Generator Sizing Calculator

Jump to section

Overview

Calculates the required generator capacity for industrial and commercial facilities based on connected loads, diversity factors, motor starting characteristics, and fuel autonomy requirements. The calculator determines the sizing basis (running load or motor starting demand), applies a safety margin, and selects the next standard generator size. Supports parallel generator configurations and provides optimisation recommendations such as soft starter installation.

Input Parameters

Facility Parameters

Parameter Type Default Range Description
facility_type Enum manufacturing — Type of facility — determines the diversity factor. Options: continuous_process, manufacturing, commercial, accommodation, essential_services
custom_diversity Number none 0.5 – 1.0 Override the automatic diversity factor with a custom value
safety_margin Number 1.25 1.0 – 2.0 Safety margin applied to required kVA before selecting standard size (1.25 = 25%)

Connected Loads (array)

Each entry in the loads array represents a connected load or group of identical loads. At least one load is required.

Parameter Type Default Range Description
name String required — Descriptive name for the load
power_kw Number required min 0 Power rating in kW (per unit)
quantity Integer 1 min 1 Number of identical loads
load_type Enum motor — Load type: motor, resistive, welding, hvac, pumps, lighting, control
power_factor Number auto 0.5 – 1.0 Power factor (if omitted, a typical value is used based on load_type)
duty_cycle Number 1.0 0.1 – 1.0 Duty cycle factor for intermittent loads
starting_method Enum dol — Motor starting method: dol, star_delta, soft_start, vsd (applies to the motor-driven load types motor, pumps and hvac)

Analysis Options

Parameter Type Default Range Description
include_starting_analysis Boolean True — Include motor starting demand in sizing analysis
fuel_tank_capacity Number none min 0 Fuel tank capacity in litres — enables autonomy calculation
consider_parallel Boolean False — Evaluate a parallel generator configuration
num_parallel_generators Integer 2 2 – 4 Number of parallel units (hidden when consider_parallel is false)

Output Results

Primary Results

Output Unit Description
selected_generator_kva kVA Recommended standard generator size
required_kva kVA Required capacity before rounding to standard size
sizing_basis text "running" or "starting" — which demand drove the selection
generator_utilization % Utilization of the selected generator at diversified running load
fuel_consumption_l_per_hour L/hr Estimated diesel fuel consumption at operating load
fuel_autonomy_hours hr Hours of operation on the specified fuel tank (only if fuel_tank_capacity is provided)

Running Load Analysis

Output Unit Description
running_load.total_kva kVA Total connected load (before diversity)
running_load.diversified_kva kVA Diversified running load
running_load.diversity_factor — Applied diversity factor
running_load.overall_pf — Overall power factor of connected loads

Starting Load Analysis

Output Unit Description
starting_load.largest_starting_kva kVA Starting kVA of the largest motor
starting_load.background_kva kVA kVA of other loads running during motor start
starting_load.total_starting_demand kVA Total demand during motor starting event

Parallel Generator Analysis

Output Unit Description
parallel_generators.size_per_unit_kva kVA Selected standard size per generator unit
parallel_generators.total_capacity_kva kVA Combined capacity of all parallel units
parallel_generators.redundancy_percent % Redundancy above required capacity
parallel_generators.n_plus_1_capable Boolean Whether the configuration can lose one unit and still meet demand

Formulas

Load kVA from kW

\[ S_{load} = \frac{P_{kW} \times D}{\cos\phi} \quad (\text{kVA}) \]

Where \(P_{kW}\) is the rated power, \(D\) is the duty cycle (0.1–1.0), and \(\cos\phi\) is the power factor.

Motor Starting kVA

\[ S_{start} = P_{kW} \times k_{start} \quad (\text{kVA}) \]

Where \(k_{start}\) is the starting multiplier for the chosen starting method. Every motor-driven load is a starting candidate: load types motor, pumps and hvac (pump, compressor and fan motors). \(P_{kW}\) is the rating of one unit — quantity and duty cycle do not change the starting kVA.

