Cable Volt Drop Table

Jump to section

Overview

The Cable Volt Drop Table generates a 34×17 reference matrix showing the maximum cable length (metres) for every motor size × cable size combination, based on running voltage drop per AS/NZS 3008.1.1:2017. The cable voltage drop factors Vc are read from the licensed Table 42 data (copper multicore cables, circular conductors) at the rated conductor temperature of the insulation you select.

Unlike single-point cable sizing calculators, this tool produces a complete "waterfall" matrix — allowing you to quickly look up the maximum cable run for any motor and cable combination at a glance.

Matrix cells are colour-coded:

  • Green — up to 100m
  • Yellow — 100m to 500m
  • Red — over 500m
  • Grey (N/A) — cable current capacity is less than motor FLC
  • Grey (> Max) — calculated length exceeds the max display cap

Input Parameters

Parameter Type Default Range Description
insulation Enum XLPE PVC, XLPE, EPR, Elastomer Cable insulation. Its rated conductor temperature (AS/NZS 3008.1.1 Table 1) selects the Table 42 Vc column: PVC (V-75) 75 °C, XLPE (X-90) 90 °C, EPR (R-EP-90) 90 °C, 110 °C elastomers (e.g. R-HF-110) 110 °C
standard_edition String 2017 2017 AS/NZS 3008.1.1 edition; 2017 is the only one supported (any other value is rejected)
voltage Number 415 V 110 – 11000 System line-to-line voltage. The 415 V motor currents are scaled by 415 / V
num_parallel Enum 1 1 – 4 Number of parallel cables per phase. 0.9 derating applied when > 1
vd_percent Number 5.0% 0.1 – 20 Maximum allowable running voltage drop percentage
max_display_length Number 10000 m 100 – 100000 Lengths above this are shown as "> Max" in the matrix

Output Results

The main output is a 34-row × 17-column matrix where:

  • Rows — 34 motor sizes from 0.37kW to 750kW (FLC tabulated at 415V, scaled to the system voltage)
  • Columns — 17 cable sizes from 2.5mm² to 500mm²
  • Cells — maximum cable length in metres (rounded integer), or N/A / > Max

Summary statistics are also provided:

  • Total combinations (34 × 17 = 578)
  • Valid combinations (cells with a numeric length within display range)
  • N/A count (cable too small for motor)
  • Exceeds max count (length beyond display cap)

Formulas

Maximum Cable Length

L = (Vd% × V × 1000 × P) / (I × Vc)

Where:

  • L = Maximum cable length (m)
  • Vd% = Voltage drop as a decimal (e.g. 0.05 for 5%)
  • V = System voltage (V)
  • P = Number of parallel cables
  • I = Full load current at the system voltage (A): \(I = I_{415} \times 415 / V\) (same kW, efficiency and power factor, so current is inversely proportional to voltage)
  • Vc = Cable three-phase voltage drop factor (mV/A.m): AS/NZS 3008.1.1:2017 Table 42, copper multicore circular, maximum-value column (\(V_c = \sqrt{3}\,Z_c\), valid for any load power factor), at the rated conductor temperature of the selected insulation

Effective Current-Carrying Capacity

CCC_eff = CCC_base × P × k_derating

Where k_derating = 0.9 when P > 1, otherwise 1.0. If CCC_eff < FLC, the cell is marked N/A.

Cable Data (Cu Multicore, 3-Phase)

Voltage drop factor Vc

Vc comes from the licensed AS/NZS 3008.1.1:2017 data installed on the server; the values are not reproduced here. Every cable size is read from Table 42 (three-phase, copper, multicore cables with circular conductors, maximum value) in the column for the insulation's rated conductor temperature, because a cable carrying a motor's full-load current is assumed to run fully loaded:

insulation Cable types (AS/NZS 3008.1.1 Table 1) Table 42 column
PVCV-7575 °C
XLPEX-9090 °C
EPRR-EP-9090 °C
Elastomer110 °C types (e.g. R-HF-110, R-E-110)110 °C

The calculation report names the table and column used. A hotter column gives a larger Vc and a shorter maximum length: for the same cable, the 90 °C column is about 5 % above the 75 °C one (less for the largest sizes, where reactance is a larger part of the impedance). A combination the installed edition does not tabulate is reported as an error naming the input to change; no substitute value is used.

