Overview
The Lightning Risk Assessment calculator evaluates the need for lightning protection systems (LPS) per IEC 62305-2 — Protection against lightning: Risk management. It calculates risk R1 (loss of human life) and determines whether a lightning protection system is required, and if so, at which protection level (LPL I–IV).
The calculator provides:
- Collection area — equivalent area attracting lightning strikes
- Expected strikes — annual frequency of dangerous lightning events (Nd)
- Risk assessment — R1 broken into RA (touch/step), RB (fire/damage), RC (system failure)
- Protection decision — whether LPS is required
- Protection level — LPL I, II, III, or IV with rolling sphere radius and mesh size
Input Parameters
Structure
| Parameter | Default | Range | Description |
|---|---|---|---|
structure_length | 40 m | 1 – 1000 | Structure length |
structure_width | 20 m | 1 – 1000 | Structure width |
structure_height | 10 m | 1 – 300 | Structure height |
Lightning Environment
| Parameter | Default | Description |
|---|---|---|
flash_density | 2 fl/km²/yr | Ground flash density Ng (from local lightning data) |
location_factor | flat | Relative location, Cd per IEC 62305-2 Table A.1: surrounded by taller objects (0.25), flat = surrounded by objects of the same height or smaller (0.5), moderate = isolated, no objects in the vicinity (1.0), exposed = isolated on a hilltop or knoll (2.0) |
Structure Properties
| Parameter | Default | Description |
|---|---|---|
structure_type | non_metal_roof | Roof and structure material → PB probability |
occupancy | occupied | Occupancy level → LA loss factor |
fire_risk | ordinary | Fire/explosion risk → LB loss factor |
Systems & Protection
| Parameter | Default | Description |
|---|---|---|
internal_systems | low_voltage | Service lines connected to the internal systems (none, LV power, telecom, LV power + telecom) → number of lines n in PC |
consequence_of_failure | standard | Consequence of system failure → LC factor |
touch_step_protection | none | Touch/step voltage measures → PA factor |
surge_protection | none | Coordinated SPD system on every connected line → PSPD (IEC 62305-2 Table B.3) |
existing_lps | none | Existing LPS level → reduces PB by efficiency |
Output Results
| Output | Symbol | Unit | Description |
|---|---|---|---|
| Collection Area | Ad | m² | Equivalent area attracting direct strikes |
| Expected Strikes | Nd | /yr | Annual expected dangerous lightning events |
| Risk RA | RA | — | Injury from touch/step voltages |
| Risk RB | RB | — | Physical damage (fire, explosion) |
| Risk RC | RC | — | Failure of internal systems |
| Total Risk | R1 | — | RA + RB + RC |
| Tolerable Risk | RT | — | 10-5 for loss of human life |
| Protection Required | — | Yes / No | Whether R1 > RT |
| Protection Level | LPL | I – IV | Required lightning protection level |
| Rolling Sphere | — | m | Rolling sphere radius for LPL (20 / 30 / 45 / 60 m) |
| Mesh Size | — | m | Maximum mesh size (5 / 10 / 15 / 20 m) |
Formulas
Collection Area (IEC 62305-2 eq. A.2)
Ad = L×W + 2×(3H)×(L+W) + π×(3H)²
The 3H factor accounts for the attractive radius of the structure. For a 40×20×10 m building: Ad = 800 + 3,600 + 2,827 ≈ 7,227 m².
Expected Dangerous Events (IEC 62305-2 Annex A)
Nd = Ng × Ad × Cd × 10-6
Risk R1 Components
RA = Nd × PA × LA RB = Nd × PB × LB RC = Nd × PC × LC, PC = 1 − (1 − PSPD × CLD)n R1 = RA + RB + RC
The probabilities and losses are category values chosen by the inputs (a simplification of the IEC 62305-2 Annex B/C factor products). An existing LPS multiplies PB by (1 − efficiency).
PC follows IEC 62305-2 B.4: each connected service line contributes PC,i = PSPD × CLD, and the lines combine as PC = 1 − (1 − PC,1)(1 − PC,2)…, so connecting more lines raises PC. The calculator simplifies this to one category: every connected line is taken as an unshielded aerial or buried line (CLD = 1, Table B.4) and the selected SPD level is applied to all of them. With no connected line (stand-alone systems) CLD = 0 and PC = 0. Shielded or bonded lines, isolating interfaces and SPDs better than LPL I (PSPD 0.005–0.001) are not modelled.
| Factor | Input | Values |
|---|---|---|
| Cd | location_factor | surrounded by higher objects 0.25, flat (same height or smaller) 0.5, moderate (isolated) 1, exposed (isolated on a hilltop) 2 — Table A.1 |
| PA | touch_step_protection | none 1, warning notices 0.1, electrical insulation 0.01, equipotential bonding 0.01 |
| PB | structure_type | metal roof + metal structure 0.001, non-metal roof + metal structure 0.01, non-metal roof 0.1, thatched roof 0.3 |
| PB multiplier | existing_lps | none 1, IV 0.2, III 0.1, II 0.05, I 0.02 |
| n (lines) | internal_systems | none 0 (PC = 0), low voltage 1, telecom 1, LV and telecom 2 |
| CLD | — | 1 (unshielded line, Table B.4) |
| PSPD | surge_protection | none 1, spd_1 (LPL III–IV) 0.05, spd_2 (LPL II) 0.02, spd_3 (LPL I) 0.01 — Table B.3 |
| LA | occupancy | occupied 0.01, high occupancy 0.1 |
| LB | fire_risk | no fire risk 0, ordinary 0.1, high fire risk 0.5, explosion risk 1 |
| LC | consequence_of_failure | no consequence 0, standard 0.01, critical 0.1 |
Protection Level Determination
If R1 > RT (10-5), lightning protection is required. The minimum LPL is the level whose PB reduction factor (efficiency) brings R1 ≤ RT.
| LPL | Efficiency | Rolling Sphere | Mesh Size |
|---|---|---|---|
| I | 0.98 | 20 m | 5 × 5 m |
| II | 0.95 | 30 m | 10 × 10 m |
| III | 0.90 | 45 m | 15 × 15 m |
| IV | 0.80 | 60 m | 20 × 20 m |
Worked Examples
The 25 examples below are the validation cases for this calculation. Each one was produced by the calculation engine from the inputs shown, every figure was checked against the independent reference quoted at the end of the example, and the same cases are run against every engine build (see validation scorecard, tool fe_calc_lightning_risk; worked examples for every calculation).
| # | Case | AD (m²) | ND (/yr) | R1 (/yr) | LPS | R1 with LPS | Result |
|---|---|---|---|---|---|---|---|
| 1 | Small building among taller ones | 1,406.9 | 3.52 × 10−4 | 1.06 × 10−5 | class IV | 7.74 × 10−6 | FAIL |
| 2 | 40 × 20 × 10 m building, all defaults | 7,227.4 | 7.23 × 10−3 | 2.17 × 10−4 | class I | 1.46 × 10−4 | FAIL |
| 3 | Hilltop warehouse with high fire risk | 34,309.7 | 0.343 | 0.024 | class I | 7.21 × 10−3 | FAIL |
| 4 | Bonded building needing class IV | 3,087.9 | 3.09 × 10−3 | 3.18 × 10−5 | class IV | 7.10 × 10−6 | FAIL |
| 5 | Bonded building needing class III | 7,227.4 | 7.23 × 10−3 | 7.44 × 10−5 | class III | 9.40 × 10−6 | FAIL |
| 6 | Bonded building needing class II | 7,227.4 | 0.0108 | 1.12 × 10−4 | class II | 8.67 × 10−6 | FAIL |
| 7 | Bonded building needing class I | 7,227.4 | 0.0217 | 2.21 × 10−4 | class I | 8.67 × 10−6 | FAIL |
| 8 | Existing class III LPS already adequate | 7,227.4 | 7.23 × 10−3 | 9.40 × 10−6 | none | – | PASS |
| 9 | Existing class IV LPS needs upgrading | 7,227.4 | 0.0108 | 2.49 × 10−5 | class II | 8.67 × 10−6 | FAIL |
| 10 | Isolated building (C_D 1) | 2,649.9 | 1.32 × 10−3 | 1.52 × 10−5 | class IV | 4.64 × 10−6 | FAIL |
| 11 | Small hut isolated on a hilltop (C_D 2) | 458.5 | 9.17 × 10−4 | 1.83 × 10−7 | none | – | PASS |
| 12 | Metal roof and metal frame | 12,351.5 | 0.0124 | 4.94 × 10−6 | none | – | PASS |
| 13 | Non-metal roof on a metal frame | 12,351.5 | 0.0185 | 2.41 × 10−5 | class IV | 9.26 × 10−6 | FAIL |
| 14 | Thatched-roof cottage | 1,833.9 | 3.67 × 10−3 | 1.14 × 10−4 | class II | 9.90 × 10−6 | FAIL |
| 15 | High-occupancy hall | 11,331.5 | 8.50 × 10−3 | 1.72 × 10−4 | class I | 8.84 × 10−5 | FAIL |
| 16 | Structure with no fire risk | 20,361.7 | 0.0407 | 2.44 × 10−5 | class I | 2.44 × 10−5 | FAIL |
| 17 | Explosion-risk process building | 6,427.4 | 0.0225 | 2.29 × 10−4 | class I | 9.00 × 10−6 | FAIL |
| 18 | Telecom equipment with critical consequence | 1,372.4 | 2.06 × 10−3 | 2.06 × 10−4 | class I | 2.06 × 10−4 | FAIL |
| 19 | Same telecom building with LPL III–IV SPDs | 1,372.4 | 2.06 × 10−3 | 1.07 × 10−5 | class I | 1.05 × 10−5 | FAIL |
| 20 | Same telecom building with SPD level 3 | 1,372.4 | 2.06 × 10−3 | 2.47 × 10−6 | none | – | PASS |
| 21 | LV and telecom lines combined | 7,227.4 | 7.23 × 10−3 | 4.31 × 10−6 | none | – | PASS |
| 22 | LV + telecom with no life consequence | 4,809.6 | 4.81 × 10−3 | 9.62 × 10−7 | none | – | PASS |
| 23 | No connected service lines | 554.5 | 8.32 × 10−4 | 1.66 × 10−7 | none | – | PASS |
| 24 | 300 m tower on a hilltop | 2,617,090.0 | 10.5 | 0.21 | class I | 0.209 | FAIL |
| 25 | Smallest structure at the lowest flash density | 41.3 | 2.06 × 10−6 | 6.19 × 10−8 | none | – | PASS |
Example 1 — Small building among taller ones
A 10 × 10 × 5 m building surrounded by higher structures (C_D 0.25) at N_G 1: with its unprotected LV line (P_C 1) R1 lands just above R_T and a class IV LPS is enough.