Starting Multipliers

Starting Method \(k_{start}\) Notes
Direct-On-Line (DOL) 6.0 Full voltage start — highest starting demand
Star-Delta 2.0 Reduced voltage start (1/3 of DOL current)
Soft Start 2.5 Controlled ramp-up via thyristors
VSD 1.2 Variable Speed Drive — minimal starting impact

Diversified Running Load

\[ S_{diversified} = S_{total} \times f_{diversity} \quad (\text{kVA}) \]

Where \(S_{total} = \sum (S_{load,i} \times n_i)\) is the sum of all individual load kVA values multiplied by quantity, and \(f_{diversity}\) is the diversity factor for the facility type.

Diversity Factors by Facility Type

Facility Type \(f_{diversity}\)
Continuous Process0.95
Manufacturing0.75
Commercial0.80
Accommodation0.85
Essential Services1.00

Total Starting Demand

\[ S_{starting\_demand} = S_{start,largest} + S_{diversified} \quad (\text{kVA}) \]

The worst-case starting event is the motor-driven load (motor, pumps or hvac) with the largest \(S_{start}\) starting while all loads are running at the diversified level.

Sizing Basis

\[ S_{required} = \max\!\left(S_{diversified},\; S_{starting\_demand}\right) \]

The generator is sized for whichever demand is greater: the diversified running load or the total starting demand.

Generator Selection

\[ S_{selected} = \text{next standard size} \geq S_{required} \times m_{safety} \]

Where \(m_{safety}\) is the safety margin (default 1.25). The selected size is the smallest value from the standard sizes list that meets or exceeds the required capacity with margin.

Generator Utilization

\[ U = \frac{S_{required}}{S_{selected}} \times 100 \quad (\%) \]

Fuel Consumption

\[ \dot{F} = S_{selected} \times 0.8 \times f_{load} \times 0.25 \quad (\text{L/hr}) \]

Where \(f_{load} = S_{diversified} / S_{selected}\) is the operating load factor. The 0.8 factor converts kVA to approximate kW, and 0.25 L/kWh is a typical diesel consumption rate.

Fuel Autonomy

\[ t_{autonomy} = \frac{V_{tank}}{\dot{F}} \quad (\text{hours}) \]

Where \(V_{tank}\) is the fuel tank capacity in litres and \(\dot{F}\) is the hourly fuel consumption.

Typical Power Factors

Load Type \(\cos\phi\)
Motor0.87
Resistive1.00
Welding0.70
HVAC0.88
Pumps0.88
Lighting0.95
Control1.00

Standard Generator Sizes (kVA)

Available Sizes
100, 125, 150, 175, 200, 250, 300, 350, 400, 450, 500, 600, 750, 800, 900, 1000, 1250, 1500, 1750, 2000, 2250, 2500, 3000, 3500, 4000, 5000

Worked Examples

The 21 examples below are the validation cases for this calculation. Each one was produced by the calculation engine from the inputs shown, every figure was checked against the independent reference quoted at the end of the example, and the same cases are run against every engine build (see validation scorecard, tool fe_calc_generator; worked examples for every calculation).

#CaseRunning (kVA)Starting (kVA)BasisSelected (kVA)Result
1100 kW resistive load in a commercial building80.0080.00running100PASS
275 kW DOL pump with lighting, two units in parallel109.29559.29starting750FAIL
3Remote accommodation camp with 5000 L tank144.12234.12starting300PASS
44500 kW furnace beyond the standard ratings4,500.00–running5,700PASS
5Press shop with a 0.6 diversity override85.74415.74starting600PASS
6Large DOL pump (load type pumps) sets the starting demand327.761,119.76starting1,500PASS
74000 kW electric boilers on the largest standard rating4,000.00–running5,000PASS
8Manufacturing workshop with VSD machines and welding88.99151.49starting200PASS
9400 kW heater bank with no safety margin400.00–running400PASS
10Hospital standby set with a 1.5 safety margin205.27655.27starting1,000PASS
11Eight 22 kW motors with motor starting excluded189.23–running250PASS
12Cold store with three DOL compressors on four units505.801,165.80starting1,500FAIL
13Four parallel units with a soft-started crusher510.00735.00starting1,000PASS
14Three parallel units carrying the load with one out80.00200.00starting250PASS
15500 kVA essential load on two parallel units500.00–running750FAIL
16Small shop on two 100 kVA units, no motors80.0080.00running100PASS
17Smaller DOL agitator out-starts a larger star-delta mixer175.95445.95starting600PASS
18160 kW soft-started borehole pump193.61593.61starting750PASS
19132 kW star-delta compressor governs starting143.76407.76starting600PASS
20Water pumping station (continuous process)149.57809.57starting1,250PASS
21Welding shop with 50 % duty welders and pump loads80.62170.62starting250PASS

