Team projects: load list to cable schedule
Models, revisions, imports, studies, exports and the report.
In a team workspace, fast.engineer keeps a network model for each project: buses (boards), sources, transformers, loads, cables, protective devices and fault scenarios. The project tools let an assistant build that model from a load list, run the studies on it and produce the deliverables — with every number traceable to the engine run that produced it. This needs the workspace endpoint, a workspace chosen at sign-in, and membership of the project.
The workflow at a glance
- Find or create the model —
fe_project_list,fe_model_list,fe_model_create(with the design basis). - Upload the load list —
fe_file_upload_urlgives a one-time upload link. - Preview the import —
fe_loadlist_import_previewshows how columns map, what is wrong and what would be created. Nothing is written. - Commit it —
fe_loadlist_import_commit, with any mapping corrections. - Complete the network —
fe_model_editadds the supply, transformers, feeders and protective devices. - Check it —
fe_qa_check. - Run the studies —
fe_study_max_demand,fe_study_fault,fe_study_size_cables,fe_study_protection; follow each withfe_job_getand drill in withfe_results_get. - Deliver —
fe_schedule_export(xlsx/csv) andfe_report_generate(PDF). - Freeze and issue —
fe_revision_set_status; branch the next revision withfe_revision_createand compare withfe_revision_diff.
The Size all cables from a load list prompt walks an assistant through exactly this sequence.
Models and revisions
A model has one or more revisions (A, B, C …). Each revision holds a complete copy of the network
and its own design basis. Every element has a tag (its name on drawings — cable number, board name,
equipment tag) and a uid that stays the same across revisions, so revisions can be compared element by
element.
| Status | Meaning | Can move to |
|---|---|---|
draft | Editable; imports, edits and cable sizes can be written. | checked |
checked | Frozen for review: the model and its elements can no longer change. | draft (to correct), approved |
approved | Frozen. | issued |
issued | Frozen permanently; records who issued it and when. | — (branch a new revision) |
fe_revision_create branches a new draft from any revision (copy-on-write: the copy diffs as identical
until something changes). fe_revision_diff lists elements added, removed and modified, field by field, and
design-basis changes.
Design basis (revision settings)
Set when the model is created (settings of fe_model_create); anything left out takes the
default.
| Setting | Default | Meaning |
|---|---|---|
standard |
asnzs3008 |
Cable sizing standard (installation.standard of fe_calc_cable_size) |
edition |
2017 |
Edition of the standard, e.g. '2017' for AS/NZS 3008.1.1 |
vd_budget_pct |
5.0 |
Total voltage-drop budget source → load, % |
feeder_vd_pct |
2.0 |
Limit for a bus-to-bus feeder cable, % (part of the budget) |
ambient_air_c |
40.0 |
Design air ambient, °C |
ambient_ground_c |
25.0 |
Design soil ambient, °C |
soil_resistivity_km_w |
1.2 |
Soil thermal resistivity, K·m/W |
burial_depth_m |
0.8 |
Depth of laying for buried cables, m |
earthing_system |
TN-C-S |
System earthing (TN-C-S = MEN in AU/NZ) |
default_installation |
copper XLPE multicore, unenclosed on a ladder, one circuit | fe_calc_cable_size installation used where a cable gives none |
default_material |
copper |
Conductor material for cables that do not give one |
default_insulation |
xlpe |
Insulation for cables that do not give one |
md_method |
duty_standby_lf |
Maximum demand method (calcs.core.demand) |
growth_factor |
1.0 |
Multiplier on board demand for future load growth |
spare_capacity_factor |
1.0 |
Multiplier on board demand for spare capacity |
default_clearing_time_s |
0.1 |
Protection clearing time where a device gives none, s |
Importing a load list
From a spreadsheet
- Accepted:
.xlsxor.csv, up to 25 MB and 20000 rows. The upload link fromfe_file_upload_urlis valid for 15 minutes and accepts onePUTof the file. - The header row is detected (title rows above it are skipped) or can be given. Each column is matched to a model
field by its heading, with a confidence: 100 % for an exact or known heading, 70 % when only the words match.