Current screen

The N/A screen uses the component's indicative derated ratings below (one fixed installation condition; the source data took PVC values for 2.5–16 mm² and XLPE values for 25–500 mm²). They do not change with the insulation input and are not a substitute for a current-carrying capacity check.

Size (mm²) Derated rating (A)
2.533
444
656
1074
1698
25131
35162
50197
70251
95302
120349
150393
185454
240532
300601
400686
500780

Motor Data (FLC at 415V)

Motor (kW) FLC (A) Motor (kW) FLC (A)
0.371.1155101.00
0.551.3175133.80
0.751.7790158.13
1.12.52110195.42
1.53.37132234.02
2.24.82160283.07
36.50185334.78
48.44220393.20
5.510.68315561.83
7.514.36400733.02
1121.65450830.00*
1528.92500892.00*
18.536.49550996.00
2242.746001087.00
3059.456501177.00
3768.457001268.00
4582.147501359.00

* The source data had these two currents transposed (450 kW = 892 A, 500 kW = 830 A, a larger motor drawing less current). Corrected 2026-10-23 to 450 kW = 830 A (1.84 A/kW) and 500 kW = 892 A (1.78 A/kW), in line with 400 kW (1.83 A/kW) and 550 kW (1.81 A/kW).

Worked Examples

The 11 examples below are the validation cases for this calculation. Each one was produced by the calculation engine from the inputs shown, every figure was checked against the independent reference quoted at the end of the example, and the same cases are run against every engine build (see validation scorecard, tool fe_calc_voltage_drop; worked examples for every calculation).

#CaseMotorFLC at VCableVc basisAllowanceLmaxRouteResult
10.37 kW motor on 2.5 mm² at 415 V0.37 kW, 415 V1.11 A2.5 mm² XLPE90 °C5.00 %1,140 m–PASS
230 kW motor on 16 mm², 120 m route30 kW, 415 V59.45 A16 mm² XLPE90 °C5.00 %137 m120 mPASS
355 kW on 2 × 35 mm² at 400 V, 1 % upstream55 kW, 400 V104.79 A35 mm² ×2 XLPE90 °C4.00 %261 m250 mPASS
411 kW on 2.5 mm² with a 3 % allowance, 50 m11 kW, 415 V21.65 A2.5 mm² XLPE90 °C3.00 %35 m50 mFAIL
530 kW on 4 mm²: cable not rated30 kW, 415 V59.45 A4 mm² XLPE90 °C5.00 %not rated–FAIL
675 kW on 16 mm² at 690 V, 200 m75 kW, 690 V80.47 A16 mm² XLPE90 °C5.00 %168 m200 mFAIL
7450 kW on 4 × 300 mm²450 kW, 415 V830.00 A300 mm² ×4 XLPE90 °C5.00 %526 m500 mPASS
8500 kW on 3 × 300 mm², 400 m500 kW, 415 V892.00 A300 mm² ×3 XLPE90 °C5.00 %367 m400 mFAIL
955 kW on 2 × 35 mm² PVC at 400 V, 340 m55 kW, 400 V104.79 A35 mm² ×2 PVC75 °C5.00 %344 m340 mPASS
1022 kW on 10 mm² EPR, 100 m22 kW, 415 V42.74 A10 mm² EPR90 °C5.00 %120 m100 mPASS
11132 kW on 120 mm² 110 °C elastomer, 250 m132 kW, 415 V234.02 A120 mm² Elastomer110 °C5.00 %230 m250 mFAIL

Example 1 — 0.37 kW motor on 2.5 mm² at 415 V

The help page's worked example: the smallest motor on the smallest cable reaches over a kilometre.

Given: 0.37 kW motor, 415 V three-phase, 2.5 mm² Cu multicore cable, XLPE (X-90) insulation (tool default); voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 1.11 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data2.5 mm²: Vc = 16.4 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 33 A
Current screenrating = 33 × 1 = 33.0 A ≥ FLC 1.11 A? → 1.11 vs limit 33.00 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 415 × 1000 × 1 / (1.110 × 16.4) = 1,139.9 m → 1,140 m
Result1/1 checks pass → PASS; governing: indicative current capacity
ReferenceHand calculation, Vc 16.4 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 column 8 (Cu multicore circular, 90 °C, maximum value; XLPE default)), FLC 1.11 A: L = 0.05 × 415 × 1000 ÷ (1.11 × 16.4) = 20 750 ÷ 18.204 = 1139.9 m → 1140 m (validation case c0035-0p37kw-2mm5-415v)

Example 2 — 30 kW motor on 16 mm², 120 m route

A route-length check against the tabulated maximum at the reference 415 V.

