| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| System Voltage | Vsys | 48 V | DC nominal voltage |
| Continuous Current | Ic | 100 A | Maximum continuous current |
| Cable Length (One-way) | L | 3 m | One-way distance |
| Maximum Voltage Drop | Vd,max | 3 % | Percentage limit |
| Ambient Temperature | Tamb | 30 °C | Installation environment |
| Installation Method | — | Open Air (Clipped Direct) | Cable routing method |
The design current includes a safety factor for continuous loads.
Convert percentage limit to volts.
Resistivity varies with temperature. At 70 degrees C, the copper resistivity is adjusted from the 20 degrees C reference value.
For DC two-conductor circuit, voltage drop is V_d = 2 * rho * I * L / A. Solving for minimum cross-sectional area gives the formula above.<br><strong>Next standard size: 35 mm²</strong>
Conductor ampacity must be adjusted for installation conditions.<br><strong>Temperature Correction Factor (C<sub>t</sub>): 1.000</strong><br><strong>Grouping Factor (C<sub>g</sub>): 1.00</strong><br><strong>Installation Method Factor (C<sub>c</sub>): 1.00</strong>
Tabulated ampacity for 35 mm² conductor: <strong>148 A</strong><br>Adjusted ampacity with derating factors applied.<br><strong>Verification:</strong> I<sub>z</sub> (148.0 A) ≥ I<sub>d</sub> (125.0 A) — <span style="color: green;">PASS</span>
Conductor resistance per kilometer, voltage drop for two-conductor DC circuit, and voltage drop percentage.<br><strong>Verification:</strong> V<sub>d,%</sub> (0.92%) ≤ V<sub>d,max%</sub> (3%) — <span style="color: green;">PASS</span>
Power dissipated as heat in the cable, and as percentage of transmitted power.
<strong>Selected Conductor Size: 35 mm² Copper</strong><br>Insulation: XLPE (75°C rating)<br>Installation: Open Air (Clipped Direct)<br>Voltage Drop: 0.92% (Max: 3%) — Margin: 2.08%<br>Ampacity: 148.0 A (Design: 125.0 A) — Margin: 15.5%<br>Compliance: <strong style="color: green;">COMPLIANT</strong>
The cable sizing diagram illustrates the DC circuit layout showing conductor size, voltage drop, and current capacity for the selected cable.
Figure 1: DC cable sizing diagram
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Design Current | Id | 125 A | With 1.25× safety factor |
| Selected Conductor Size | A | 35 mm² | Copper conductor |
| Actual Voltage Drop | Vd | 0.921 % | 0.442 V |
| Adjusted Ampacity | Iz | 148 A | With all derating factors |
| Power Loss | Ploss | 55.3 W | 0.92% of transmitted power |
| Conductor Resistance | R | 589 mΩ/km | At 70°C |
Scan this QR code with your mobile device to view the calculation online.