Fields:
tag,description,board,rated_kw,rated_kva,voltage_v,phases,power_factor,efficiency,duty_qty,standby_qty,load_factor,kind,start_method,cable_no,cable_length_m,status. tagandboardare required, and each row needs a kW or kVA rating. Voltages given in kV and power factors or efficiencies given in % are converted. The phases column must read as single- or three-phase; DC loads are reported as problems because the network model is AC.- The preview reports every problem by row, boards that exist or would be created, new and updated loads, and
sample rows. Correct the mapping at commit with
overrides, e.g.{"board": "Fed From"}. - Commit is all-or-nothing unless you ask to skip invalid rows. It creates or updates loads (matched by tag), a
supply cable per new load (the list's cable number, or
C-<tag>) and any missing boards.
From the project's load design
source='loaddesign' imports the project's loaddesign electrical load list instead: boards come from load
centres and the supply hierarchy, boards fed from boards become feeder cables, and ratings in kW, kVA, HP or A are
converted. Loads with no supplying board are reported.
Editing the model
fe_model_edit applies a list of add / update / delete operations
to a draft revision in one all-or-nothing batch. kind is one of bus, source, transformer, load, cable,
device or scenario; other elements are referred to by tag or uid. Every operation is validated (types, choices, a cable
going to exactly one bus or load); deleting an element others depend on is refused. Use fe_model_get to see
the fields of each kind.
Studies and jobs
Studies run in the background. Each fe_study_* call returns a job_id at once;
fe_job_get reports progress and, when finished, a summary that puts exceptions first
("3 cables fail voltage drop; …; 27 of 36 pass"). fe_job_cancel stops a job; a cancelled job keeps no
results. fe_results_get pages through per-element results, failures first, optionally with each element's
full provenance envelope.
| Study | What it does |
|---|---|
| Maximum demand | Duty/standby and load-factor method per board, rolled up the supply tree with diversity, growth and spare factors; transformer loading against rating. |
| Fault | IEC 60909 at every bus and load terminal: Ik″ maximum (c = 1.1, cable resistance at 20 °C) and peak, Ik″ minimum (hot conductors), and line-to-earth minimum giving the upstream earth-fault loop impedance. Each bus is cross-checked against the MVA method; bus short-circuit ratings are checked. |
| Cable sizing | Every cable through the same engine as fe_calc_cable_size, from the source
down (see below). |
| Protection | Each device: Ib ≤ In ≤ Iz, breaking capacity Icu ≥ Ik″max, adiabatic withstand (k²S² ≥ I²t) and earth-fault loop impedance against the magnetic trip current. |
How cable sizing works
- Design current: a load cable carries one unit at full load (motors with the motor design factor); a feeder carries the downstream board's design demand.
- Voltage drop is shared out from the source: a feeder may use up to
feeder_vd_pct; a final circuit gets what is left ofvd_budget_pctafter its upstream feeders. A per-cable limit overrides both. - Fault level and earth loop at each cable's supply end come from the fault study; the cable's own
protective device is used when modelled, otherwise the smallest standard rating above the design current (recorded
as an assumption). Without a device clearing time the revision's
default_clearing_time_sapplies. - Iteration: new sizes change fault levels, so the fault study is re-solved and cables re-sized until no size changes (up to 3 passes); the summary says whether it converged.
- By default only unsized cables are selected; cables that already have a size are checked at that size.
resize='all're-selects everything. Withapply_sizesthe selected sizes are written to the draft revision. - Every cable's result keeps the exact input it was sized with and the full provenance envelope, so any line of
the schedule can be re-run with
fe_calc_cable_sizeand compared hash for hash.
Quality checks
fe_qa_check runs without starting a job and reports errors, warnings and notes, for example: no source,
unreachable buses or loads, voltage mismatches, loads without cables, missing ratings or lengths, duplicate tags,
loops or multiple feeds, ways exceeded or few spare ways, single-phase imbalance, voltage drop over budget, and
unsized or unprotected cables.
Deliverables
- Cable schedule —
fe_schedule_export, xlsx or csv: cable number, from, to, description, voltage, cores, size, parallel runs, earth, material, insulation, length, installation, design current, capacity, voltage drop and cumulative drop, status, governing check, the run it came from and the result hash. An administrator can set up other column layouts (export templates) and pass one withtemplate_id. - Calculation report —
fe_report_generate, PDF: revision history, design basis, exceptions first, maximum demand by board, fault levels, the cable schedule with governing checks, the assumptions and clause references collected from every result, engine build and validation suite, a "design aid until signed" notice and an unsigned sign-off block. - Both return a download link valid for 15 minutes, bound to you and the project.