Given: 30 kW motor, 415 V three-phase, 16 mm² Cu multicore cable, XLPE (X-90) insulation (tool default), actual route 120 m; voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 59.45 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data16 mm²: Vc = 2.55 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 98 A
Current screenrating = 98 × 1 = 98.0 A ≥ FLC 59.45 A? → 59.45 vs limit 98.00 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 415 × 1000 × 1 / (59.450 × 2.55) = 136.9 m → 137 m
Route check120 m ≤ 137 m? → 120 vs limit 137 m PASS
Result2/2 checks pass → PASS; governing: voltage drop route length
ReferenceHand calculation, FLC 59.45 A at 415 V, Vc 2.55 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 column 8 (Cu multicore circular, 90 °C, maximum value; XLPE default)): L = 0.05 × 415 × 1000 ÷ (59.45 × 2.55) = 20 750 ÷ 151.598 = 136.9 m → 137 m ≥ 120 m (validation case c0035-30kw-16mm2-415v-5pct)

Example 3 — 55 kW on 2 × 35 mm² at 400 V, 1 % upstream

Off-reference voltage (FLC scaled 415/400), two parallel cables with the 0.9 grouping factor, and an upstream drop.

Given: 55 kW motor, 400 V three-phase, 35 mm² Cu multicore cable × 2 in parallel, XLPE (X-90) insulation (tool default), actual route 250 m; voltage-drop limit 5 % from the point of supply (tool default), 1 % already used upstream.

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentComponent motor table: 101 A at 415 V; at 400 V (same kW) FLC = 101 × 415 / 400 = 104.787 A
AllowanceVd% = limit − upstream = 5 − 1 = 4.00 %
Cable data35 mm²: Vc = 1.17 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 162 A
Current screenrating = 162 × 2 × 0.9 = 291.6 A ≥ FLC 104.79 A? → 104.79 vs limit 291.60 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0400 × 400 × 1000 × 2 / (104.787 × 1.17) = 261.0 m → 261 m
Route check250 m ≤ 261 m? → 250 vs limit 261 m PASS
Result2/2 checks pass → PASS; governing: voltage drop route length
ReferenceHand calculation: allowance 5 − 1 = 4 %; FLC = 101.0 × 415 ÷ 400 = 104.7875 A; Vc 1.17 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 column 8 (Cu multicore circular, 90 °C, maximum value; XLPE default)); L = 0.04 × 400 × 1000 × 2 ÷ (104.7875 × 1.17) = 32 000 ÷ 122.601 = 261.0 m ≥ 250 m; rating 162 × 2 × 0.9 = 291.6 A (validation case c0035-55kw-35mm2-2-parallel-400v-upstream)

Example 4 — 11 kW on 2.5 mm² with a 3 % allowance, 50 m

A tighter drop allowance shortens the reach below the actual route, so the route check fails.

Given: 11 kW motor, 415 V three-phase, 2.5 mm² Cu multicore cable, XLPE (X-90) insulation (tool default), actual route 50 m; voltage-drop limit 3 % from the point of supply.

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 21.65 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 3 − 0 = 3.00 %
Cable data2.5 mm²: Vc = 16.4 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 33 A
Current screenrating = 33 × 1 = 33.0 A ≥ FLC 21.65 A? → 21.65 vs limit 33.00 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0300 × 415 × 1000 × 1 / (21.650 × 16.4) = 35.1 m → 35 m
Route check50 m ≤ 35 m? → 50 vs limit 35 m FAIL
Result1/2 checks pass → FAIL; governing: voltage drop route length
ReferenceHand calculation, Vc 16.4 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 column 8 (Cu multicore circular, 90 °C, maximum value; XLPE default)): L = 0.03 × 415 × 1000 ÷ (21.65 × 16.4) = 12 450 ÷ 355.06 = 35.1 m → 35 m < 50 m; 21.65 A ≤ 33 A (validation case c0035-11kw-2mm5-3pct-route-fail)

Example 5 — 30 kW on 4 mm²: cable not rated

A cable whose rating is below the motor current has no tabulated length; the capacity screen fails and governs.

