| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Voltage (Single Phase) | V | 240 V | Single-Phase System |
| Efficiency | η | 100 | At rated load |
| Power Factor | PF | 0.85 | Lagging |
The full-load current is calculated using the single-phase formula: This represents the current drawn by the single-phase load.
The phase angle is calculated using the formula:
The phasor diagram shows the single-phase voltage and current phasors with the phase angle (φ) between them. The solid red line represents voltage phasor, while the dashed blue line represents current phasor lagging behind voltage.
Figure 1: Single-phase phasor diagram showing voltage and current relationship
The power triangle illustrates the relationship between active power (P), reactive power (Q), and apparent power (S). Active power does useful work, reactive power oscillates between source and load, and apparent power is the vector sum of both.
Figure 2: Power triangle showing P, Q, and S relationships
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Current | I | 73.5 A | Load Current |
| Apparent Power | S | 17.6 kVA | Load |
| Active Power | P | 15 kW | Load |
| Reactive Power | Q | 9.3 kVAr | Load |
Scan this QR code with your mobile device to view the calculation online.