Given: Structure 10 × 10 × 5 m (L × W × H), ground flash density NG = 1 flashes/km²/yr, located surrounded by higher objects; non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: none; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 10 × 10 + 2 × 15 × (10 + 10) + π × 15² = 100.0 + 600.0 + 706.9 = 1,406.9 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 1 × 1,406.9 × 0.25 × 10−6 = 3.517 × 10−4 /yr |
| Probabilities | PA = 1 (none); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 1 × 1)1 = 1 (LV power line, n = 1, unshielded CLD = 1; no coordinated SPDs, PSPD = 1, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 3.517 × 10−4 × 1 × 0.01 = 3.517 × 10−6; RB = ND·PB·LB = 3.517 × 10−4 × 0.1 × 0.1 = 3.517 × 10−6; RC = ND·PC·LC = 3.517 × 10−4 × 1 × 0.01 = 3.517 × 10−6 |
| R1 check | R1 = RA + RB + RC = 3.517 × 10−6 + 3.517 × 10−6 + 3.517 × 10−6 → 1.055 × 10−5 > RT = 10−5/yr (105.5 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 3.517 × 10−6): class IV: 3.517 × 10−6 + 3.517 × 10−6 × 0.2 + 3.517 × 10−6 = 7.738 × 10−6 ≤ RT → class IV; rolling sphere 60 m, mesh 20 × 20 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class IV LPS → 7.738 × 10−6 ≤ RT = 10−5/yr (77.4 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 1.055 × 10−5/yr; recommended LPS: class IV; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 10 × 10 + 6 × 5 × (10 + 10) + 9π × 5² = 1406.9 m²; N_D = 1 × 1406.9 × 0.25 × 1e-6 = 0.0003517/yr; R_A = N_D × 1 × 0.01 = 3.517e-06, R_B = N_D × 0.1 × 0.1 = 3.517e-06, P_C = 1 − (1 − 1 × 1)^1 = 1 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 1, Table B.3); R_C = N_D × 1 × 0.01 = 3.517e-06; R1 = 1.055e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): IV, residual R1 = 7.738e-06; rolling sphere 60 m, mesh 20 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-10x10x5m-ng1-surrounded) |
Example 2 — 40 × 20 × 10 m building, all defaults
With every factor at its default the touch/step component R_A alone exceeds R_T, so even a class I LPS leaves R1 above the limit.
Given: Structure 40 × 20 × 10 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: none; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 40 × 20 + 2 × 30 × (40 + 20) + π × 30² = 800.0 + 3,600.0 + 2,827.4 = 7,227.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 7,227.4 × 0.5 × 10−6 = 7.227 × 10−3 /yr |
| Probabilities | PA = 1 (none); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 1 × 1)1 = 1 (LV power line, n = 1, unshielded CLD = 1; no coordinated SPDs, PSPD = 1, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 7.227 × 10−3 × 1 × 0.01 = 7.227 × 10−5; RB = ND·PB·LB = 7.227 × 10−3 × 0.1 × 0.1 = 7.227 × 10−5; RC = ND·PC·LC = 7.227 × 10−3 × 1 × 0.01 = 7.227 × 10−5 |
| R1 check | R1 = RA + RB + RC = 7.227 × 10−5 + 7.227 × 10−5 + 7.227 × 10−5 → 2.168 × 10−4 > RT = 10−5/yr (2,168.2 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 7.227 × 10−5): class IV: 7.227 × 10−5 + 7.227 × 10−5 × 0.2 + 7.227 × 10−5 = 1.590 × 10−4 > RT; class III: 7.227 × 10−5 + 7.227 × 10−5 × 0.1 + 7.227 × 10−5 = 1.518 × 10−4 > RT; class II: 7.227 × 10−5 + 7.227 × 10−5 × 0.05 + 7.227 × 10−5 = 1.482 × 10−4 > RT; class I: 7.227 × 10−5 + 7.227 × 10−5 × 0.02 + 7.227 × 10−5 = 1.460 × 10−4 > RT — no class achieves RT, class I recommended as the ceiling; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 1.460 × 10−4 > RT = 10−5/yr (1,459.9 %) FAIL |
| Result | 0/2 checks pass → FAIL; R1 = 2.168 × 10−4/yr; recommended LPS: class I; governing: risk r1 with recommended lps. Even an LPS of class I leaves R1 = 0.000146 > 1e-05; the remaining risk is dominated by RA, which an LPS does not reduce in this engine — add touch/step protection measures (RA) or coordinated SPDs (RC). |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 40 × 20 + 6 × 10 × (40 + 20) + 9π × 10² = 7227.4 m²; N_D = 2 × 7227.4 × 0.5 × 1e-6 = 0.007227/yr; R_A = N_D × 1 × 0.01 = 7.227e-05, R_B = N_D × 0.1 × 0.1 = 7.227e-05, P_C = 1 − (1 − 1 × 1)^1 = 1 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 1, Table B.3); R_C = N_D × 1 × 0.01 = 7.227e-05; R1 = 0.0002168 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I (none suffices, I is the ceiling), residual R1 = 0.000146; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-40x20x10m-ng2-flat) |
Example 3 — Hilltop warehouse with high fire risk
A large exposed warehouse (C_D 2, L_B 0.5) is far above R_T; class I is recommended but R_A keeps the residual risk above the limit.
Given: Structure 100 × 50 × 20 m (L × W × H), ground flash density NG = 5 flashes/km²/yr, located isolated on a hilltop or knoll (exposed); non-metallic roof and structure, high fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: none; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 100 × 50 + 2 × 60 × (100 + 50) + π × 60² = 5,000.0 + 18,000.0 + 11,309.7 = 34,309.7 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 5 × 34,309.7 × 2 × 10−6 = 0.3431 /yr |
| Probabilities | PA = 1 (none); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 1 × 1)1 = 1 (LV power line, n = 1, unshielded CLD = 1; no coordinated SPDs, PSPD = 1, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.5 (high fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.3431 × 1 × 0.01 = 3.431 × 10−3; RB = ND·PB·LB = 0.3431 × 0.1 × 0.5 = 0.01715; RC = ND·PC·LC = 0.3431 × 1 × 0.01 = 3.431 × 10−3 |
| R1 check | R1 = RA + RB + RC = 3.431 × 10−3 + 0.01715 + 3.431 × 10−3 → 0.02402 > RT = 10−5/yr (240,168.1 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 0.01715): class IV: 3.431 × 10−3 + 0.01715 × 0.2 + 3.431 × 10−3 = 0.01029 > RT; class III: 3.431 × 10−3 + 0.01715 × 0.1 + 3.431 × 10−3 = 8.577 × 10−3 > RT; class II: 3.431 × 10−3 + 0.01715 × 0.05 + 3.431 × 10−3 = 7.720 × 10−3 > RT; class I: 3.431 × 10−3 + 0.01715 × 0.02 + 3.431 × 10−3 = 7.205 × 10−3 > RT — no class achieves RT, class I recommended as the ceiling; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 7.205 × 10−3 > RT = 10−5/yr (72,050.4 %) FAIL |
| Result | 0/2 checks pass → FAIL; R1 = 0.02402/yr; recommended LPS: class I; governing: risk r1 with recommended lps. Even an LPS of class I leaves R1 = 0.00721 > 1e-05; the remaining risk is dominated by RA, which an LPS does not reduce in this engine — add touch/step protection measures (RA) or coordinated SPDs (RC). |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 100 × 50 + 6 × 20 × (100 + 50) + 9π × 20² = 34309.7 m²; N_D = 5 × 34309.7 × 2 × 1e-6 = 0.3431/yr; R_A = N_D × 1 × 0.01 = 0.003431, R_B = N_D × 0.1 × 0.5 = 0.01715, P_C = 1 − (1 − 1 × 1)^1 = 1 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 1, Table B.3); R_C = N_D × 1 × 0.01 = 0.003431; R1 = 0.02402 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I (none suffices, I is the ceiling), residual R1 = 0.007205; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-100x50x20m-ng5-exposed-high-fire) |
Example 4 — Bonded building needing class IV
With equipotential bonding and coordinated SPDs only R_B matters, and a class IV LPS (P_B × 0.2) is the lowest class that meets R_T.
