond this point, the CT may saturate.

Formula: $$ n = \frac{I_{primary}}{I_{secondary}} = \frac{50}{5} = 10 $$

3. SECONDARY CIRCUIT RESISTANCE

The total secondary circuit resistance includes cable, relay, and CT internal resistance.

3.1 Resistance Calculations

Where: * rho(75.0C) = 0.020968 Ohm*mm2/m (copper @ 75.0C) * L = 20.0 m (one-way length) * A = 2.5 mm2 R_cable = 0.335482 Ohm (94.4% of total) R_relay = 0.020000 Ohm (5.6% of total) R_CT = 0.000000 Ohm (0.0% of total)

Formula: $$ R_{cable} = \frac{\rho(T) \times 2L}{A} $$

Cable resistance typically dominates for long cable runs. Use larger conductor area to reduce cable resistance.

Formula: $$ R_{total} = R_{cable} + R_{relay} + R_{CT} = 0.335482 + 0.020000 + 0.000000 = 0.355482 \text{ Ohm} $$

4. BURDEN ANALYSIS - PASS

The burden represents power consumed by the secondary circuit. It must not exceed the CT rated VA.

4.1 Burden Calculation

**Burden Assessment:** * CT Rated Burden: 10.0 VA * Actual Burden: 8.887 VA * Utilization: 88.9% * Margin: 1.113 VA **Result: PASS** Actual burden is within CT rated burden. Recommended: 50-80% utilization for safety margin.

Formula: $$ VA_{actual} = I_{sec}^2 \times R_{total} = 5^2 \times 0.355482 = 8.887 \text{ VA} $$

6. FAULT CURRENT ANALYSIS

STEP 7: FAULT CURRENT TRANSFORMATION TO SECONDARY During fault conditions, the CT must accurately reproduce the fault current on the secondary side without saturating. Fault Multiple Calculation (IEC 60044-1 cl. 3.4.202): Fault_Multiple = I_fault / I_rated_primary Where: I_fault = 5,000 A (maximum fault current from fault study) I_rated_primary = 50.0 A (CT rated primary current) Calculation: Fault_Multiple = 5,000 / 50.0 Fault_Multiple = 100.0x This indicates the fault current is 100.0 times the CT rated primary current. --- STEP 8: SECONDARY FAULT CURRENT The secondary fault current is determined by the CT ratio: Formula: I_sec_fault = I_fault / n Where: I_fault = 5,000 A n = 10.0 (CT ratio factor) Calculation: I_sec_fault = 5,000 / 10.0 I_sec_fault = 500.0 A The secondary circuit will experience 500.0 A during maximum fault. --- STEP 9: REQUIRED SECONDARY VOLTAGE DURING FAULT The voltage required to drive the fault current through the secondary circuit resistance determines saturation risk: Formula: V_required = I_sec_fault x R_total Where: I_sec_fault = 500.0 A R_total = 0.355482 Ohm Calculation: V_required = 500.0 x 0.355482 V_required = 177.7 V CRITICAL REQUIREMENT: This voltage MUST be less than the CT knee-point voltage (Vk) to prevent core saturation during fault conditions. If V_required > Vk: * The CT core will saturate * Secondary current will be distorted * Protection relay may fail to detect fault correctly * Relay operating time will be extended (dangerous!) VOLTAGE BUDGET ANALYSIS: * Required Secondary Voltage: 177.7 V * CT Knee Point Voltage: Not specified * Utilization: Cannot calculate (Vk not specified)

