| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| AS/NZS 3008 Edition | 2017 | The only supported edition | |
| Power Factor Direction | lagging | Controls the sign of the reactive voltage component | |
| Specify By | Power Rating | Input mode | |
| Load Power | P | 90 kW | Rated load power |
| Power Unit | kW | Power measurement unit | |
| Supply Voltage | Vpp | 400 V | Phase-to-phase voltage |
| Power Factor | PF | 0.85 | cos(φ) |
| Load Type | General Load | Type of load | |
| Design Factor | kdesign | 1 | Design margin multiplier |
| Cable Length | L | 100 Meter | Cable run length |
| Length Unit | Meter | Length measurement unit | |
| Max Voltage Drop | Vd,max | 5 % | Maximum allowable |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Sizing Mode | Manual | Cable sizing approach | |
| Cable Type | Fixed | Cable construction | |
| Cable Formation | Multicore | Multicore or Singlecore | |
| Conductor Size | A | 50 | Phase conductor CSA |
| MC Arrangement | Circular | Conductor arrangement | |
| Cable Insulation | XLPE | Insulation type | |
| Conductor Material | Material | Cu | Cu or Al |
| Earth Conductor | 50 | Earth conductor CSA |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Installation Method | Unenclosed | ||
| Unenclosed Type (MC) | Spaced from Surface | ||
| Air Arrangement | Perforated Trays Horizontal | ||
| Cables Per Tier | 1 | ||
| Ladder Spacing | Spaced | ||
| Ladder Tiers | 1Tier | ||
| Air Ambient Temp | 40 | ||
| Cables per Tier | 1 |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Prospective Fault Current | If | 10 kA | Maximum fault current |
| CB Clearance Time | tprot | 100 ms | Protection device time |
| Earth Fault Clearing Time | tef | 40 ms | Near-end earth fault (earth withstand) |
| Protection Device Rating | Itrip | 100 A | CB rating |
| Instantaneous Trip Multiplier | kmag | 5 | Magnetic trip factor |
| Source Impedance | Zsource | 100 mΩ | Upstream impedance |
Three-phase load current from rated power: This is the continuous operating current for which the cable must be sized.
Design current with factor k_design = 1.0: Design current accounts for load growth and safety margin.
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Table 24 | $$F_{ladder}$$ | 1 | Table 24 (Col: Row 10, Row: 1) |
| Table 27(1) | $$F_{temp}$$ | 1 | Table 27(1) (Col: Row 90, Row: 40) |
Combined derating factor from applicable AS/NZS 3008 tables:
Base current rating adjusted for installation conditions: Ref: Table 14, Column 2, Row: 50mm²
Check if derated capacity meets or exceeds design current:
Cable utilization as a percentage of derated capacity:
Calculate cable impedance from resistance and reactance: Rc Ref: Table 35, Column 5, Row: 50mm². Values from AS/NZS 3008 impedance tables.
Three-phase voltage drop at the design current I_B = I_load × k_design (152.8 A), the same current the capacity and device checks use: Absolute voltage drop in volts. Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).
Express voltage drop as percentage of supply voltage: Compared against maximum allowable limit.
Check if voltage drop is within acceptable limits:
Three-phase cable resistive power loss:
Power loss as percentage of transmitted power: Power loss: 3461.4 W (3.85%)
Maximum fault withstand time from k-factor and conductor area: k-factor = 143.0 for Cu XLPE
Check if cable can withstand fault for protection operating time:
Minimum conductor cross-sectional area to withstand the fault:
Check if selected conductor meets minimum size requirement:
Active conductor impedance over the cable length: Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).
Protective earth conductor impedance, resistance and reactance at the earth size: R_e from Tables 34/35 and X_e from AS/NZS 3008.1.1:2017 Table 30 at 50 mm² (multicore, circular), read with the phase cable's arrangement. Resistances are read at the insulation operating temperature (PVC 75 °C, XLPE 90 °C, EPR 110 °C; aluminium capped at 90 °C).
Sum of source, phase cable, and earth cable impedances: The magnitudes are added arithmetically, an upper bound on the phasor sum. Total impedance determines fault current magnitude.
Fault current from phase-to-earth voltage and loop impedance: Must exceed magnetic trip threshold of protection device.
Maximum cable length that still meets earth fault protection (same loop model, per-km impedances): z_phase and z_earth are the phase and earth impedances in Ω/km.
Check if actual cable length is within maximum:
Check if fault current will reliably trip protection:
Design current, device rating and derated cable capacity in ascending order: Device rating (100A) < Design current (152.8A)
Earth conductor against the AS/NZS 3000:2018 Table 5.1 minimum: The earth conductor meets the Table 5.1 minimum.
Phase-to-earth voltage over the source impedance (near-end fault): A fault further along the cable adds cable impedance and draws less current.
Adiabatic minimum cross-sectional area for the earth-fault clearing time: k = 143 from AS/NZS 3008.1.1:2017 Table 52 (Cu, initial 90 °C, final 250 °C); t_ef = 0.04 s (input).
Longest time the earth conductor can carry the earth-fault current:
Check the earth conductor against the adiabatic minimum: The earth conductor withstands the earth-fault current for the earth-fault clearing time.
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Load Current | Iload | 153 A | Full load current |
| Design Current | Idesign | 153 A | I_load × 1.0 |
| Base Current Rating | Ibase | 182 A | Ref: Table 14, Column 2, Row: 50mm² |
| Derated Capacity | Irated | 182 A | After derating factors |
| CCC Margin | ΔICCC | 29.2 A | Available capacity margin |
| Cable Impedance | Zc | 500 mΩ/km | Per kilometer |
| Voltage Drop | Vd | 12.2 V | Absolute voltage drop |
| Voltage Drop % | Vd% | 3.04 % | As percentage of supply |
| Max Withstand Time | tmax | 511 ms | Cable withstand capability |
| Protection Time | tprot | 100 ms | Device operating time |
| Loop Impedance | Zloop | 200 mΩ | Total earth fault loop |
| Fault Current | Ifault | 1.16 kA | Earth fault current |
| Device Rating | IN | 100 A | Overload protective device (I_B ≤ I_N ≤ I_Z) |
| Max Device Rating | IZ | 182 A | Derated cable capacity, the largest device the cable may have |
| Minimum Earth Conductor | Se,5.1 | 16 mm² | AS/NZS 3000:2018 Table 5.1 for a 50 mm² phase conductor |
| Earth-Fault Current at Origin | Ief | 2.31 kA | Largest earth-fault current, V_ph / Z_source |
| Earth Withstand Minimum | Se,min | 3.23 mm² | Adiabatic minimum earth size, I_ef√t_ef / k |
| Earth Max Withstand Time | te,max | 9.59 s | Earth conductor withstand at I_ef |