Example 1 — 100 kW resistive load in a commercial building

A purely resistive load with commercial diversity lands exactly on the 100 kVA rating, sized on the running load.

Given: Loads: Heaters 100 kW (resistive, typical pf). Commercial facility (typical diversity); safety margin 1.25, largest-motor starting checked.

Load kVASload = P × duty / pf × qty: Heaters: 100 / 1 = 100.00 kVA
ConnectedStotal = 100.00 = 100.00 kVA; Ptotal = 100.00 kW; overall pf = 100.00 / 100.00 = 1.000
Running loadSdiv = 100.00 × 0.8 (commercial) = 80.00 kVA (80.00 kW)
Starting demandNo motor-driven loads (motor, pumps, hvac) → Ssd = 0 + 80.00 = 80.00 kVA
SizingSreq = max(80.00, 80.00) = 80.00 kVA → sized on running; Sreq × m = 80.00 × 1.25 = 100.00 kVA → next standard rating ≥ 100.00 = 100 kVA PASS
UtilisationRunning = 80.00 / 100 = 80.0 %; peak = 80.00 / 100 = 80.0 %
FuelF = 100 × 0.8 × (80.00 / 100) × 0.25 = 16.00 L/h
Result1/1 checks pass → PASS; 100 kVA set, running utilisation 80.0 %; governing: running load
ReferenceHand calculation: S = 100/1 = 100.00 kVA; running = 100.00 × 0.8 = 80.00 kVA; no motor loads, so starting demand = running load; 80.00 × 1.25 = 100.00 → 100 kVA (running); running utilisation = 80.00/100 = 80.0 %; fuel = 0.25 × 100 × 0.8 × 80.00/100 = 16.00 L/h (validation case c0014-100kw-resistive-commercial)

Example 2 — 75 kW DOL pump with lighting, two units in parallel

A DOL-started pump drives the rating on starting demand; a 2-unit parallel set cannot carry the starting load with one unit out, and the tank gives the autonomy.

Given: Loads: Pump 75 kW (motor, pf 0.85, DOL starting); Lights 20 kW (lighting, typical pf). Essential services facility (typical diversity); safety margin 1.25, largest-motor starting checked, fuel tank 1,000 L, 2 identical units in parallel.

