| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| AS/NZS 3008 Edition | 2017 | The only supported edition | |
| Power Factor Direction | lagging | Controls the sign of the reactive voltage component | |
| Specify By | Power Rating | Input mode | |
| Load Power | P | 5 kW | Rated load power |
| Power Unit | kW | Power measurement unit | |
| Supply Voltage | V | 230 V | Single-phase supply voltage |
| Power Factor | PF | 0.85 | cos(φ) |
| Load Type | General Load | Type of load | |
| Design Factor | kdesign | 1 | Design margin multiplier |
| Cable Length | L | 30 Meter | Cable run length |
| Length Unit | Meter | Length measurement unit | |
| Max Voltage Drop | Vd,max | 5 % | Maximum allowable |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Sizing Mode | Manual | Cable sizing approach | |
| Cable Type | Fixed | Cable construction | |
| Conductor Size | A | 16 | Phase conductor CSA |
| MC Arrangement | Circular | Conductor arrangement | |
| Cable Insulation | XLPE | Insulation type | |
| Conductor Material | Material | Cu | Cu or Al |
| Earth Conductor | 16 | Earth conductor CSA |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Installation Method | Unenclosed | ||
| Unenclosed Type | Spaced from Surface | ||
| Air Arrangement | Perforated Trays Horizontal | ||
| Cables Per Tier | 1 | ||
| Ladder Spacing | Spaced | ||
| Ladder Tiers | 1Tier | ||
| Air Ambient Temp | 40 | ||
| Cables per Tier | 1 |
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Prospective Fault Current | If | 10 kA | Maximum fault current |
| CB Clearance Time | tprot | 100 ms | Protection device time |
| Earth Fault Clearing Time | tef | 40 ms | Earth-conductor withstand: instantaneous operation, or upstream backup if relied on |
| Protection Device Rating | Itrip | 32 A | CB rating |
| Instantaneous Trip Multiplier | kmag | 5 | Magnetic trip factor |
| Source Impedance | Zsource | 100 mΩ | Upstream impedance |
Single-phase load current from rated power: This is the continuous operating current for which the cable must be sized.
Design current with factor k_design = 1.0: Design current accounts for load growth and safety margin.
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Table 24 | $$F_{ladder}$$ | 1 | Table 24 (Col: Row 10, Row: 1) |
| Table 27(1) | $$F_{temp}$$ | 1 | Table 27(1) (Col: Row 90, Row: 40) |
Combined derating factor from applicable AS/NZS 3008 tables:
Base current rating adjusted for installation conditions: Ref: Table 11, Column 2, Row: 16mm²
Check if derated capacity meets or exceeds design current:
Cable utilization as a percentage of derated capacity:
Calculate cable impedance from resistance and reactance: Rc Ref: Table 35, Column 5, Row: 16mm². Values from AS/NZS 3008 impedance tables.
Single-phase voltage drop at the design current I_B = 25.58 A (factor of 2 for go+return): Absolute voltage drop in volts.
Express voltage drop as percentage of supply voltage: Compared against maximum allowable limit.
Check if voltage drop is within acceptable limits:
I²R power loss in cable at the load current I_L (2 conductors for single-phase go+return):
Power loss as percentage of transmitted power:
Maximum fault withstand time from k-factor and conductor area: k-factor = 143.0 for Cu XLPE
Check if cable can withstand fault for protection operating time: Insufficient withstand: 0.052s < 0.1s
Minimum conductor cross-sectional area to withstand the fault:
Check if selected conductor meets minimum size requirement:
Earth conductor impedance from its resistance and reactance at the earth size: R_e = 1.47 Ω/km: AC resistance at 90 °C, the operating temperature of Cu XLPE cable. X_e = 0.0805 Ω/km: AS/NZS 3008.1.1:2017 Table 30 reactance at the 16 mm² earth size, same cable arrangement as the phase conductor.
Sum of source, phase cable, and earth cable impedances: Total impedance determines fault current magnitude.
Fault current from phase voltage and loop impedance (V_ph = V for single-phase): Must exceed magnetic trip threshold of protection device.
Maximum cable length that still meets earth fault protection: |z_phase| = |R_c + jX_c| and |z_earth| = |R_e + jX_e| per kilometre. Impedances are added as magnitudes, which gives a loop impedance no smaller than the phasor sum.
Check if actual cable length is within maximum:
Check if fault current will reliably trip protection:
Table 5.1 minimum earth conductor S_e,min = 6.0 mm²; earth conductor given S_e = 16.0 mm²: Earth conductor meets the Table 5.1 minimum.
Near-end earth fault current from supply voltage and source impedance: Cable impedance is zero at the origin, so this is the largest earth-fault current the earth conductor can see.
Adiabatic minimum for the earth-fault clearing time t_ef = 0.04 s, with k = 143 from AS/NZS 3008.1.1:2017 Table 52 (Cu, initial 90 °C, final 250 °C): The earth is an integral core of the same cable, so it starts at the insulation operating temperature and ends at the same final temperature as the phase conductor; it shares the phase conductor's Table 52 k.
Maximum time the earth conductor can carry the near-end earth fault current:
Check if the earth conductor meets the adiabatic minimum: Earth conductor can withstand the earth fault for the clearing time.
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Load Current | Iload | 25.6 A | Full load current |
| Design Current | Idesign | 25.6 A | I_load × 1.0 |
| Base Current Rating | Ibase | 104 A | Ref: Table 11, Column 2, Row: 16mm² |
| Derated Capacity | Irated | 104 A | After derating factors |
| CCC Margin | ΔICCC | 78.4 A | Available capacity margin |
| Cable Impedance | Zc | 1.47 Ω/km | Per kilometer |
| Voltage Drop | Vd | 1.98 V | Absolute voltage drop |
| Voltage Drop % | Vd% | 0.862 % | As percentage of supply |
| Max Withstand Time | tmax | 52.3 ms | Cable withstand capability |
| Protection Time | tprot | 100 ms | Device operating time |
| Loop Impedance | Zloop | 188 mΩ | Total earth fault loop |
| Fault Current | Ifault | 1.22 kA | Earth fault current |
| Min Earth Conductor | Se,min | 6 mm² | AS/NZS 3000:2018 Table 5.1 minimum; earth used 16.0 mm² |
| Max Earth Fault Current | Ief | 2.3 kA | Near-end earth fault, V / Z_source |
| Earth Withstand Min CSA | Se,adb | 3.22 mm² | I_ef √t / k, k = 143.0 |
| Power Loss | Ploss | 57.7 W | 1.15% of transmitted power |