Given: 30 kW motor, 415 V three-phase, 4 mm² Cu multicore cable, XLPE (X-90) insulation (tool default); voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 59.45 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data4 mm²: Vc = 10.2 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 44 A
Current screenrating = 44 × 1 = 44.0 A ≥ FLC 59.45 A? → 59.45 vs limit 44.00 A FAIL
Maximum lengthNot tabulated: the cable is not rated for the motor current
Result0/1 checks pass → FAIL; governing: indicative current capacity
ReferenceComponent data: 4 mm² derated rating 44 A < FLC 59.45 A → no maximum length (independent of Vc) (validation case c0035-30kw-4mm2-undersized)

Example 6 — 75 kW on 16 mm² at 690 V, 200 m

A 690 V system: the motor draws 415/690 of its 415 V current, so a 16 mm² cable carries it, but 200 m is too far.

Given: 75 kW motor, 690 V three-phase, 16 mm² Cu multicore cable, XLPE (X-90) insulation (tool default), actual route 200 m; voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentComponent motor table: 133.8 A at 415 V; at 690 V (same kW) FLC = 133.8 × 415 / 690 = 80.474 A
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data16 mm²: Vc = 2.55 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 98 A
Current screenrating = 98 × 1 = 98.0 A ≥ FLC 80.47 A? → 80.47 vs limit 98.00 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 690 × 1000 × 1 / (80.474 × 2.55) = 168.1 m → 168 m
Route check200 m ≤ 168 m? → 200 vs limit 168 m FAIL
Result1/2 checks pass → FAIL; governing: voltage drop route length
ReferenceHand calculation: FLC = 133.8 × 415 ÷ 690 = 80.474 A ≤ 98 A; Vc 2.55 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 column 8 (Cu multicore circular, 90 °C, maximum value; XLPE default)); L = 0.05 × 690 × 1000 ÷ (80.474 × 2.55) = 34 500 ÷ 205.208 = 168.1 m → 168 m < 200 m (validation case c0035-75kw-16mm2-690v-route-fail)

Example 7 — 450 kW on 4 × 300 mm²

A large motor on four parallel cables, using the corrected 450 kW full-load current (830 A).

Given: 450 kW motor, 415 V three-phase, 300 mm² Cu multicore cable × 4 in parallel, XLPE (X-90) insulation (tool default), actual route 500 m; voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 830 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data300 mm²: Vc = 0.19 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 601 A
Current screenrating = 601 × 4 × 0.9 = 2,163.6 A ≥ FLC 830.00 A? → 830.00 vs limit 2,163.60 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 415 × 1000 × 4 / (830.000 × 0.19) = 526.3 m → 526 m
Route check500 m ≤ 526 m? → 500 vs limit 526 m PASS
Result2/2 checks pass → PASS; governing: voltage drop route length
ReferenceHand calculation: FLC 830 A (450 kW); rating 601 × 4 × 0.9 = 2163.6 A; Vc 0.19 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 column 8 (Cu multicore circular, 90 °C, maximum value; XLPE default)); L = 0.05 × 415 × 1000 × 4 ÷ (830 × 0.19) = 83 000 ÷ 157.7 = 526.3 m → 526 m ≥ 500 m (validation case c0035-450kw-4x300mm2)

Example 8 — 500 kW on 3 × 300 mm², 400 m

The corrected 500 kW current (892 A) on three parallel cables falls short of a 400 m route.

Given: 500 kW motor, 415 V three-phase, 300 mm² Cu multicore cable × 3 in parallel, XLPE (X-90) insulation (tool default), actual route 400 m; voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of XLPE (X-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 892 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data300 mm²: Vc = 0.19 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 601 A
Current screenrating = 601 × 3 × 0.9 = 1,622.7 A ≥ FLC 892.00 A? → 892.00 vs limit 1,622.70 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 415 × 1000 × 3 / (892.000 × 0.19) = 367.3 m → 367 m
Route check400 m ≤ 367 m? → 400 vs limit 367 m FAIL
Result1/2 checks pass → FAIL; governing: voltage drop route length
ReferenceHand calculation: FLC 892 A (500 kW); rating 601 × 3 × 0.9 = 1622.7 A; Vc 0.19 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 column 8 (Cu multicore circular, 90 °C, maximum value; XLPE default)); L = 0.05 × 415 × 1000 × 3 ÷ (892 × 0.19) = 62 250 ÷ 169.48 = 367.3 m → 367 m < 400 m (validation case c0035-500kw-3x300mm2-route-fail)

Example 9 — 55 kW on 2 × 35 mm² PVC at 400 V, 340 m

PVC (V-75) reads the 75 °C Vc column, so the run reaches 344 m and a 340 m route passes; the same cables in XLPE (90 °C) would fail it.

