| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| System Voltage | VLL | 415 V | Line-to-line voltage |
| System Frequency | f | 50 Hz | Electrical frequency |
| Short Circuit Level | Ssc | 10 MVA | Available fault level at switchboard |
| Short Circuit Current | Isc | 13.9 kA | Calculated from S<sub>sc</sub> |
| Source Resistance | Rs | 10 mΩ | Resistive component of source impedance |
| Source Reactance | Xs | 50 mΩ | Reactive component of source impedance |
| Number of VSDs | N | 1 | Total Variable Speed Drives analyzed |
| Total VSD Power | Ptotal | 75 kW | Sum of all VSD operating power |
Calculate available short circuit current from fault level
The short circuit current at the 415V switchboard is 13912A
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| VSD-01 - Rated Power | P1 | 100 kW | VSD 1 rated power |
| VSD-01 - Load | Load1 | 75 % | Operating load percentage |
| VSD-01 - Fundamental Current | I1,1 | 116 A | Fundamental (50Hz) current |
| VSD-01 - THD | THD1 | 26.5 % | Individual THD |
| VSD-01 - Rectifier Type | 6-pulse | Rectifier configuration |
The fundamental current for each VSD is calculated from the operating power, efficiency, and power factor. For multiple VSDs, the fundamental currents are summed arithmetically as they are all at the same frequency (50Hz or 60Hz).
Sum of fundamental currents from all 1 VSD(s)
Harmonic currents are generated at characteristic frequencies: h = kq ± 1, where q is the pulse number and k is a positive integer. For a 6-pulse VSD, characteristic harmonics are 5th, 7th, 11th, 13th, 17th, 19th, etc. The magnitude depends on:<br>• <b>I<sub>h,base</sub></b>: Baseline harmonic as % of fundamental (from manufacturer data)<br>• <b>K<sub>load</sub></b>: Load correction factor (harmonics reduce at light load)<br>• <b>K<sub>reactor</sub></b>: Input reactor reduction factor (3-5% reactance reduces harmonics by 30-50%)<br>• <b>K<sub>dc</sub></b>: DC link choke reduction factor (further reduces harmonics)<br>• <b>K<sub>pulse</sub></sub>: Pulse number factor (12-pulse eliminates 5th/7th, 18-pulse eliminates up to 17th)
Phasor random summation (realistic scenario, assumes random phase displacement between VSDs). This is the recommended method per IEEE 519 for multiple non-linear loads with uncorrelated operation.
Total Harmonic Distortion of current (THD<sub>I</sub>) represents the ratio of harmonic content to fundamental
Assessment: SEVERE - Very high distortion, mitigation required
Harmonic currents flowing through the source impedance create harmonic voltage distortion. R<sub>s</sub> and X<sub>s</sub> are per-phase (star-equivalent) values, so V<sub>h</sub> is a line-to-neutral voltage. The impedance increases with harmonic order (h) due to the inductive reactance component. This means higher-order harmonics create proportionally larger voltage distortion.
Total Harmonic Distortion of voltage (THD<sub>V</sub>)
Assessment: MODERATE - Mitigation may be beneficial
The K-factor quantifies additional transformer heating due to harmonic currents. Standard transformers are rated K-4. Harmonic loads require higher K-rated transformers to prevent overheating and premature failure.<br><br><b>Recommended Transformer Rating: K-13 (moderate harmonic environment)</b>
Select transformer rated for K-13 (moderate harmonic environment)
Triplen harmonics (3rd, 9th, 15th, 21st, etc.) do not cancel in the neutral conductor of a three-phase four-wire system. Instead, they add arithmetically, potentially causing neutral current to exceed phase current. VSD loads are single-phase equivalent and triplen harmonics typically have lower magnitude than in traditional three-phase non-linear loads.<br><br><b>Neutral Current Ratio: 0.0%</b><br><b>Assessment: NORMAL - Standard neutral conductor adequate</b>
Ratio to fundamental: 0.0%
| Parameter | Symbol | Value | Notes |
|---|---|---|---|
| Total Fundamental Current | I1 | 116 A | Sum of fundamental currents from all VSDs |
| Total RMS Current | Irms | 120 A | Root mean square of total current |
| Current THD | THDI | 26.5 % | Total harmonic distortion of current |
| Voltage THD | THDV | 7.99 % | Total harmonic distortion of voltage |
| K-Factor | K | 11.2 | Transformer K-factor rating required |
| Neutral Current | In | 0 A | Triplen harmonic current in neutral |
| Crest Factor | CF | 1.43 | Peak to RMS current ratio |
| IEEE 519 Current TDD | TDD | 26.5 % | Total demand distortion |
| IEEE 519 Compliance | FAIL | Overall IEEE 519-2022 compliance status | |
| IEC 61000 Compliance | FAIL | Overall IEC 61000-2-2 compliance status |