Given: Structure 30 × 15 × 6 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: equipotential bonding; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 30 × 15 + 2 × 18 × (30 + 15) + π × 18² = 450.0 + 1,620.0 + 1,017.9 = 3,087.9 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 3,087.9 × 0.5 × 10−6 = 3.088 × 10−3 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 3.088 × 10−3 × 0.01 × 0.01 = 3.088 × 10−7; RB = ND·PB·LB = 3.088 × 10−3 × 0.1 × 0.1 = 3.088 × 10−5; RC = ND·PC·LC = 3.088 × 10−3 × 0.02 × 0.01 = 6.176 × 10−7 |
| R1 check | R1 = RA + RB + RC = 3.088 × 10−7 + 3.088 × 10−5 + 6.176 × 10−7 → 3.181 × 10−5 > RT = 10−5/yr (318.1 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 3.088 × 10−5): class IV: 3.088 × 10−7 + 3.088 × 10−5 × 0.2 + 6.176 × 10−7 = 7.102 × 10−6 ≤ RT → class IV; rolling sphere 60 m, mesh 20 × 20 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class IV LPS → 7.102 × 10−6 ≤ RT = 10−5/yr (71.0 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 3.181 × 10−5/yr; recommended LPS: class IV; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 30 × 15 + 6 × 6 × (30 + 15) + 9π × 6² = 3087.9 m²; N_D = 2 × 3087.9 × 0.5 × 1e-6 = 0.003088/yr; R_A = N_D × 0.01 × 0.01 = 3.088e-07, R_B = N_D × 0.1 × 0.1 = 3.088e-05, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 6.176e-07; R1 = 3.181e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): IV, residual R1 = 7.102e-06; rolling sphere 60 m, mesh 20 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-lpl-iv-selected) |
Example 5 — Bonded building needing class III
The same protection measures on a larger building: class IV is not enough and class III (P_B × 0.1) is selected.
Given: Structure 40 × 20 × 10 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: equipotential bonding; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 40 × 20 + 2 × 30 × (40 + 20) + π × 30² = 800.0 + 3,600.0 + 2,827.4 = 7,227.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 7,227.4 × 0.5 × 10−6 = 7.227 × 10−3 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 7.227 × 10−3 × 0.01 × 0.01 = 7.227 × 10−7; RB = ND·PB·LB = 7.227 × 10−3 × 0.1 × 0.1 = 7.227 × 10−5; RC = ND·PC·LC = 7.227 × 10−3 × 0.02 × 0.01 = 1.445 × 10−6 |
| R1 check | R1 = RA + RB + RC = 7.227 × 10−7 + 7.227 × 10−5 + 1.445 × 10−6 → 7.444 × 10−5 > RT = 10−5/yr (744.4 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 7.227 × 10−5): class IV: 7.227 × 10−7 + 7.227 × 10−5 × 0.2 + 1.445 × 10−6 = 1.662 × 10−5 > RT; class III: 7.227 × 10−7 + 7.227 × 10−5 × 0.1 + 1.445 × 10−6 = 9.396 × 10−6 ≤ RT → class III; rolling sphere 45 m, mesh 15 × 15 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class III LPS → 9.396 × 10−6 ≤ RT = 10−5/yr (94.0 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 7.444 × 10−5/yr; recommended LPS: class III; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 40 × 20 + 6 × 10 × (40 + 20) + 9π × 10² = 7227.4 m²; N_D = 2 × 7227.4 × 0.5 × 1e-6 = 0.007227/yr; R_A = N_D × 0.01 × 0.01 = 7.227e-07, R_B = N_D × 0.1 × 0.1 = 7.227e-05, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 1.445e-06; R1 = 7.444e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): III, residual R1 = 9.396e-06; rolling sphere 45 m, mesh 15 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-lpl-iii-selected) |
Example 6 — Bonded building needing class II
Higher flash density (N_G 3) pushes the recommendation to class II (P_B × 0.05, 30 m rolling sphere).
Given: Structure 40 × 20 × 10 m (L × W × H), ground flash density NG = 3 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: equipotential bonding; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 40 × 20 + 2 × 30 × (40 + 20) + π × 30² = 800.0 + 3,600.0 + 2,827.4 = 7,227.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 3 × 7,227.4 × 0.5 × 10−6 = 0.01084 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.01084 × 0.01 × 0.01 = 1.084 × 10−6; RB = ND·PB·LB = 0.01084 × 0.1 × 0.1 = 1.084 × 10−4; RC = ND·PC·LC = 0.01084 × 0.02 × 0.01 = 2.168 × 10−6 |
| R1 check | R1 = RA + RB + RC = 1.084 × 10−6 + 1.084 × 10−4 + 2.168 × 10−6 → 1.117 × 10−4 > RT = 10−5/yr (1,116.6 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 1.084 × 10−4): class IV: 1.084 × 10−6 + 1.084 × 10−4 × 0.2 + 2.168 × 10−6 = 2.493 × 10−5 > RT; class III: 1.084 × 10−6 + 1.084 × 10−4 × 0.1 + 2.168 × 10−6 = 1.409 × 10−5 > RT; class II: 1.084 × 10−6 + 1.084 × 10−4 × 0.05 + 2.168 × 10−6 = 8.673 × 10−6 ≤ RT → class II; rolling sphere 30 m, mesh 10 × 10 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class II LPS → 8.673 × 10−6 ≤ RT = 10−5/yr (86.7 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 1.117 × 10−4/yr; recommended LPS: class II; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 40 × 20 + 6 × 10 × (40 + 20) + 9π × 10² = 7227.4 m²; N_D = 3 × 7227.4 × 0.5 × 1e-6 = 0.01084/yr; R_A = N_D × 0.01 × 0.01 = 1.084e-06, R_B = N_D × 0.1 × 0.1 = 0.0001084, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 2.168e-06; R1 = 0.0001117 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): II, residual R1 = 8.673e-06; rolling sphere 30 m, mesh 10 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-lpl-ii-selected) |
Example 7 — Bonded building needing class I
At N_G 6 only a class I LPS (P_B × 0.02, 20 m sphere, 5 m mesh) brings R1 within R_T.
Given: Structure 40 × 20 × 10 m (L × W × H), ground flash density NG = 6 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: electrical insulation; surge protection: coordinated SPDs for LPL I; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 40 × 20 + 2 × 30 × (40 + 20) + π × 30² = 800.0 + 3,600.0 + 2,827.4 = 7,227.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 6 × 7,227.4 × 0.5 × 10−6 = 0.02168 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.01 × 1)1 = 0.01 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL I, PSPD = 0.01, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.02168 × 0.01 × 0.01 = 2.168 × 10−6; RB = ND·PB·LB = 0.02168 × 0.1 × 0.1 = 2.168 × 10−4; RC = ND·PC·LC = 0.02168 × 0.01 × 0.01 = 2.168 × 10−6 |
| R1 check | R1 = RA + RB + RC = 2.168 × 10−6 + 2.168 × 10−4 + 2.168 × 10−6 → 2.212 × 10−4 > RT = 10−5/yr (2,211.6 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 2.168 × 10−4): class IV: 2.168 × 10−6 + 2.168 × 10−4 × 0.2 + 2.168 × 10−6 = 4.770 × 10−5 > RT; class III: 2.168 × 10−6 + 2.168 × 10−4 × 0.1 + 2.168 × 10−6 = 2.602 × 10−5 > RT; class II: 2.168 × 10−6 + 2.168 × 10−4 × 0.05 + 2.168 × 10−6 = 1.518 × 10−5 > RT; class I: 2.168 × 10−6 + 2.168 × 10−4 × 0.02 + 2.168 × 10−6 = 8.673 × 10−6 ≤ RT → class I; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 8.673 × 10−6 ≤ RT = 10−5/yr (86.7 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 2.212 × 10−4/yr; recommended LPS: class I; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 40 × 20 + 6 × 10 × (40 + 20) + 9π × 10² = 7227.4 m²; N_D = 6 × 7227.4 × 0.5 × 1e-6 = 0.02168/yr; R_A = N_D × 0.01 × 0.01 = 2.168e-06, R_B = N_D × 0.1 × 0.1 = 0.0002168, P_C = 1 − (1 − 0.01 × 1)^1 = 0.01 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.01, Table B.3); R_C = N_D × 0.01 × 0.01 = 2.168e-06; R1 = 0.0002212 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I, residual R1 = 8.673e-06; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-lpl-i-selected) |
Example 8 — Existing class III LPS already adequate
An installed class III LPS reduces P_B to 0.01 and the building passes as it stands; no further LPS is recommended.
