| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Motor Type | - | Three-Phase | Winding configuration |
| Control Method | - | DOL | Starting and running control method |
| Rated Voltage | V_LL | 400 V | Rated RMS line-to-line voltage |
| Equivalent-Circuit Connection | - | Star | Star: V_ph = V_LL/√3; delta: V_ph = V_LL (line current √3 × phase current) |
| Line Frequency | f_line | 50 Hz | Rated supply frequency |
| Number of Poles | p | 4 - | Magnetic poles in motor stator |
| Stator Resistance | R₁ | 200 mΩ | Resistance of stator winding per phase |
| Stator Reactance | X₁ | 500 mΩ | Leakage reactance of stator winding per phase |
| Rotor Resistance | R₂ | 300 mΩ | Rotor resistance per phase, referred to stator |
| Rotor Reactance | X₂ | 600 mΩ | Rotor leakage reactance per phase, referred to stator |
| Magnetizing Reactance | Xₘ | 20 Ω | Magnetizing reactance per phase |
| Core Loss | P_core | 75 W | Rotational losses due to hysteresis and eddy currents |
| Friction & Windage Loss | P_fw | 25 W | Mechanical losses due to friction and windage |
Synchronous speed is the speed of the rotating magnetic field. Where: • f = 50.0 Hz (operating frequency) • p = 4 (number of poles) The rotor rotates slightly slower than synchronous speed, with the difference called slip.
Angular velocity of the rotating magnetic field in radians per second.
Star (Y) connected equivalent circuit: each phase sees the line-to-neutral voltage and the line current equals the phase current.
The stator circuit is simplified using Thévenin theorem as seen from the rotor terminals. This reduces the complex stator impedance network to a simple voltage source (V_th) in series with equivalent impedance (R_th + jX_th).
Equivalent resistance as seen from rotor terminals = 0.190345 Ω
Equivalent reactance as seen from rotor terminals = 0.489662 Ω
Rotor current referred to the stator, used for the developed torque. At starting (s=1), rotor current is maximum. Where: • s = slip = (n_s - n_r) / n_s • n_r = rotor speed (RPM) Example shown for starting condition (s=1). I₂ excludes the magnetising current, so it is not the current drawn from the supply — see the stator current below.
Stator phase current including the magnetising current (Chapman, Electric Machinery Fundamentals, Example 6-5). Star connection: the line current equals I₁. The current-speed curve and the reported starting currents are line currents. At starting (s=1): I₁ = 194.225 A (DOL locked-rotor line current at rated voltage and frequency: 194.22 A).
Electromagnetic torque developed by the motor. The factor of 3 accounts for three-phase operation. At starting (s=1): T = 203.69 N·m The complete torque-speed curve is calculated by repeating this calculation for slip values from 1.0 (standstill) to 0.001 (near synchronous speed).
I²R losses in stator windings. Three phases, each carrying the stator current I₁ of the full equivalent circuit (magnetising current included).
Electromagnetic power transferred across air gap from stator to rotor.
Total electrical power input to motor.
Portion of air gap power converted to mechanical form. At starting (s=1), P_conv = 0 (all power dissipated as heat in rotor).
Useful mechanical power available at shaft after subtracting friction/windage (25.0 W). Core loss is already accounted for in P_in.
Ratio of output power to input power. Maximum efficiency achieved at 1478.9 RPM with η_max = 95.25%.
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Operating Frequency | f_op | 50 Hz | Actual operating frequency |
| Per-Phase Voltage | V_ph | 231 V | Rated voltage across one phase of the equivalent circuit (V_LL/√3 star, V_LL delta) |
| Effective Voltage | V_eff | 231 V | Per-phase voltage after V/Hz scaling (held at rated voltage above base frequency) |
| Synchronous Speed | n_s | 1.5 kRPM | Speed of rotating magnetic field |
| Thévenin Voltage | V_th | 225 V | Thévenin equivalent voltage |
| Thévenin Resistance | R_th | 190 mΩ | Thévenin equivalent resistance |
| Thévenin Reactance | X_th | 490 mΩ | Thévenin equivalent reactance |
| DOL Starting Torque | T_start | 204 N·m | Starting torque with direct-on-line start at rated frequency |
| DOL Starting Current | I_1,start | 194 A | Locked-rotor line current at rated voltage and frequency (stator I₁; × √3 for delta) |
| Maximum Torque (Pull-out) | T_max | 374 N·m | Maximum torque capacity before motor stalls |
| Speed at Max Torque | n_Tmax | 1.09 kRPM | Rotor speed at maximum torque |
| Maximum Efficiency | η_max | 95.2 % | Maximum efficiency operating point |
| Speed at Max Efficiency | n_ηmax | 1.48 kRPM | Rotor speed at maximum efficiency |