7. ACCURACY LIMIT FACTOR (ALF) VERIFICATION - FAIL

STEP 10: ALF COMPLIANCE CHECK The Accuracy Limit Factor (ALF) defines the maximum current multiple at which the CT maintains its specified accuracy. Per IEC 60044-1: * The CT is guaranteed to have <= specified composite error up to (ALF x rated primary current) * Beyond ALF, the CT may saturate and produce errors > specified limit Verification Formula: Fault_Multiple <= ALF Values: Fault_Multiple = 100.0x ALF = 10x (from CT class 5P10) Check: 100.0 <= 10? UNACCEPTABLE Margin: -90.0x (Negative margin - INADEQUATE!) --- ALF INTERPRETATION: For CT class 5P10: * Rated primary current: 50.0 A * Accuracy maintained up to: 500 A (10x rated) * Maximum fault current: 5,000 A COMPOSITE ERROR DEFINITION: The composite error combines: * Ratio error (deviation from ideal transformation ratio) * Phase displacement (angular error between primary and secondary) For 5P10 class: * Composite error <= 5% at 10x rated current WARNING: ALF EXCEEDED! The fault current exceeds the CT's accuracy limit. Possible consequences: * CT may saturate during fault * Protection relay may malfunction * Fault clearance time may be extended * Equipment damage risk increased CORRECTIVE ACTIONS (if ALF check fails): * Option 1: Specify higher ALF class (e.g., 5P20 instead of 5P10) * Option 2: Increase CT ratio to 100:5.0 (adjust relay settings) * Option 3: Use PX/TPX class with higher knee-point voltage * Option 4: Review fault study - verify maximum fault current

8. KNEE POINT VOLTAGE CHECK - DATA NOT AVAILABLE

STEP 11: KNEE POINT VOLTAGE NOT PROVIDED The CT knee-point voltage (V_k) has not been specified. This parameter is essential for accurate saturation assessment. Required Secondary Voltage: 177.7 V Estimated Saturation Risk: HIGH ESTIMATION METHOD (without V_k): Rule of thumb for protection CTs: * 5P class at rated VA: V_k ~ 75-150 V (typical range) * 10P class at rated VA: V_k ~ 50-100 V (typical range) * PX class: V_k >= 200 V (manufacturer specified) Saturation Risk Estimation: * V_required < 50 V: LOW risk (typical) * V_required 50-150 V: MEDIUM risk (verify from datasheet) * V_required > 150 V: HIGH risk (likely saturation) For this application: * Required voltage: 177.7 V * Estimated risk: HIGH IMPORTANT - ACTION REQUIRED: Obtain the CT knee-point voltage from: 1. Manufacturer's datasheet (most reliable) 2. Excitation curve (V_k is at 10%V -> 50%I point) 3. Type test report (if available) 4. Factory test certificate Cannot accurately verify CT suitability without V_k! INTERIM RECOMMENDATION: Specify minimum V_k requirement in procurement: * Minimum V_k >= 267 V (with 50% margin) * Recommended V_k >= 355 V (with 100% margin) For critical protection applications: * Specify Class PX with minimum V_k * Request excitation curves from manufacturer * Perform acceptance testing to verify V_k

9. OVERALL SUITABILITY ASSESSMENT

STEP 12: OVERALL CT SUITABILITY ASSESSMENT Overall Status: NOT SUITABLE --- DETAILED SUITABILITY CHECKS: PASS - Burden Check VA burden (8.89 VA) ≤ CT rated VA (10.0 VA) FAIL - ALF Check Fault multiple (100.0×) exceeds ALF (10×) WARNING - Knee Point Check Knee point not provided. Required voltage: 177.7 V --- SUITABILITY CRITERIA SUMMARY: For a CT to be suitable for protection application: Burden Check: VA_actual <= VA_rated - Ensures CT operates within thermal limits - Maintains specified accuracy ALF Check: Fault_Multiple <= ALF - Ensures accuracy during fault conditions - Prevents saturation up to rated fault current Knee Point Check: V_required <= V_k - Prevents core saturation - Ensures linear operation during faults CT SUITABILITY ASSESSMENT: NOT SUITABLE One or more critical checks have FAILED. This CT should NOT be used for this application without modifications. Review the recommendations below for corrective actions.