Given: Structure 40 × 20 × 10 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: equipotential bonding; surge protection: coordinated SPDs for LPL II; existing LPS: class III.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 40 × 20 + 2 × 30 × (40 + 20) + π × 30² = 800.0 + 3,600.0 + 2,827.4 = 7,227.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 7,227.4 × 0.5 × 10−6 = 7.227 × 10−3 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.1 (non-metallic roof and structure) × 0.1 (existing class III LPS) = 0.01; PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 7.227 × 10−3 × 0.01 × 0.01 = 7.227 × 10−7; RB = ND·PB·LB = 7.227 × 10−3 × 0.01 × 0.1 = 7.227 × 10−6; RC = ND·PC·LC = 7.227 × 10−3 × 0.02 × 0.01 = 1.445 × 10−6 |
| R1 check | R1 = RA + RB + RC = 7.227 × 10−7 + 7.227 × 10−6 + 1.445 × 10−6 → 9.396 × 10−6 ≤ RT = 10−5/yr (94.0 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 9.396 × 10−6/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 40 × 20 + 6 × 10 × (40 + 20) + 9π × 10² = 7227.4 m²; N_D = 2 × 7227.4 × 0.5 × 1e-6 = 0.007227/yr; R_A = N_D × 0.01 × 0.01 = 7.227e-07, R_B = N_D × 0.01 × 0.1 = 7.227e-06, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 1.445e-06; R1 = 9.396e-06 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-existing-lps-iii-passes) |
Example 9 — Existing class IV LPS needs upgrading
An installed class IV LPS leaves R1 above R_T, so the tool recommends the class that does meet it.
Given: Structure 40 × 20 × 10 m (L × W × H), ground flash density NG = 3 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: equipotential bonding; surge protection: coordinated SPDs for LPL II; existing LPS: class IV.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 40 × 20 + 2 × 30 × (40 + 20) + π × 30² = 800.0 + 3,600.0 + 2,827.4 = 7,227.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 3 × 7,227.4 × 0.5 × 10−6 = 0.01084 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.1 (non-metallic roof and structure) × 0.2 (existing class IV LPS) = 0.02; PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.01084 × 0.01 × 0.01 = 1.084 × 10−6; RB = ND·PB·LB = 0.01084 × 0.02 × 0.1 = 2.168 × 10−5; RC = ND·PC·LC = 0.01084 × 0.02 × 0.01 = 2.168 × 10−6 |
| R1 check | R1 = RA + RB + RC = 1.084 × 10−6 + 2.168 × 10−5 + 2.168 × 10−6 → 2.493 × 10−5 > RT = 10−5/yr (249.3 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 1.084 × 10−4): class IV: 1.084 × 10−6 + 1.084 × 10−4 × 0.2 + 2.168 × 10−6 = 2.493 × 10−5 > RT; class III: 1.084 × 10−6 + 1.084 × 10−4 × 0.1 + 2.168 × 10−6 = 1.409 × 10−5 > RT; class II: 1.084 × 10−6 + 1.084 × 10−4 × 0.05 + 2.168 × 10−6 = 8.673 × 10−6 ≤ RT → class II; rolling sphere 30 m, mesh 10 × 10 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class II LPS → 8.673 × 10−6 ≤ RT = 10−5/yr (86.7 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 2.493 × 10−5/yr; recommended LPS: class II; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 40 × 20 + 6 × 10 × (40 + 20) + 9π × 10² = 7227.4 m²; N_D = 3 × 7227.4 × 0.5 × 1e-6 = 0.01084/yr; R_A = N_D × 0.01 × 0.01 = 1.084e-06, R_B = N_D × 0.02 × 0.1 = 2.168e-05, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 2.168e-06; R1 = 2.493e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): II, residual R1 = 8.673e-06; rolling sphere 30 m, mesh 10 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-existing-lps-iv-upgrade) |
Example 10 — Isolated building (C_D 1)
An isolated structure with no neighbours (location 'moderate', C_D 1) doubles N_D compared with the 'flat' case.
Given: Structure 25 × 12 × 6 m (L × W × H), ground flash density NG = 0.5 flashes/km²/yr, located isolated, no other objects nearby (moderate); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: warning notices; surge protection: coordinated SPDs for LPL III–IV; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 25 × 12 + 2 × 18 × (25 + 12) + π × 18² = 300.0 + 1,332.0 + 1,017.9 = 2,649.9 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 0.5 × 2,649.9 × 1 × 10−6 = 1.325 × 10−3 /yr |
| Probabilities | PA = 0.1 (warning notices); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.05 × 1)1 = 0.05 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL III–IV, PSPD = 0.05, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 1.325 × 10−3 × 0.1 × 0.01 = 1.325 × 10−6; RB = ND·PB·LB = 1.325 × 10−3 × 0.1 × 0.1 = 1.325 × 10−5; RC = ND·PC·LC = 1.325 × 10−3 × 0.05 × 0.01 = 6.625 × 10−7 |
| R1 check | R1 = RA + RB + RC = 1.325 × 10−6 + 1.325 × 10−5 + 6.625 × 10−7 → 1.524 × 10−5 > RT = 10−5/yr (152.4 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 1.325 × 10−5): class IV: 1.325 × 10−6 + 1.325 × 10−5 × 0.2 + 6.625 × 10−7 = 4.637 × 10−6 ≤ RT → class IV; rolling sphere 60 m, mesh 20 × 20 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class IV LPS → 4.637 × 10−6 ≤ RT = 10−5/yr (46.4 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 1.524 × 10−5/yr; recommended LPS: class IV; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 25 × 12 + 6 × 6 × (25 + 12) + 9π × 6² = 2649.9 m²; N_D = 0.5 × 2649.9 × 1 × 1e-6 = 0.001325/yr; R_A = N_D × 0.1 × 0.01 = 1.325e-06, R_B = N_D × 0.1 × 0.1 = 1.325e-05, P_C = 1 − (1 − 0.05 × 1)^1 = 0.05 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.05, Table B.3); R_C = N_D × 0.05 × 0.01 = 6.625e-07; R1 = 1.524e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): IV, residual R1 = 4.637e-06; rolling sphere 60 m, mesh 20 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-moderate-location) |
Example 11 — Small hut isolated on a hilltop (C_D 2)
An isolated structure on a hilltop or knoll takes C_D 2 (Table A.1), four times the 'flat' (same-height neighbours) value of 0.5 used by default.
Given: Structure 6 × 4 × 3 m (L × W × H), ground flash density NG = 1 flashes/km²/yr, located isolated on a hilltop or knoll (exposed); metal roof on a metal structure, ordinary fire risk, occupied; internal systems: no connected lines (standard consequence); touch/step measures: electrical insulation; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 6 × 4 + 2 × 9 × (6 + 4) + π × 9² = 24.0 + 180.0 + 254.5 = 458.5 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 1 × 458.5 × 2 × 10−6 = 9.169 × 10−4 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.001 (metal roof on a metal structure); PC = 0 (no connected lines: CLD = 0, Table B.4) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 9.169 × 10−4 × 0.01 × 0.01 = 9.169 × 10−8; RB = ND·PB·LB = 9.169 × 10−4 × 0.001 × 0.1 = 9.169 × 10−8; RC = ND·PC·LC = 9.169 × 10−4 × 0 × 0.01 = 0 |
| R1 check | R1 = RA + RB + RC = 9.169 × 10−8 + 9.169 × 10−8 + 0 → 1.834 × 10−7 ≤ RT = 10−5/yr (1.8 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 1.834 × 10−7/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 6 × 4 + 6 × 3 × (6 + 4) + 9π × 3² = 458.5 m²; N_D = 1 × 458.5 × 2 × 1e-6 = 0.0009169/yr; R_A = N_D × 0.01 × 0.01 = 9.169e-08, R_B = N_D × 0.001 × 0.1 = 9.169e-08, P_C = 0 (no connected line, C_LD = 0, Table B.4); R_C = N_D × 0 × 0.01 = 0; R1 = 1.834e-07 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-hilltop-hut) |
Example 12 — Metal roof and metal frame
A metal-clad steel-frame building has P_B 0.001, so R_B is negligible and the building passes without an LPS.
Given: Structure 60 × 30 × 12 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located among objects of the same height or smaller (flat); metal roof on a metal structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: electrical insulation; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 60 × 30 + 2 × 36 × (60 + 30) + π × 36² = 1,800.0 + 6,480.0 + 4,071.5 = 12,351.5 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 12,351.5 × 0.5 × 10−6 = 0.01235 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.001 (metal roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.01235 × 0.01 × 0.01 = 1.235 × 10−6; RB = ND·PB·LB = 0.01235 × 0.001 × 0.1 = 1.235 × 10−6; RC = ND·PC·LC = 0.01235 × 0.02 × 0.01 = 2.470 × 10−6 |
| R1 check | R1 = RA + RB + RC = 1.235 × 10−6 + 1.235 × 10−6 + 2.470 × 10−6 → 4.941 × 10−6 ≤ RT = 10−5/yr (49.4 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 4.941 × 10−6/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 60 × 30 + 6 × 12 × (60 + 30) + 9π × 12² = 12351.5 m²; N_D = 2 × 12351.5 × 0.5 × 1e-6 = 0.01235/yr; R_A = N_D × 0.01 × 0.01 = 1.235e-06, R_B = N_D × 0.001 × 0.1 = 1.235e-06, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 2.47e-06; R1 = 4.941e-06 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-metal-structure) |
Example 13 — Non-metal roof on a metal frame
P_B 0.01 for a non-metallic roof on a steel frame: R1 is above R_T and a class IV LPS is enough.
