| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Voltage (Phase to Phase) | VL-L | 415 V | 3-Phase System |
| Active Power | P | 15 kW | Load |
| Efficiency | η | 100 | At rated load |
| Power Factor | PF | 0.85 | Lagging |
The full-load current is calculated using the formula: This represents the phase current drawn by the load.
The phase angle is calculated using the formula:
The phasor diagram shows the three-phase voltage and current phasors with the phase angle (φ) between them. Each phase (A, B, C) is separated by 120°. Solid lines represent voltage phasors, while dashed lines represent current phasors lagging behind voltage.
Figure 1: Three-phase phasor diagram showing voltage and current relationships
The power triangle illustrates the relationship between active power (P), reactive power (Q), and apparent power (S). Active power does useful work, reactive power oscillates between source and load, and apparent power is the vector sum of both.
Figure 2: Power triangle showing P, Q, and S relationships
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Current (Phase) | Ip | 24.6 A | Phase Current |
| Apparent Power | S | 17.6 kVA | Load |
| Active Power | P | 15 kW | Load |
| Reactive Power | Q | 9.3 kVAr | Load |