| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Soil Resistivity | \rho | 100 Ω·m | Measured soil resistivity |
| Fault Current | I_f | 10 kA | Maximum grid fault current |
| Clearing Time | t_s | 500 ms | Fault clearing time |
| Grid Length | L | 60 m | |
| Grid Width | W | 40 m | |
| Conductor Spacing | D | 6 m | |
| Burial Depth | h | 500 mm | |
| Conductor Diameter | d | 12.8 mm | Copper, annealed soft-drawn |
| Ground Rods | n_r | 20 | 3.0m each |
| Surface Resistivity | \rho_s | 3 kΩ·m | Crushed rock layer |
| Surface Thickness | h_s | 100 mm | |
| Body Weight | 70 kg | Cb = 0.157 |
Derating factor for high-resistivity surface layer (IEEE 80 eq. 27):
Number of conductors and total horizontal length: Total length with rods: LT = 920.0 m
Grid resistance, IEEE 80-2013 Eq. 57 (Sverak); the depth factor applies to the area term only:
Maximum allowable touch voltage for 70kg body (IEEE 80 eq. 32):
Maximum allowable step voltage for 70kg body (IEEE 80 eq. 29):
Geometric spacing factor for mesh voltage (IEEE 80 eq. 81):
Geometric spacing factor for step voltage (IEEE 80 eq. 83):
Correction factor for grid irregularity (IEEE 80 eq. 89):
Maximum mesh (touch) voltage at grid surface (IEEE 80 eq. 80):
Maximum step voltage at grid perimeter (IEEE 80 eq. 84):
Maximum ground potential rise during fault:
IEEE 80-2013 Eq. 37 with the Table 1 constants for Copper, annealed soft-drawn (fusing temperature 1083 °C). Joint type Bolted / pressure-type (incl. compression) connector: Tm = min(250, 1083) = 250 °C: Selected standard size: 50 mm²