Given: Structure 60 × 30 × 12 m (L × W × H), ground flash density NG = 3 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof on a metal structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: electrical insulation; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 60 × 30 + 2 × 36 × (60 + 30) + π × 36² = 1,800.0 + 6,480.0 + 4,071.5 = 12,351.5 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 3 × 12,351.5 × 0.5 × 10−6 = 0.01853 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.01 (non-metallic roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.01853 × 0.01 × 0.01 = 1.853 × 10−6; RB = ND·PB·LB = 0.01853 × 0.01 × 0.1 = 1.853 × 10−5; RC = ND·PC·LC = 0.01853 × 0.02 × 0.01 = 3.705 × 10−6 |
| R1 check | R1 = RA + RB + RC = 1.853 × 10−6 + 1.853 × 10−5 + 3.705 × 10−6 → 2.409 × 10−5 > RT = 10−5/yr (240.9 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 1.853 × 10−5): class IV: 1.853 × 10−6 + 1.853 × 10−5 × 0.2 + 3.705 × 10−6 = 9.264 × 10−6 ≤ RT → class IV; rolling sphere 60 m, mesh 20 × 20 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class IV LPS → 9.264 × 10−6 ≤ RT = 10−5/yr (92.6 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 2.409 × 10−5/yr; recommended LPS: class IV; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 60 × 30 + 6 × 12 × (60 + 30) + 9π × 12² = 12351.5 m²; N_D = 3 × 12351.5 × 0.5 × 1e-6 = 0.01853/yr; R_A = N_D × 0.01 × 0.01 = 1.853e-06, R_B = N_D × 0.01 × 0.1 = 1.853e-05, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 3.705e-06; R1 = 2.409e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): IV, residual R1 = 9.264e-06; rolling sphere 60 m, mesh 20 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-non-metal-roof-metal-frame) |
Example 14 — Thatched-roof cottage
A thatched roof (P_B 0.3) makes R_B dominant even on a small house; the LPS class follows from R_B alone.
Given: Structure 12 × 8 × 6 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located isolated, no other objects nearby (moderate); thatched roof, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: warning notices; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 12 × 8 + 2 × 18 × (12 + 8) + π × 18² = 96.0 + 720.0 + 1,017.9 = 1,833.9 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 1,833.9 × 1 × 10−6 = 3.668 × 10−3 /yr |
| Probabilities | PA = 0.1 (warning notices); PB = 0.3 (thatched roof); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 3.668 × 10−3 × 0.1 × 0.01 = 3.668 × 10−6; RB = ND·PB·LB = 3.668 × 10−3 × 0.3 × 0.1 = 1.100 × 10−4; RC = ND·PC·LC = 3.668 × 10−3 × 0.02 × 0.01 = 7.336 × 10−7 |
| R1 check | R1 = RA + RB + RC = 3.668 × 10−6 + 1.100 × 10−4 + 7.336 × 10−7 → 1.144 × 10−4 > RT = 10−5/yr (1,144.3 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 1.100 × 10−4): class IV: 3.668 × 10−6 + 1.100 × 10−4 × 0.2 + 7.336 × 10−7 = 2.641 × 10−5 > RT; class III: 3.668 × 10−6 + 1.100 × 10−4 × 0.1 + 7.336 × 10−7 = 1.540 × 10−5 > RT; class II: 3.668 × 10−6 + 1.100 × 10−4 × 0.05 + 7.336 × 10−7 = 9.903 × 10−6 ≤ RT → class II; rolling sphere 30 m, mesh 10 × 10 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class II LPS → 9.903 × 10−6 ≤ RT = 10−5/yr (99.0 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 1.144 × 10−4/yr; recommended LPS: class II; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 12 × 8 + 6 × 6 × (12 + 8) + 9π × 6² = 1833.9 m²; N_D = 2 × 1833.9 × 1 × 1e-6 = 0.003668/yr; R_A = N_D × 0.1 × 0.01 = 3.668e-06, R_B = N_D × 0.3 × 0.1 = 0.00011, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 7.336e-07; R1 = 0.0001144 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): II, residual R1 = 9.903e-06; rolling sphere 30 m, mesh 10 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-thatched-roof) |
Example 15 — High-occupancy hall
High occupancy raises L_A to 0.1; warning notices (P_A 0.1) are not enough to keep R_A within R_T.
Given: Structure 50 × 30 × 12 m (L × W × H), ground flash density NG = 1.5 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, high occupancy; internal systems: LV power line (standard consequence); touch/step measures: warning notices; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 50 × 30 + 2 × 36 × (50 + 30) + π × 36² = 1,500.0 + 5,760.0 + 4,071.5 = 11,331.5 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 1.5 × 11,331.5 × 0.5 × 10−6 = 8.499 × 10−3 /yr |
| Probabilities | PA = 0.1 (warning notices); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)1 = 0.02 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.1 (high occupancy); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 8.499 × 10−3 × 0.1 × 0.1 = 8.499 × 10−5; RB = ND·PB·LB = 8.499 × 10−3 × 0.1 × 0.1 = 8.499 × 10−5; RC = ND·PC·LC = 8.499 × 10−3 × 0.02 × 0.01 = 1.700 × 10−6 |
| R1 check | R1 = RA + RB + RC = 8.499 × 10−5 + 8.499 × 10−5 + 1.700 × 10−6 → 1.717 × 10−4 > RT = 10−5/yr (1,716.7 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 8.499 × 10−5): class IV: 8.499 × 10−5 + 8.499 × 10−5 × 0.2 + 1.700 × 10−6 = 1.037 × 10−4 > RT; class III: 8.499 × 10−5 + 8.499 × 10−5 × 0.1 + 1.700 × 10−6 = 9.518 × 10−5 > RT; class II: 8.499 × 10−5 + 8.499 × 10−5 × 0.05 + 1.700 × 10−6 = 9.094 × 10−5 > RT; class I: 8.499 × 10−5 + 8.499 × 10−5 × 0.02 + 1.700 × 10−6 = 8.839 × 10−5 > RT — no class achieves RT, class I recommended as the ceiling; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 8.839 × 10−5 > RT = 10−5/yr (883.9 %) FAIL |
| Result | 0/2 checks pass → FAIL; R1 = 1.717 × 10−4/yr; recommended LPS: class I; governing: risk r1 with recommended lps. Even an LPS of class I leaves R1 = 8.84e-05 > 1e-05; the remaining risk is dominated by RA, which an LPS does not reduce in this engine — add touch/step protection measures (RA) or coordinated SPDs (RC). |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 50 × 30 + 6 × 12 × (50 + 30) + 9π × 12² = 11331.5 m²; N_D = 1.5 × 11331.5 × 0.5 × 1e-6 = 0.008499/yr; R_A = N_D × 0.1 × 0.1 = 8.499e-05, R_B = N_D × 0.1 × 0.1 = 8.499e-05, P_C = 1 − (1 − 0.02 × 1)^1 = 0.02 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.02 × 0.01 = 1.7e-06; R1 = 0.0001717 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I (none suffices, I is the ceiling), residual R1 = 8.839e-05; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-high-occupancy) |
Example 16 — Structure with no fire risk
L_B 0 removes R_B entirely, so R1 = R_A + R_C stays above R_T and the recommended class I LPS cannot change it.
Given: Structure 80 × 40 × 15 m (L × W × H), ground flash density NG = 4 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, no fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: electrical insulation; surge protection: coordinated SPDs for LPL III–IV; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 80 × 40 + 2 × 45 × (80 + 40) + π × 45² = 3,200.0 + 10,800.0 + 6,361.7 = 20,361.7 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 4 × 20,361.7 × 0.5 × 10−6 = 0.04072 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.05 × 1)1 = 0.05 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL III–IV, PSPD = 0.05, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0 (no fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.04072 × 0.01 × 0.01 = 4.072 × 10−6; RB = ND·PB·LB = 0.04072 × 0.1 × 0 = 0; RC = ND·PC·LC = 0.04072 × 0.05 × 0.01 = 2.036 × 10−5 |
| R1 check | R1 = RA + RB + RC = 4.072 × 10−6 + 0 + 2.036 × 10−5 → 2.443 × 10−5 > RT = 10−5/yr (244.3 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 0): class IV: 4.072 × 10−6 + 0 × 0.2 + 2.036 × 10−5 = 2.443 × 10−5 > RT; class III: 4.072 × 10−6 + 0 × 0.1 + 2.036 × 10−5 = 2.443 × 10−5 > RT; class II: 4.072 × 10−6 + 0 × 0.05 + 2.036 × 10−5 = 2.443 × 10−5 > RT; class I: 4.072 × 10−6 + 0 × 0.02 + 2.036 × 10−5 = 2.443 × 10−5 > RT — no class achieves RT, class I recommended as the ceiling; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 2.443 × 10−5 > RT = 10−5/yr (244.3 %) FAIL |
| Result | 0/2 checks pass → FAIL; R1 = 2.443 × 10−5/yr; recommended LPS: class I; governing: risk r1 with recommended lps. Even an LPS of class I leaves R1 = 2.44e-05 > 1e-05; the remaining risk is dominated by RC, which an LPS does not reduce in this engine — add touch/step protection measures (RA) or coordinated SPDs (RC). |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 80 × 40 + 6 × 15 × (80 + 40) + 9π × 15² = 20361.7 m²; N_D = 4 × 20361.7 × 0.5 × 1e-6 = 0.04072/yr; R_A = N_D × 0.01 × 0.01 = 4.072e-06, R_B = N_D × 0.1 × 0 = 0, P_C = 1 − (1 − 0.05 × 1)^1 = 0.05 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.05, Table B.3); R_C = N_D × 0.05 × 0.01 = 2.036e-05; R1 = 2.443e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I (none suffices, I is the ceiling), residual R1 = 2.443e-05; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-no-fire-risk) |
Example 17 — Explosion-risk process building
L_B 1 for explosion risk on a steel-framed building (P_B 0.01): class II leaves R1 above R_T and class I is required.