10. WARNINGS & RECOMMENDATIONS

WARNINGS: The following warnings have been identified: 1. Verify knee-point voltage from CT datasheet 2. Cable resistance dominates burden - consider shorter cable run or larger conductor --- RECOMMENDATIONS: Consider the following options to improve CT suitability: 1. Use higher ALF class (e.g., 5P20) or increase CT ratio 2. Option 2: Use CT with ALF ≥ 100 (e.g., 5P20) 3. Option 3: Increase CT ratio to 100:5 (adjust relay settings) --- GENERAL RECOMMENDATIONS FOR CT SELECTION: Burden Optimization: * Minimize cable length where possible * Use adequate conductor size (2.5mm2 minimum for 5A secondary) * Select modern digital relays (low burden < 0.5 VA) * Consider 1A secondary for long cable runs (1/25th the burden) Protection Class Selection: * Overcurrent/earth fault: 5P10 or 5P20 typically adequate * Differential protection: Class PX or TPX preferred * High fault current systems: Use 5P20 or PX class * Generator protection: TPX or TPS class for stability Ratio Selection: * Choose next standard ratio above nominal current * Typical guideline: I_primary = (1.2 to 1.5) x I_nominal * For motors: Consider 1.25 x I_FLC as minimum * For feeders: Consider load growth and diversity Specification Best Practices: * Always specify minimum knee-point voltage * Request excitation curves from manufacturer * Specify maximum secondary winding resistance * Include acceptance testing requirements * Verify accuracy class and ALF in datasheet

11. CT RATIO SELECTION RECOMMENDATION

STEP 13: CT RATIO SELECTION RECOMMENDATION Optimal CT ratio selection balances: * Adequate range for maximum fault current * Sufficient sensitivity at nominal current * Standard available ratios Selection Guideline: Choose the next standard ratio above nominal current. Your System: * Nominal Current: 50.0 A * Current CT Ratio: 50:5 * Recommended Ratio: 50:5 RATIO SELECTION: OPTIMAL The current CT ratio matches the recommended ratio. This provides good balance between sensitivity and range. Relay Sensitivity Check: * Nominal secondary current: 5.00 A * Minimum pickup setting: ~2.50 A (typical 50%) * Maximum fault secondary: 500.0 A Verify relay settings can accommodate this range. --- STANDARD CT RATIOS (5A Secondary): Low Current: * 5:5, 10:5, 15:5, 20:5, 25:5, 30:5, 40:5, 50:5 Medium Current: * 60:5, 75:5, 100:5, 150:5, 200:5, 250:5, 300:5, 400:5, 500:5 High Current: * 600:5, 750:5, 800:5, 1000:5, 1200:5, 1500:5, 2000:5 1A Secondary (for long cable runs): * 50:1, 100:1, 200:1, 500:1, 1000:1

12. CALCULATION SUMMARY & COMPLIANCE

CALCULATION SUMMARY Input Parameters: * Nominal Current: 50.0 A * Fault Current: 5,000 A (100.0x nominal) * CT Ratio: 50:5 (Class 5P10) * Secondary Circuit: 20.0m x 2.5mm2 + 0.5VA relay Key Results: * Secondary Burden: 8.887 VA (Rated: 10.0 VA) - PASS * Required Voltage: 177.7 V (Vk: Not specified) - N/A * ALF Compliance: Fault 100.0x vs ALF 10x - FAIL * Overall Status: NOT SUITABLE --- STANDARDS & REFERENCES International Standards: * IEC 60044-1 (2003) - Instrument transformers - Current transformers * IEC 61869-2 (2012) - Instrument transformers - Additional requirements for current transformers * IEC 60255 - Measuring relays and protection equipment Regional Standards: * AS 60044.1 (Australian adoption of IEC 60044-1) * IEEE C57.13 (American standard for instrument transformers) * BS 3938 (British standard for current transformers) Protection Standards: * IEC 60255-151 - Overcurrent protection * IEEE C37.91 - Guide for protective relay applications * ANSI/IEEE C37.110 - Guide for application of current transformers

CALCULATION RESULTS - CT NOT SUITABLE

Final assessment of CT suitability for this application. **Overall Result: NOT SUITABLE** One or more checks failed
Parameter Symbol Value Notes
Cable Resistance Rcable 335 mOhm @ 75.0C
Total Secondary Resistance Rtotal 355 mOhm Cable + relay + CT
Actual Burden VAactual 8.89 VA 88.9% of rated
Burden Check PASS Margin: 1.11 VA
Fault Multiple 100 x I<sub>fault</sub> / I<sub>rated,primary</sub>
Required Voltage (Fault) Vreq 178 V During fault
ALF Check FAIL Fault multiple vs ALF
Saturation Check N/A V<sub>req</sub> vs V<sub>k</sub>
Overall Suitability NOT SUITABLE One or more checks failed