Load kVASload = P × duty / pf × qty: Pump: 75 / 0.85 = 88.24 kVA; Lights: 20 / 0.95 = 21.05 kVA
ConnectedStotal = 88.24 + 21.05 = 109.29 kVA; Ptotal = 95.00 kW; overall pf = 95.00 / 109.29 = 0.869
Running loadSdiv = 109.29 × 1 (essential services) = 109.29 kVA (95.00 kW)
Starting demandLargest starting kVA: Pump 75 kW DOL → Sstart = 6 × 75 = 450.00 kVA; Ssd = 450.00 + 109.29 = 559.29 kVA
SizingSreq = max(109.29, 559.29) = 559.29 kVA → sized on starting; Sreq × m = 559.29 × 1.25 = 699.11 kVA → next standard rating ≥ 699.11 = 750 kVA PASS
UtilisationRunning = 109.29 / 750 = 14.6 %; peak = 559.29 / 750 = 74.6 %
FuelF = 750 × 0.8 × (109.29 / 750) × 0.25 = 21.86 L/h; autonomy = 1,000 / 21.86 = 45.7 h
Parallel setUnit = next standard ≥ 1.1 × 559.29 / 2 = 307.61 → 350 kVA; 2 × 350 = 700 kVA; N−1 = 1 × 350 = 350 kVA vs Sreq 559.29 kVA (159.8 %) FAIL
Result1/2 checks pass → FAIL; 750 kVA set, running utilisation 14.6 %; governing: motor starting. Install soft starter on Pump: Reduce generator from 750 kVA to 400 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 75/0.85 + 20/0.95 = 109.29 kVA; running = 109.29 × 1 = 109.29 kVA; start = 6 × 75 + 109.29 = 559.29 kVA; 559.29 × 1.25 = 699.11 → 750 kVA (starting); running utilisation = 109.29/750 = 14.6 %; peak = 559.29/750 = 74.6 %; fuel = 0.25 × 750 × 0.8 × 109.29/750 = 21.86 L/h; autonomy = 1000/21.86 = 45.7 h; parallel 2 units: 1.1 × 559.29/2 = 307.61 → 350 kVA each, N−1 = 350 kVA < 559.29 kVA (validation case c0014-75kw-dol-pump-with-lighting)

Example 3 — Remote accommodation camp with 5000 L tank

Mixed HVAC, lighting, kitchen, control and a soft-started pump at accommodation diversity, with the typical power factor of each load type and the tank autonomy; the DOL split AC units (hvac is motor-driven) set the starting demand, not the soft-started pump.

Given: Loads: Split AC units 15 kW × 6 (hvac, typical pf, DOL starting); Lighting 12 kW (lighting, typical pf); Kitchen 40 kW (resistive, typical pf); Water pump 11 kW (motor, typical pf, soft-start starting); Control 2 kW (control, typical pf). Accommodation facility (typical diversity); safety margin 1.25, largest-motor starting checked, fuel tank 5,000 L.

Load kVASload = P × duty / pf × qty: Split AC units: 15 / 0.88 × 6 = 102.27 kVA; Lighting: 12 / 0.95 = 12.63 kVA; Kitchen: 40 / 1 = 40.00 kVA; Water pump: 11 / 0.87 = 12.64 kVA; Control: 2 / 1 = 2.00 kVA
ConnectedStotal = 102.27 + 12.63 + 40.00 + 12.64 + 2.00 = 169.55 kVA; Ptotal = 155.00 kW; overall pf = 155.00 / 169.55 = 0.914
Running loadSdiv = 169.55 × 0.85 (accommodation) = 144.12 kVA (131.75 kW)
Starting demandLargest starting kVA: Split AC units 15 kW DOL → Sstart = 6 × 15 = 90.00 kVA; Ssd = 90.00 + 144.12 = 234.12 kVA
SizingSreq = max(144.12, 234.12) = 234.12 kVA → sized on starting; Sreq × m = 234.12 × 1.25 = 292.65 kVA → next standard rating ≥ 292.65 = 300 kVA PASS
UtilisationRunning = 144.12 / 300 = 48.0 %; peak = 234.12 / 300 = 78.0 %
FuelF = 300 × 0.8 × (144.12 / 300) × 0.25 = 28.82 L/h; autonomy = 5,000 / 28.82 = 173.5 h
Result1/1 checks pass → PASS; 300 kVA set, running utilisation 48.0 %; governing: motor starting. Install soft starter on Split AC units: Reduce generator from 300 kVA to 250 kVA
ReferenceHand calculation: S = 15/0.88 × 6 + 12/0.95 + 40/1 + 11/0.87 + 2/1 = 169.55 kVA; running = 169.55 × 0.85 = 144.12 kVA; start = 6 × 15 (Split AC units, hvac) + 144.12 = 234.12 kVA; 234.12 × 1.25 = 292.65 → 300 kVA (starting); running utilisation = 144.12/300 = 48.0 %; peak = 234.12/300 = 78.0 %; fuel = 0.25 × 300 × 0.8 × 144.12/300 = 28.82 L/h; autonomy = 5000/28.82 = 173.5 h (validation case c0014-accommodation-camp)

Example 4 — 4500 kW furnace beyond the standard ratings

Above 5000 kVA the tool rounds up to the next 100 kVA (5625 → 5700 kVA) instead of a list entry.