Given: Structure 30 × 20 × 10 m (L × W × H), ground flash density NG = 7 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof on a metal structure, explosion risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: equipotential bonding; surge protection: coordinated SPDs for LPL I; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 30 × 20 + 2 × 30 × (30 + 20) + π × 30² = 600.0 + 3,000.0 + 2,827.4 = 6,427.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 7 × 6,427.4 × 0.5 × 10−6 = 0.0225 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.01 (non-metallic roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.01 × 1)1 = 0.01 (LV power line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL I, PSPD = 0.01, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 1 (explosion risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 0.0225 × 0.01 × 0.01 = 2.250 × 10−6; RB = ND·PB·LB = 0.0225 × 0.01 × 1 = 2.250 × 10−4; RC = ND·PC·LC = 0.0225 × 0.01 × 0.01 = 2.250 × 10−6 |
| R1 check | R1 = RA + RB + RC = 2.250 × 10−6 + 2.250 × 10−4 + 2.250 × 10−6 → 2.295 × 10−4 > RT = 10−5/yr (2,294.6 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 2.250 × 10−4): class IV: 2.250 × 10−6 + 2.250 × 10−4 × 0.2 + 2.250 × 10−6 = 4.949 × 10−5 > RT; class III: 2.250 × 10−6 + 2.250 × 10−4 × 0.1 + 2.250 × 10−6 = 2.700 × 10−5 > RT; class II: 2.250 × 10−6 + 2.250 × 10−4 × 0.05 + 2.250 × 10−6 = 1.575 × 10−5 > RT; class I: 2.250 × 10−6 + 2.250 × 10−4 × 0.02 + 2.250 × 10−6 = 8.998 × 10−6 ≤ RT → class I; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 8.998 × 10−6 ≤ RT = 10−5/yr (90.0 %) PASS |
| Result | 1/2 checks pass → FAIL; R1 = 2.295 × 10−4/yr; recommended LPS: class I; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 30 × 20 + 6 × 10 × (30 + 20) + 9π × 10² = 6427.4 m²; N_D = 7 × 6427.4 × 0.5 × 1e-6 = 0.0225/yr; R_A = N_D × 0.01 × 0.01 = 2.25e-06, R_B = N_D × 0.01 × 1 = 0.000225, P_C = 1 − (1 − 0.01 × 1)^1 = 0.01 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.01, Table B.3); R_C = N_D × 0.01 × 0.01 = 2.25e-06; R1 = 0.0002295 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I, residual R1 = 8.998e-06; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-explosion-risk) |
Example 18 — Telecom equipment with critical consequence
One unshielded telecom line with no SPDs (P_C 1) and a critical failure consequence (L_C 0.1): R_C dominates and an LPS cannot fix it.
Given: Structure 20 × 10 × 4 m (L × W × H), ground flash density NG = 6 flashes/km²/yr, located surrounded by higher objects; metal roof on a metal structure, ordinary fire risk, occupied; internal systems: telecom line (critical consequence); touch/step measures: electrical insulation; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 20 × 10 + 2 × 12 × (20 + 10) + π × 12² = 200.0 + 720.0 + 452.4 = 1,372.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 6 × 1,372.4 × 0.25 × 10−6 = 2.059 × 10−3 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.001 (metal roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 1 × 1)1 = 1 (telecom line, n = 1, unshielded CLD = 1; no coordinated SPDs, PSPD = 1, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.1 (critical consequence) |
| Risk components | RA = ND·PA·LA = 2.059 × 10−3 × 0.01 × 0.01 = 2.059 × 10−7; RB = ND·PB·LB = 2.059 × 10−3 × 0.001 × 0.1 = 2.059 × 10−7; RC = ND·PC·LC = 2.059 × 10−3 × 1 × 0.1 = 2.059 × 10−4 |
| R1 check | R1 = RA + RB + RC = 2.059 × 10−7 + 2.059 × 10−7 + 2.059 × 10−4 → 2.063 × 10−4 > RT = 10−5/yr (2,062.7 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 2.059 × 10−7): class IV: 2.059 × 10−7 + 2.059 × 10−7 × 0.2 + 2.059 × 10−4 = 2.061 × 10−4 > RT; class III: 2.059 × 10−7 + 2.059 × 10−7 × 0.1 + 2.059 × 10−4 = 2.061 × 10−4 > RT; class II: 2.059 × 10−7 + 2.059 × 10−7 × 0.05 + 2.059 × 10−4 = 2.061 × 10−4 > RT; class I: 2.059 × 10−7 + 2.059 × 10−7 × 0.02 + 2.059 × 10−4 = 2.061 × 10−4 > RT — no class achieves RT, class I recommended as the ceiling; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 2.061 × 10−4 > RT = 10−5/yr (2,060.7 %) FAIL |
| Result | 0/2 checks pass → FAIL; R1 = 2.063 × 10−4/yr; recommended LPS: class I; governing: risk r1 with recommended lps. Even an LPS of class I leaves R1 = 0.000206 > 1e-05; the remaining risk is dominated by RC, which an LPS does not reduce in this engine — add touch/step protection measures (RA) or coordinated SPDs (RC). |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 20 × 10 + 6 × 4 × (20 + 10) + 9π × 4² = 1372.4 m²; N_D = 6 × 1372.4 × 0.25 × 1e-6 = 0.002059/yr; R_A = N_D × 0.01 × 0.01 = 2.059e-07, R_B = N_D × 0.001 × 0.1 = 2.059e-07, P_C = 1 − (1 − 1 × 1)^1 = 1 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 1, Table B.3); R_C = N_D × 1 × 0.1 = 0.0002059; R1 = 0.0002063 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I (none suffices, I is the ceiling), residual R1 = 0.0002061; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-telecom-critical) |
Example 19 — Same telecom building with LPL III–IV SPDs
SPDs designed for LPL III–IV (P_SPD 0.05, Table B.3) leave R_C = N_D × 0.05 × 0.1 just above R_T; an LPS cannot remove it, so better-coordinated SPDs are needed.
Given: Structure 20 × 10 × 4 m (L × W × H), ground flash density NG = 6 flashes/km²/yr, located surrounded by higher objects; metal roof on a metal structure, ordinary fire risk, occupied; internal systems: telecom line (critical consequence); touch/step measures: electrical insulation; surge protection: coordinated SPDs for LPL III–IV; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 20 × 10 + 2 × 12 × (20 + 10) + π × 12² = 200.0 + 720.0 + 452.4 = 1,372.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 6 × 1,372.4 × 0.25 × 10−6 = 2.059 × 10−3 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.001 (metal roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.05 × 1)1 = 0.05 (telecom line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL III–IV, PSPD = 0.05, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.1 (critical consequence) |
| Risk components | RA = ND·PA·LA = 2.059 × 10−3 × 0.01 × 0.01 = 2.059 × 10−7; RB = ND·PB·LB = 2.059 × 10−3 × 0.001 × 0.1 = 2.059 × 10−7; RC = ND·PC·LC = 2.059 × 10−3 × 0.05 × 0.1 = 1.029 × 10−5 |
| R1 check | R1 = RA + RB + RC = 2.059 × 10−7 + 2.059 × 10−7 + 1.029 × 10−5 → 1.070 × 10−5 > RT = 10−5/yr (107.0 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 2.059 × 10−7): class IV: 2.059 × 10−7 + 2.059 × 10−7 × 0.2 + 1.029 × 10−5 = 1.054 × 10−5 > RT; class III: 2.059 × 10−7 + 2.059 × 10−7 × 0.1 + 1.029 × 10−5 = 1.052 × 10−5 > RT; class II: 2.059 × 10−7 + 2.059 × 10−7 × 0.05 + 1.029 × 10−5 = 1.051 × 10−5 > RT; class I: 2.059 × 10−7 + 2.059 × 10−7 × 0.02 + 1.029 × 10−5 = 1.050 × 10−5 > RT — no class achieves RT, class I recommended as the ceiling; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 1.050 × 10−5 > RT = 10−5/yr (105.0 %) FAIL |
| Result | 0/2 checks pass → FAIL; R1 = 1.070 × 10−5/yr; recommended LPS: class I; governing: risk r1 with recommended lps. Even an LPS of class I leaves R1 = 1.05e-05 > 1e-05; the remaining risk is dominated by RC, which an LPS does not reduce in this engine — add touch/step protection measures (RA) or coordinated SPDs (RC). |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 20 × 10 + 6 × 4 × (20 + 10) + 9π × 4² = 1372.4 m²; N_D = 6 × 1372.4 × 0.25 × 1e-6 = 0.002059/yr; R_A = N_D × 0.01 × 0.01 = 2.059e-07, R_B = N_D × 0.001 × 0.1 = 2.059e-07, P_C = 1 − (1 − 0.05 × 1)^1 = 0.05 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.05, Table B.3); R_C = N_D × 0.05 × 0.1 = 1.029e-05; R1 = 1.07e-05 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I (none suffices, I is the ceiling), residual R1 = 1.05e-05; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-telecom-critical-spd1) |
Example 20 — Same telecom building with SPD level 3
Coordinated SPDs designed for LPL I (P_SPD 0.01, Table B.3) cut P_C to 0.01 and the building passes.
