Input Parameters

The following design parameters were considered for this earth fault loop impedance calculation:
Parameter Symbol Value Notes
Cable Length L 50 m Main cable run
Active Conductor CSA CSAactive 4 Phase conductor
Earth Conductor CSA CSAearth 4 Protective conductor
Nominal Voltage Uo 230 V Phase to earth voltage
Breaker Rating In 32 A Circuit breaker nominal current
Trip Curve Multiplier k 7.5 Type C curve

Calculations

All calculations were performed in accordance with IEC 60364 and BS 7671 standards.

Cable Loop Impedance

The cable impedance is calculated from the active and earth conductor impedances: This represents the impedance of the cable between the source and the fault location.

Formula: $$ \begin{aligned} Z_{cable} &= \sqrt{R^2 + X^2} \\ &= \sqrt{(0.561)^2 + (0.0102)^2} \\ &= 0.561 \; \Omega \end{aligned} $$

Trip Current Calculation

The required trip current is calculated using: This is the minimum current required to operate the protective device.

Formula: $$ \begin{aligned} I_a &= I_n \times \text{Trip Multiplier} \\ &= 32 \times 7.5 \\ &= 240 \; \text{A} \end{aligned} $$

Maximum Allowed Impedance

The maximum earth fault loop impedance is calculated using: This is the maximum impedance that allows proper operation of the protective device.

Formula: $$ \begin{aligned} Z_{max} &= \frac{U_o}{I_a} = \frac{U_o}{I_n \times \text{Trip Multiplier}} \\ &= \frac{230}{32 \times 7.5} \\ &= 0.958 \; \Omega \end{aligned} $$

Total Earth Fault Loop Impedance (Zs)

The total earth fault loop impedance is the sum of source and cable impedances: This is the actual impedance of the complete earth fault loop path.

Formula: $$ \begin{aligned} Z_s &= Z_t + Z_{cable} \\ &= 0 + 0.561 \\ &= 0.561 \; \Omega \end{aligned} $$

Compliance Check

The calculated earth fault loop impedance Zs = 0.5610 Ω is less than the maximum allowed Zmax = 0.9583 Ω. The installation complies with the requirements.

Summary of Results

Below is the summary of calculated values for ease of reference:
Parameter Symbol Value Notes
Trip Current Ia 240 A Required tripping current
Cable Loop Impedance Zcable 561 mΩ Active + Earth conductor impedance
Total Earth Fault Loop Impedance Zs 561 mΩ Measured/calculated impedance
Maximum Allowed Impedance Zmax 958 mΩ For proper protection operation
Compliance Status Status PASS Circuit complies with requirements

Approval:

This calculation has been reviewed and approved by:
Created By
Engineer Name
Date: ..........................
Checked
By: .............................
Date: ..........................
Approved
By: .............................
Date: ..........................
Client Approved
By: .............................
Date: ..........................

Scan to View Online

Scan this QR code with your mobile device to view the calculation online.

Scan to access this calculation from any device