Given: 55 kW motor, 400 V three-phase, 35 mm² Cu multicore cable × 2 in parallel, PVC (V-75) insulation, actual route 340 m; voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of PVC (V-75) insulation (AS/NZS 3008.1.1 Table 1) = 75 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentComponent motor table: 101 A at 415 V; at 400 V (same kW) FLC = 101 × 415 / 400 = 104.787 A
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data35 mm²: Vc = 1.11 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 6, Cu multicore circular, 75 °C, maximum value); component derated rating 162 A
Current screenrating = 162 × 2 × 0.9 = 291.6 A ≥ FLC 104.79 A? → 104.79 vs limit 291.60 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 400 × 1000 × 2 / (104.787 × 1.11) = 343.9 m → 344 m
Route check340 m ≤ 344 m? → 340 vs limit 344 m PASS
Result2/2 checks pass → PASS; governing: voltage drop route length
ReferenceHand calculation: PVC rated 75 °C (AS/NZS 3008.1.1:2017 Table 1); Vc 1.11 mV/A·m (Table 42 column 6, Cu multicore circular, 75 °C, maximum value); FLC = 101.0 × 415 ÷ 400 = 104.7875 A; L = 0.05 × 400 × 1000 × 2 ÷ (104.7875 × 1.11) = 40 000 ÷ 116.314 = 343.9 m → 344 m ≥ 340 m. XLPE (90 °C, Vc 1.17): 40 000 ÷ 122.601 = 326.3 m < 340 m (validation case c0035-55kw-2x35mm2-400v-pvc-340m)

Example 10 — 22 kW on 10 mm² EPR, 100 m

EPR (R-EP-90) is rated 90 °C like XLPE, so it reads the 90 °C Vc column.

Given: 22 kW motor, 415 V three-phase, 10 mm² Cu multicore cable, EPR (R-EP-90) insulation, actual route 100 m; voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of EPR (R-EP-90) insulation (AS/NZS 3008.1.1 Table 1) = 90 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 42.74 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data10 mm²: Vc = 4.05 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 8, Cu multicore circular, 90 °C, maximum value); component derated rating 74 A
Current screenrating = 74 × 1 = 74.0 A ≥ FLC 42.74 A? → 42.74 vs limit 74.00 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 415 × 1000 × 1 / (42.740 × 4.05) = 119.9 m → 120 m
Route check100 m ≤ 120 m? → 100 vs limit 120 m PASS
Result2/2 checks pass → PASS; governing: voltage drop route length
ReferenceHand calculation: EPR rated 90 °C (AS/NZS 3008.1.1:2017 Table 1); Vc 4.05 mV/A·m (Table 42 column 8, Cu multicore circular, 90 °C, maximum value); FLC 42.74 A ≤ 74 A; L = 0.05 × 415 × 1000 ÷ (42.74 × 4.05) = 20 750 ÷ 173.097 = 119.9 m → 120 m ≥ 100 m (validation case c0035-22kw-10mm2-epr-100m)

Example 11 — 132 kW on 120 mm² 110 °C elastomer, 250 m

A 110 °C elastomer cable reads the hottest Vc column, which shortens the reach below a 250 m route.

Given: 132 kW motor, 415 V three-phase, 120 mm² Cu multicore cable, 110 °C elastomer insulation, actual route 250 m; voltage-drop limit 5 % from the point of supply (tool default).

Conductor temperatureRated temperature of 110 °C elastomer insulation (AS/NZS 3008.1.1 Table 1) = 110 °C: the cable is taken as fully loaded, which selects the Vc column
Full-load currentFLC = 234.02 A (component motor table at 415 V)
AllowanceVd% = limit − upstream = 5 − 0 = 5.00 %
Cable data120 mm²: Vc = 0.385 mV/A·m (AS/NZS 3008.1.1:2017 Table 42 Column 10, Cu multicore circular, 110 °C, maximum value); component derated rating 349 A
Current screenrating = 349 × 1 = 349.0 A ≥ FLC 234.02 A? → 234.02 vs limit 349.00 A PASS
Maximum lengthL = Vd% × V × 1000 × n / (FLC × Vc) = 0.0500 × 415 × 1000 × 1 / (234.020 × 0.385) = 230.3 m → 230 m
Route check250 m ≤ 230 m? → 250 vs limit 230 m FAIL
Result1/2 checks pass → FAIL; governing: voltage drop route length
ReferenceHand calculation: 110 °C elastomer (AS/NZS 3008.1.1:2017 Table 1); Vc 0.385 mV/A·m (Table 42 column 10, Cu multicore circular, 110 °C, maximum value); FLC 234.02 A ≤ 349 A; L = 0.05 × 415 × 1000 ÷ (234.02 × 0.385) = 20 750 ÷ 90.098 = 230.3 m → 230 m < 250 m (validation case c0035-132kw-120mm2-110c-elastomer-250m)