Given: Loads: Arc furnace supply 4,500 kW (resistive, typical pf). Essential services facility (typical diversity); safety margin 1.25, motor starting not checked.

Load kVASload = P × duty / pf × qty: Arc furnace supply: 4,500 / 1 = 4,500.00 kVA
ConnectedStotal = 4,500.00 = 4,500.00 kVA; Ptotal = 4,500.00 kW; overall pf = 4,500.00 / 4,500.00 = 1.000
Running loadSdiv = 4,500.00 × 1 (essential services) = 4,500.00 kVA (4,500.00 kW)
Starting demandMotor starting not checked (include_motor_starting = no)
SizingSreq = Sdiv = 4,500.00 kVA → sized on running; Sreq × m = 4,500.00 × 1.25 = 5,625.00 kVA → above 5000 kVA, next 100 kVA ≥ 5,625.00 = 5,700 kVA PASS
UtilisationRunning = 4,500.00 / 5,700 = 79.0 %; peak = 4,500.00 / 5,700 = 79.0 %
FuelF = 5,700 × 0.8 × (4,500.00 / 5,700) × 0.25 = 900.00 L/h
Result1/1 checks pass → PASS; 5,700 kVA set, running utilisation 79.0 %; governing: running load
ReferenceHand calculation: S = 4500/1 = 4500.00 kVA; running = 4500.00 × 1 = 4500.00 kVA; 4500.00 × 1.25 = 5625.00 → 5700 kVA (running); running utilisation = 4500.00/5700 = 79.0 %; fuel = 0.25 × 5700 × 0.8 × 4500.00/5700 = 900.00 L/h (validation case c0014-beyond-standard-ratings)

Example 5 — Press shop with a 0.6 diversity override

diversity_factor overrides the manufacturing default of 0.75; six lathes and a 40 % duty welder show quantity and duty cycle in the load kVA.

Given: Loads: Press 55 kW (motor, pf 0.86, DOL starting); Lathes 7.5 kW × 6 (motor, typical pf, DOL starting); Lighting 15 kW (lighting, typical pf); Welder 20 kW (welding, typical pf, duty 0.4). Diversity override 0.6; safety margin 1.25, largest-motor starting checked.

Load kVASload = P × duty / pf × qty: Press: 55 / 0.86 = 63.95 kVA; Lathes: 7.5 / 0.87 × 6 = 51.72 kVA; Lighting: 15 / 0.95 = 15.79 kVA; Welder: 20 × 0.4 / 0.7 = 11.43 kVA
ConnectedStotal = 63.95 + 51.72 + 15.79 + 11.43 = 142.90 kVA; Ptotal = 123.00 kW; overall pf = 123.00 / 142.90 = 0.861
Running loadSdiv = 142.90 × 0.6 (given) = 85.74 kVA (73.80 kW)
Starting demandLargest starting kVA: Press 55 kW DOL → Sstart = 6 × 55 = 330.00 kVA; Ssd = 330.00 + 85.74 = 415.74 kVA
SizingSreq = max(85.74, 415.74) = 415.74 kVA → sized on starting; Sreq × m = 415.74 × 1.25 = 519.67 kVA → next standard rating ≥ 519.67 = 600 kVA PASS
UtilisationRunning = 85.74 / 600 = 14.3 %; peak = 415.74 / 600 = 69.3 %
FuelF = 600 × 0.8 × (85.74 / 600) × 0.25 = 17.15 L/h
Result1/1 checks pass → PASS; 600 kVA set, running utilisation 14.3 %; governing: motor starting. Install soft starter on Press: Reduce generator from 600 kVA to 300 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 55/0.86 + 7.5/0.87 × 6 + 15/0.95 + 20 × 0.4/0.7 = 142.90 kVA; running = 142.90 × 0.6 = 85.74 kVA; start = 6 × 55 + 85.74 = 415.74 kVA; 415.74 × 1.25 = 519.67 → 600 kVA (starting); running utilisation = 85.74/600 = 14.3 %; peak = 415.74/600 = 69.3 %; fuel = 0.25 × 600 × 0.8 × 85.74/600 = 17.15 L/h (validation case c0014-diversity-override)