Given: Structure 20 × 10 × 4 m (L × W × H), ground flash density NG = 6 flashes/km²/yr, located surrounded by higher objects; metal roof on a metal structure, ordinary fire risk, occupied; internal systems: telecom line (critical consequence); touch/step measures: electrical insulation; surge protection: coordinated SPDs for LPL I; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 20 × 10 + 2 × 12 × (20 + 10) + π × 12² = 200.0 + 720.0 + 452.4 = 1,372.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 6 × 1,372.4 × 0.25 × 10−6 = 2.059 × 10−3 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.001 (metal roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.01 × 1)1 = 0.01 (telecom line, n = 1, unshielded CLD = 1; coordinated SPDs for LPL I, PSPD = 0.01, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.1 (critical consequence) |
| Risk components | RA = ND·PA·LA = 2.059 × 10−3 × 0.01 × 0.01 = 2.059 × 10−7; RB = ND·PB·LB = 2.059 × 10−3 × 0.001 × 0.1 = 2.059 × 10−7; RC = ND·PC·LC = 2.059 × 10−3 × 0.01 × 0.1 = 2.059 × 10−6 |
| R1 check | R1 = RA + RB + RC = 2.059 × 10−7 + 2.059 × 10−7 + 2.059 × 10−6 → 2.470 × 10−6 ≤ RT = 10−5/yr (24.7 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 2.470 × 10−6/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 20 × 10 + 6 × 4 × (20 + 10) + 9π × 4² = 1372.4 m²; N_D = 6 × 1372.4 × 0.25 × 1e-6 = 0.002059/yr; R_A = N_D × 0.01 × 0.01 = 2.059e-07, R_B = N_D × 0.001 × 0.1 = 2.059e-07, P_C = 1 − (1 − 0.01 × 1)^1 = 0.01 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.01, Table B.3); R_C = N_D × 0.01 × 0.1 = 2.059e-06; R1 = 2.47e-06 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-telecom-critical-spd3) |
Example 21 — LV and telecom lines combined
Two connected lines with LPL II SPDs: P_C = 1 − (1 − 0.02)² = 0.0396, almost twice the single-line 0.02 — adding a line raises the internal-systems risk; R1 still meets R_T.
Given: Structure 40 × 20 × 10 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located among objects of the same height or smaller (flat); metal roof on a metal structure, ordinary fire risk, occupied; internal systems: LV power and telecom lines (standard consequence); touch/step measures: equipotential bonding; surge protection: coordinated SPDs for LPL II; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 40 × 20 + 2 × 30 × (40 + 20) + π × 30² = 800.0 + 3,600.0 + 2,827.4 = 7,227.4 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 7,227.4 × 0.5 × 10−6 = 7.227 × 10−3 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.001 (metal roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 0.02 × 1)2 = 0.0396 (LV power and telecom lines, n = 2, unshielded CLD = 1; coordinated SPDs for LPL II, PSPD = 0.02, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 7.227 × 10−3 × 0.01 × 0.01 = 7.227 × 10−7; RB = ND·PB·LB = 7.227 × 10−3 × 0.001 × 0.1 = 7.227 × 10−7; RC = ND·PC·LC = 7.227 × 10−3 × 0.0396 × 0.01 = 2.862 × 10−6 |
| R1 check | R1 = RA + RB + RC = 7.227 × 10−7 + 7.227 × 10−7 + 2.862 × 10−6 → 4.308 × 10−6 ≤ RT = 10−5/yr (43.1 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 4.308 × 10−6/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 40 × 20 + 6 × 10 × (40 + 20) + 9π × 10² = 7227.4 m²; N_D = 2 × 7227.4 × 0.5 × 1e-6 = 0.007227/yr; R_A = N_D × 0.01 × 0.01 = 7.227e-07, R_B = N_D × 0.001 × 0.1 = 7.227e-07, P_C = 1 − (1 − 0.02 × 1)^2 = 0.0396 (2 unshielded line(s), C_LD = 1, Table B.4; P_SPD 0.02, Table B.3); R_C = N_D × 0.0396 × 0.01 = 2.862e-06; R1 = 4.308e-06 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-lv-and-telecom-spd2-combined) |
Example 22 — LV + telecom with no life consequence
LV and telecom lines without SPDs give P_C = 1, but no consequence of failure (L_C 0) makes R_C = 0.
Given: Structure 30 × 20 × 8 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located among objects of the same height or smaller (flat); metal roof on a metal structure, ordinary fire risk, occupied; internal systems: LV power and telecom lines (no consequence for life); touch/step measures: equipotential bonding; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 30 × 20 + 2 × 24 × (30 + 20) + π × 24² = 600.0 + 2,400.0 + 1,809.6 = 4,809.6 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 4,809.6 × 0.5 × 10−6 = 4.810 × 10−3 /yr |
| Probabilities | PA = 0.01 (equipotential bonding); PB = 0.001 (metal roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 1 × 1)2 = 1 (LV power and telecom lines, n = 2, unshielded CLD = 1; no coordinated SPDs, PSPD = 1, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0 (no consequence for life) |
| Risk components | RA = ND·PA·LA = 4.810 × 10−3 × 0.01 × 0.01 = 4.810 × 10−7; RB = ND·PB·LB = 4.810 × 10−3 × 0.001 × 0.1 = 4.810 × 10−7; RC = ND·PC·LC = 4.810 × 10−3 × 1 × 0 = 0 |
| R1 check | R1 = RA + RB + RC = 4.810 × 10−7 + 4.810 × 10−7 + 0 → 9.619 × 10−7 ≤ RT = 10−5/yr (9.6 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 9.619 × 10−7/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 30 × 20 + 6 × 8 × (30 + 20) + 9π × 8² = 4809.6 m²; N_D = 2 × 4809.6 × 0.5 × 1e-6 = 0.00481/yr; R_A = N_D × 0.01 × 0.01 = 4.81e-07, R_B = N_D × 0.001 × 0.1 = 4.81e-07, P_C = 1 − (1 − 1 × 1)^2 = 1 (2 unshielded line(s), C_LD = 1, Table B.4; P_SPD 1, Table B.3); R_C = N_D × 1 × 0 = 0; R1 = 9.619e-07 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-lv-and-telecom-no-consequence) |
Example 23 — No connected service lines
A stand-alone shed with no incoming lines has C_LD 0 (Table B.4), so P_C = 0 and R_C = 0 even without SPDs.
Given: Structure 8 × 6 × 3 m (L × W × H), ground flash density NG = 3 flashes/km²/yr, located among objects of the same height or smaller (flat); metal roof on a metal structure, ordinary fire risk, occupied; internal systems: no connected lines (standard consequence); touch/step measures: electrical insulation; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 8 × 6 + 2 × 9 × (8 + 6) + π × 9² = 48.0 + 252.0 + 254.5 = 554.5 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 3 × 554.5 × 0.5 × 10−6 = 8.317 × 10−4 /yr |
| Probabilities | PA = 0.01 (electrical insulation); PB = 0.001 (metal roof on a metal structure); PC = 0 (no connected lines: CLD = 0, Table B.4) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 8.317 × 10−4 × 0.01 × 0.01 = 8.317 × 10−8; RB = ND·PB·LB = 8.317 × 10−4 × 0.001 × 0.1 = 8.317 × 10−8; RC = ND·PC·LC = 8.317 × 10−4 × 0 × 0.01 = 0 |
| R1 check | R1 = RA + RB + RC = 8.317 × 10−8 + 8.317 × 10−8 + 0 → 1.663 × 10−7 ≤ RT = 10−5/yr (1.7 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 1.663 × 10−7/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 8 × 6 + 6 × 3 × (8 + 6) + 9π × 3² = 554.5 m²; N_D = 3 × 554.5 × 0.5 × 1e-6 = 0.0008317/yr; R_A = N_D × 0.01 × 0.01 = 8.317e-08, R_B = N_D × 0.001 × 0.1 = 8.317e-08, P_C = 0 (no connected line, C_LD = 0, Table B.4); R_C = N_D × 0 × 0.01 = 0; R1 = 1.663e-07 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-no-internal-systems) |
Example 24 — 300 m tower on a hilltop
At the 300 m height limit the 3H collection radius dominates (A_D ≈ 2.6 km²): dozens of flashes a year, so class I is recommended and R_A and R_C still exceed R_T.
