Given floor area; used for floor conduction, lighting, room volume and the default roof area
Total perimeter wall area
Internal room volume
Outside design temperature 35.0 °C, inside target 22.0 °C
Tetens' equation for saturation vapor pressure at outside temperature
Where P_vapor = P_sat x RH/100 = 5631.2 x 60/100 = 3378.7 Pa
Tetens' equation at inside design temperature
Where P_vapor = P_sat x RH/100 = 2642.8 x 50/100 = 1321.4 Pa
Difference in moisture content used for latent infiltration load
Sum of 1 equipment item(s)
U = 0.60 W/m²K, A = 108.0 m²
U = 0.40 W/m²K, A = 77.0 m²
U = 0.30 W/m²K, A = 77.0 m²
Sum of 3 surface(s)
Sun-exposed wall area = 40.0 m², factor = 150 W/m²
Sun-exposed roof area = 77.0 m², factor = 300 W/m²
Solar radiation through exposed surfaces and windows
Lighting density = 10.0 W/m²
ASHRAE standard: 75 W sensible heat per person
ASHRAE standard: 55 W latent heat per person
Air changes per hour = 0.50
Coefficient 1.23 = air density x specific heat (kW per m³/s per K)
Coefficient 3010 = air density x latent heat of vaporization
Sum of all sensible heat sources
Sum of all latent heat sources
Total cooling load to be removed
Ratio of sensible to total load; higher SHR means less dehumidification needed
Safety factor of 15% applied for uncertainties and future growth
Rounded up to next whole unit; each unit rated at 10.00 kW
0 redundant unit(s)
Install 5 air conditioning unit(s) with total installed capacity of 50.00 kW