Input Parameters

The following design parameters were considered for this calculation:
Parameter Symbol Value Notes
Voltage (Phase to Phase) VL-L 415 V 3-Phase System
Active Power P 15 kW Load
Efficiency η 100 At rated load
Power Factor PF 0.85 Lagging

Calculations

All calculations were performed in accordance with IEC standards and good engineering practice.

Current Calculation

The full-load current is calculated using the formula: This represents the phase current drawn by the load.

Formula: $$ \begin{aligned} I_{(A)} &= \frac{\left( \frac{P}{\eta} \right) \times 1{,}000}{\sqrt{3} \times V_{L-L(V)} \times PF} \\ &= \frac{\left( \frac{15}{1} \right) \times 1{,}000}{\sqrt{3} \times 415 \times 0.85} \\ &= 24.6 \; Amps \end{aligned} $$

Phase Angle Calculation

The phase angle is calculated using the formula:

Formula: $$ \begin{aligned} \theta &= \cos^{-1}(PF) \times \frac{180}{\pi} \\ &= \cos^{-1}(0.85) \times \frac{180}{3.142} \\ &= 31.8^\circ \end{aligned} $$

Three-Phase Voltage and Current Phasors

Three-Phase Voltage and Current Phasors VA VB VC IA IB IC φ = 31.8°

The phasor diagram shows the three-phase voltage and current phasors with the phase angle (φ) between them. Each phase (A, B, C) is separated by 120°. Solid lines represent voltage phasors, while dashed lines represent current phasors lagging behind voltage.

Figure 1: Three-phase phasor diagram showing voltage and current relationships

Three-Phase Power Relationships

Three-Phase Power Triangle P = 15.00 kW Q = 9.30 kVAr S = 17.64 kVA θ = 31.8°

The power triangle illustrates the relationship between active power (P), reactive power (Q), and apparent power (S). Active power does useful work, reactive power oscillates between source and load, and apparent power is the vector sum of both.

Figure 2: Power triangle showing P, Q, and S relationships

Summary of Results

Below is the summary of calculated values for ease of reference:
Parameter Symbol Value Notes
Current (Phase) Ip 24.6 A Phase Current
Apparent Power S 17.6 kVA Load
Active Power P 15 kW Load
Reactive Power Q 9.3 kVAr Load

Approval:

This calculation has been reviewed and approved by:
Created By
Engineer Name
Date: ..........................
Checked
By: .............................
Date: ..........................
Approved
By: .............................
Date: ..........................
Client Approved
By: .............................
Date: ..........................

Scan to View Online

Scan this QR code with your mobile device to view the calculation online.

Scan to access this calculation from any device