Given: Structure 20 × 20 × 300 m (L × W × H), ground flash density NG = 2 flashes/km²/yr, located isolated on a hilltop or knoll (exposed); metal roof on a metal structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: none; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 20 × 20 + 2 × 900 × (20 + 20) + π × 900² = 400.0 + 72,000.0 + 2,544,690.0 = 2,617,090.0 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 2 × 2,617,090.0 × 2 × 10−6 = 10.47 /yr |
| Probabilities | PA = 1 (none); PB = 0.001 (metal roof on a metal structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 1 × 1)1 = 1 (LV power line, n = 1, unshielded CLD = 1; no coordinated SPDs, PSPD = 1, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 10.47 × 1 × 0.01 = 0.1047; RB = ND·PB·LB = 10.47 × 0.001 × 0.1 = 1.047 × 10−3; RC = ND·PC·LC = 10.47 × 1 × 0.01 = 0.1047 |
| R1 check | R1 = RA + RB + RC = 0.1047 + 1.047 × 10−3 + 0.1047 → 0.2104 > RT = 10−5/yr (2,104,140.4 %) FAIL |
| LPS selection | Try classes from IV, PB × 0.2 / 0.1 / 0.05 / 0.02, R1 = RA + ND·PB·LB × factor + RC (unprotected ND·PB·LB = 1.047 × 10−3): class IV: 0.1047 + 1.047 × 10−3 × 0.2 + 0.1047 = 0.2096 > RT; class III: 0.1047 + 1.047 × 10−3 × 0.1 + 0.1047 = 0.2095 > RT; class II: 0.1047 + 1.047 × 10−3 × 0.05 + 0.1047 = 0.2094 > RT; class I: 0.1047 + 1.047 × 10−3 × 0.02 + 0.1047 = 0.2094 > RT — no class achieves RT, class I recommended as the ceiling; rolling sphere 20 m, mesh 5 × 5 m (IEC 62305-3 Table 2) |
| Residual R1 | R1 with class I LPS → 0.2094 > RT = 10−5/yr (2,093,881.4 %) FAIL |
| Result | 0/2 checks pass → FAIL; R1 = 0.2104/yr; recommended LPS: class I; governing: risk r1 with recommended lps. Even an LPS of class I leaves R1 = 0.209 > 1e-05; the remaining risk is dominated by RA, which an LPS does not reduce in this engine — add touch/step protection measures (RA) or coordinated SPDs (RC). |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 20 × 20 + 6 × 300 × (20 + 20) + 9π × 300² = 2617090.0 m²; N_D = 2 × 2617090.0 × 2 × 1e-6 = 10.47/yr; R_A = N_D × 1 × 0.01 = 0.1047, R_B = N_D × 0.001 × 0.1 = 0.001047, P_C = 1 − (1 − 1 × 1)^1 = 1 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 1, Table B.3); R_C = N_D × 1 × 0.01 = 0.1047; R1 = 0.2104 > R_T 1e-5 (Table 4); lowest LPS class with R1 ≤ R_T (P_B × 0.2/0.1/0.05/0.02 for IV/III/II/I, Table B.2): I (none suffices, I is the ceiling), residual R1 = 0.2094; rolling sphere 20 m, mesh 5 m (IEC 62305-3 Table 2). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-tall-tower-300m) |
Example 25 — Smallest structure at the lowest flash density
A 1 × 1 × 1 m kiosk at N_G 0.1 (both at their input minimums) has a negligible risk.
Given: Structure 1 × 1 × 1 m (L × W × H), ground flash density NG = 0.1 flashes/km²/yr, located among objects of the same height or smaller (flat); non-metallic roof and structure, ordinary fire risk, occupied; internal systems: LV power line (standard consequence); touch/step measures: none; surge protection: no coordinated SPDs; existing LPS: none.
| Collection area | AD = L·W + 2·(3H)·(L + W) + π·(3H)² = 1 × 1 + 2 × 3 × (1 + 1) + π × 3² = 1.0 + 12.0 + 28.3 = 41.3 m² |
|---|---|
| Dangerous events | ND = NG × AD × CD × 10−6 = 0.1 × 41.3 × 0.5 × 10−6 = 2.064 × 10−6 /yr |
| Probabilities | PA = 1 (none); PB = 0.1 (non-metallic roof and structure); PC = 1 − (1 − PSPD·CLD)n = 1 − (1 − 1 × 1)1 = 1 (LV power line, n = 1, unshielded CLD = 1; no coordinated SPDs, PSPD = 1, Table B.3) |
| Losses | LA = 0.01 (occupied); LB = 0.1 (ordinary fire risk); LC = 0.01 (standard consequence) |
| Risk components | RA = ND·PA·LA = 2.064 × 10−6 × 1 × 0.01 = 2.064 × 10−8; RB = ND·PB·LB = 2.064 × 10−6 × 0.1 × 0.1 = 2.064 × 10−8; RC = ND·PC·LC = 2.064 × 10−6 × 1 × 0.01 = 2.064 × 10−8 |
| R1 check | R1 = RA + RB + RC = 2.064 × 10−8 + 2.064 × 10−8 + 2.064 × 10−8 → 6.191 × 10−8 ≤ RT = 10−5/yr (0.6 %) PASS |
| LPS selection | R1 ≤ RT: no (further) lightning protection system is required |
| Result | 1/1 checks pass → PASS; R1 = 6.191 × 10−8/yr; recommended LPS: none; governing: risk r1 |
| Reference | Hand calculation, IEC 62305-2:2010 Annex A: A_D = 1 × 1 + 6 × 1 × (1 + 1) + 9π × 1² = 41.3 m²; N_D = 0.1 × 41.3 × 0.5 × 1e-6 = 2.064e-06/yr; R_A = N_D × 1 × 0.01 = 2.064e-08, R_B = N_D × 0.1 × 0.1 = 2.064e-08, P_C = 1 − (1 − 1 × 1)^1 = 1 (1 unshielded line(s), C_LD = 1, Table B.4; P_SPD 1, Table B.3); R_C = N_D × 1 × 0.01 = 2.064e-08; R1 = 6.191e-08 ≤ R_T 1e-5 (Table 4). P_A, P_B and L factors are the tool's published category values (help page factor table); P_C per IEC 62305-2 B.4 with unshielded lines (C_LD 1, Table B.4) and P_SPD from Table B.3. (validation case c0038-minimum-inputs) |
Standards & References
- IEC 62305-1:2010 — Protection against lightning: General principles
- IEC 62305-2:2010 — Protection against lightning: Risk management. Primary reference for risk assessment methodology.
- IEC 62305-3:2010 — Protection against lightning: Physical damage and life hazard
- IEC 62305-4:2010 — Protection against lightning: Electrical and electronic systems
- AS/NZS 1768:2007 — Lightning protection (Australian/NZ implementation)
Tips & Limitations
- This calculator implements Risk R1 (loss of human life) only. R4 (economic loss) uses the same framework but with different tolerable risk (10-3).
- Ground flash density Ng should come from local meteorological data. In Australia, typical values range from 0.5 (Tasmania) to 12 (Darwin).
- The location factor Cd significantly affects results. Use “moderate” (Cd = 1) for an isolated structure with no other objects nearby and “exposed” (Cd = 2) only for an isolated structure on a hilltop or knoll (IEC 62305-2 Table A.1).
- An LPS reduces only RB. When RA (touch/step) or RC (internal systems) alone exceeds 10-5, even LPL I cannot achieve the tolerable risk: the calculator still reports LPL I and the residual risk check fails — add touch/step measures or coordinated SPDs.
- Existing LPS reduces risk through the PB efficiency factor. If an existing LPS is already installed but the assessment still shows FAIL, a higher-level LPS is needed.
- Surge protection devices (SPDs) reduce the PC component (internal system failures) but do not affect the physical damage risk RB. Even SPDs designed for LPL I only reduce PC to 0.01 per line, so with a critical failure consequence RC can still govern.
- For structures with explosion risk, R1 is almost always above the tolerable threshold — LPL I is typically required.
Developer Guide — Architecture
This calculator follows the standard calcs component pattern:
components/c0038_lightning_risk_assessment/ ├── __init__.py # Docstring ├── apps.py # Django AppConfig ├── calculations.py # Pure Python — IEC 62305-2 tables and formulas ├── component.py # Schema, Calculator class, builders, registration ├── equations.py # LaTeX equation templates ├── excel_generator.py # Excel report generator └── templates/.../sidebar_form.html # Vue 3 sidebar form
This is the most table-heavy calc — calculations.py contains all
IEC 62305-2 lookup tables as Python dictionaries.
Developer Guide — Code Paths
| Purpose | File | Key Function / Class |
|---|---|---|
| Collection area | calculations.py | calculate_collection_area(L, W, H) |
| Expected strikes | calculations.py | calculate_expected_strikes(Ng, Ad, Cd) |
| Internal systems PC | calculations.py | calculate_internal_systems_probability(n_lines, P_SPD, C_LD) |
| Risk components | calculations.py | calculate_risk_components() |
| Protection level | calculations.py | determine_protection_level() |
| Main entry | calculations.py | calculate_lightning_risk(data) |
| Validation | component.py | LightningRiskCalculator.validate_parameters() |
| Excel report | excel_generator.py | create_c0038_excel_report(calculation) |
| Registration | component.py | register_component(registry) |
Developer Guide — Testing
# Run all tests for this component pytest calcs/test_c0038_lightning_risk_assessment.py -v
Test coverage includes:
TestCollectionArea— geometric area calculationTestExpectedStrikes— Nd calculation with various Ng and CdTestRiskComponents— individual risk component calculationsTestNoProtectionNeeded— small/sheltered structuresTestProtectionRequired— large/exposed structuresTestProtectionLevel— correct LPL determinationTestExistingLPS— risk reduction from existing protectionTestInternalSystemsProbability— PC per IEC 62305-2 B.4 (PSPD Table B.3, lines combined)TestLocationFactors— CD per IEC 62305-2 Table A.1TestCalculateLightningRisk— end-to-end integrationTestCalculatorClass— validation, round-trip, registration