Reading a result
The provenance envelope field by field, and how to reproduce a number.
Every tool returns two things: a short text summary for the assistant to read, and a structured result (JSON matching the tool's published output schema). For engineering tools the structured result is a provenance envelope: the answer, the evidence for it, and what is needed to reproduce it.
A worked example
Asking for a transformer for a 1600 kVA load at 11 kV / 415 V (fe_calc_transformer with
load_kva=1600, primary_kv=11, secondary_kv=0.415) returns this summary:
2000 kVA transformer (Load 1600 kVA × 1.2 growth); utilisation 80.0%. Z = 6.5%, η = 97.59% at full load,
regulation 4.44%, LV fault 42.81 kA (infinite source). Design aid: verify before use.
and this structured result (abridged):
{
"result": {
"selected_rating_kva": 2000.0,
"utilisation_pct": 80.0,
"impedance_percent": 6.5,
"voltage_regulation_pct": 4.44,
"lv_fault_ka_symmetrical": 42.81,
...
},
"governing_constraint": "capacity",
"checks": [
{ "name": "capacity", "value": 1920.0, "limit": 2000.0, "unit": "kVA", "passed": true,
"utilisation_pct": 96.0,
"clause_ref": { "standard": "IEC 60076-1", "note": "Rated power", ... } },
{ "name": "winding_temperature", "value": 105.0, "limit": 155.0, "unit": "°C", "passed": true }
],
"warnings": [],
"sensitivity": [
{ "change": "load above 1600 kVA",
"effect": "2000 kVA remains adequate up to 1667 kVA of present load" }
],
"provenance": {
"method": "Next standard rating at or above load × growth ..., derated for altitude; ...",
"clause_refs": [ { "standard": "IEC 60076-1", "note": "Ratings, impedance and losses" } ],
"assumptions": [
{ "field": "growth_factor", "value": 1.2, "source": "default", "note": "" },
{ "field": "impedance_percent", "value": 6.5, "source": "derived",
"note": "Estimated from rating and voltage: ... use the nameplate value when known" },
{ "field": "upstream_source", "value": "infinite", "source": "default",
"note": "LV fault level is transformer-limited (conservative maximum); use fe_calc_short_circuit ..." }
],
"engine": { "component": "calcs.c0024_transformer_sizing",
"build": "3a9a0815ce5f", "validation_suite": "corpus-6ba2d6feaac1" },
"hashes": { "inputs_sha256": "08520315…", "outputs_sha256": "59e8e8c8…" },
"verification_status": "unverified",
"timestamp": "2026-10-13T07:11:27Z",
"request_id": "7f3c2a9e41d04b6c"
}
}
Read it as: a 2000 kVA unit is the smallest standard rating that carries 1600 kVA with 20 % growth; capacity is what decided it; it was not given the impedance or losses so it estimated them — use nameplate values when you have them; and the fault level assumes an infinite upstream source.
The fields
- result
- The answer, in the tool's own fields (names carry their units:
_kva,_ka,_pct,_m…). Withresponse_format='detailed'it also containsintermediates— every value along the way, such as the table ratings and impedances looked up. - governing_constraint
- The name of the check that decided the answer: the one with the least margin, or the one that failed. For a cable
it is one of
current_carrying_capacity,voltage_drop,short_circuit_withstandorearth_fault_loop_impedance. This is the first thing to look at when you want a different answer: relax that constraint and the answer can change. - checks[]
- Every check made:
valueagainstlimitinunit,passed, and how much of the limit is used (utilisation_pct). A check carries the clause or table it comes from where there is one. - clause_ref
- A reference into a standard: designation, edition, clause, table, column and row. Only the reference is given — the text and tables of standards are copyright, so check the cited table in your licensed copy.
- warnings[]
- Things the engine noticed that do not fail a check but deserve attention (an input near a table edge, a value clamped to the engine's range).
- sensitivity[]
- How far an input can move before the answer changes, worked out by re-running the engine.
- provenance.method
- The method in plain words.
- provenance.assumptions[]
- Every value the tool used that you did not give it exactly.
sourceisuser(your value, possibly mapped — e.g. an ambient of 42 °C read from the 45 °C column, which is the conservative direction),default(a documented default) orderived(estimated or calculated from other inputs). Read this list before relying on a result. - provenance.engine
- Which engine produced the number (
component), the exact code version (build) and the version of the validation corpus that build was checked against (validation_suite). - provenance.hashes
- SHA-256 of the inputs (after defaults were applied) and of the decision-bearing outputs (
result,checksandgoverning_constraint), each serialised as canonical JSON: sorted keys, no whitespace, UTF-8. - provenance.verification_status
unverifiedfor everything a tool returns. A result becomes checked or approved only through your own review process — for team projects, through the revision status.- provenance.request_id
- The id of this call in fast.engineer's audit log. Quote it if you ask about a result.
Reproducing a result
- Call the same tool with the same inputs. The engine is deterministic: on the same
buildyou get the sameoutputs_sha256. - To prove which inputs produced a result, compute the SHA-256 of the canonical JSON of the full input (every
field, defaults included, as echoed by the tool's input schema) and compare it with
inputs_sha256. - For a team project, each cable result stores the exact input it was sized with, so any line of a cable schedule
can be re-run on its own with
fe_calc_cable_sizeand compared hash for hash.
A different build can legitimately give a different hash (a corrected engine); the
validation scorecard shows which build each published run
checked.
Errors that teach
When an input is wrong or a combination is not covered by the standard, the tool returns an error (marked
isError) that names the field and says how to fix it — for example that AS/NZS 3008.1.1 gives no rating for
a chosen installation and which settings to change. Assistants read these and retry. Unexpected faults return only a
request id: no internals are exposed.