The load power factor 0.899 is at or below the UPS output power factor 0.9, so the kVA rating governs.
The rating is the UPS output; efficiency sets the input and battery power, not the output rating.
Next standard three-phase rating.
60-80 % utilisation leaves headroom for transients and growth.
UPS (inverter) efficiency in battery operation.
Average discharge voltage 364.8 V (0.95 of nominal).
Peukert exponent n = 1.3 for VRLA-AGM (5-10 year).
k_T at 25 °C; lead-acid takes no capacity credit above 25 °C (IEEE 485 cl. 6.2.2).
Target 15 min: met.
Half the current: Peukert gives 2^n times the full-load runtime.
With N strings each carries 1/N of the current.