Standards & References

  • AS/NZS 3008.1.1:2017 — Electrical installations – Selection of cables. Table 1 for the insulation's maximum conductor operating temperature, Table 42 for the three-phase voltage drop factors (copper multicore, circular conductors); Table 13 is the basis the source data names for the indicative ratings.
  • AS/NZS 3000:2018 — Electrical installations (Wiring Rules). Clause 3.6 covers voltage drop requirements.

Tips & Limitations

  • The 0.9 derating factor for parallel cables is a simplified approach per AS3008 for grouped cables. Actual derating may vary by installation method.
  • Motor FLC values are tabulated for 415V, 3-phase and scaled by 415 / V for other system voltages (the same motor output draws a current inversely proportional to voltage). The voltage in the numerator of the length formula is a separate effect: both apply.
  • This calculator computes running voltage drop only (not startup). Startup voltage drop (typically allowed up to 15-20%) is handled separately.
  • Vc is taken at the insulation's rated temperature (fully loaded cable). A cable loaded well below its rating runs cooler and reaches further; the matrix is conservative for it.
  • Copper multicore cables only. Aluminium and single-core cables have their own Table 40–45 values; use the Cable Voltage Drop calculator for them.
  • The matrix is too wide for A4 PDF — it is available only in the interactive web view. The PDF report includes the formula, cable data reference, and statistics.

Developer Guide — Architecture

This calculator follows the standard calcs component pattern:

components/c0035_cable_volt_drop_table/
├── __init__.py              # Docstring
├── apps.py                  # Django AppConfig
├── calculations.py          # Pure Python — all math, no Django
├── component.py             # Schema, Calculator class, builders, registration
├── equations.py             # LaTeX equation templates
└── templates/.../sidebar_form.html  # Vue 3 sidebar form

Data flow: Sidebar form → CableVoltDropTableCalculator.calculate() → calculate_cable_volt_drop_table() (pure Python) → results dict → equation_builder() / summary_cards_builder() → UI rendering

Developer Guide — Code Paths

Purpose File Key Function / Class
Max length formula calculations.py calculate_max_cable_length(voltage, vd_percent, num_parallel, flc, cable_vdrop)
Effective CCC calculations.py get_effective_ccc(cable_derated_amps, num_parallel)
Cell classification calculations.py classify_cell(max_length, max_display_length)
Matrix builder calculations.py build_volt_drop_matrix(voltage, vd_percent, num_parallel, max_display_length, vc_factors)
Vc lookup (Table 42) calculations.py lookup_vc_factors(insulation, standard_edition, gateway) via calcs.core.as3008.AS3008Gateway (licensed table data in the database)
Main entry calculations.py calculate_cable_volt_drop_table(data)
Validation component.py CableVoltDropTableCalculator.validate_parameters()
Registration component.py register_component(registry)

Developer Guide — Testing

# Run all tests for this component
pytest calcs/test_c0035_cable_volt_drop_table.py -v

Test coverage includes:

  • TestLookupVcFactors — Table 42 column per insulation (75/90/110 °C), edition and gap errors; rows are served from transcribed values (the licensed data is not in the test database), and a dev-database test checks them against the installed tables
  • TestCalculateMaxCableLength — known formula values, parallel doubles length, higher Vd% increases length
  • TestGetEffectiveCCC — single no derating, 2 cables with 0.9 derating, 4 cables
  • TestClassifyCell — green/yellow/red boundaries, exceeds_max, N/A
  • TestBuildVoltDropMatrix — 34 rows × 17 cols, N/A for undersized cable, stats
  • TestCalculateCableVoltDropTable — defaults, spot-check cell, input echo
  • TestCalculatorClass — validation, round-trip calculation, registration