Example 6 — Large DOL pump (load type pumps) sets the starting demand

A 132 kW pump entered as load type 'pumps' is a motor-driven starting candidate: its DOL start (6 × 132 kW) outweighs the 30 kW motor and drives the rating; quantity 2 does not double the single-unit starting kVA.

Given: Loads: Raw water pump 132 kW × 2 (pumps, typical pf, DOL starting); Dosing skid 30 kW (motor, typical pf, DOL starting); Lighting 10 kW (lighting, typical pf). Continuous process facility (typical diversity); safety margin 1.25, largest-motor starting checked, fuel tank 3,000 L.

Load kVASload = P × duty / pf × qty: Raw water pump: 132 / 0.88 × 2 = 300.00 kVA; Dosing skid: 30 / 0.87 = 34.48 kVA; Lighting: 10 / 0.95 = 10.53 kVA
ConnectedStotal = 300.00 + 34.48 + 10.53 = 345.01 kVA; Ptotal = 304.00 kW; overall pf = 304.00 / 345.01 = 0.881
Running loadSdiv = 345.01 × 0.95 (continuous process) = 327.76 kVA (288.80 kW)
Starting demandLargest starting kVA: Raw water pump 132 kW DOL → Sstart = 6 × 132 = 792.00 kVA; Ssd = 792.00 + 327.76 = 1,119.76 kVA
SizingSreq = max(327.76, 1,119.76) = 1,119.76 kVA → sized on starting; Sreq × m = 1,119.76 × 1.25 = 1,399.70 kVA → next standard rating ≥ 1,399.70 = 1,500 kVA PASS
UtilisationRunning = 327.76 / 1,500 = 21.9 %; peak = 1,119.76 / 1,500 = 74.7 %
FuelF = 1,500 × 0.8 × (327.76 / 1,500) × 0.25 = 65.55 L/h; autonomy = 3,000 / 65.55 = 45.8 h
Result1/1 checks pass → PASS; 1,500 kVA set, running utilisation 21.9 %; governing: motor starting. Install soft starter on Raw water pump: Reduce generator from 1500 kVA to 900 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 132/0.88 × 2 + 30/0.87 + 10/0.95 = 345.01 kVA; running = 345.01 × 0.95 = 327.76 kVA; start = 6 × 132 (Raw water pump, pumps) + 327.76 = 1119.76 kVA; 1119.76 × 1.25 = 1399.70 → 1500 kVA (starting); running utilisation = 327.76/1500 = 21.9 %; peak = 1119.76/1500 = 74.7 %; fuel = 0.25 × 1500 × 0.8 × 327.76/1500 = 65.55 L/h; autonomy = 3000/65.55 = 45.8 h (validation case c0014-large-pump-governs-starting)

Example 7 — 4000 kW electric boilers on the largest standard rating

4000 kVA × 1.25 = 5000 kVA exactly: the largest entry in the standard rating list.

Given: Loads: Electric boiler 2,000 kW × 2 (resistive, typical pf). Essential services facility (typical diversity); safety margin 1.25, motor starting not checked.

Load kVASload = P × duty / pf × qty: Electric boiler: 2,000 / 1 × 2 = 4,000.00 kVA
ConnectedStotal = 4,000.00 = 4,000.00 kVA; Ptotal = 4,000.00 kW; overall pf = 4,000.00 / 4,000.00 = 1.000
Running loadSdiv = 4,000.00 × 1 (essential services) = 4,000.00 kVA (4,000.00 kW)
Starting demandMotor starting not checked (include_motor_starting = no)
SizingSreq = Sdiv = 4,000.00 kVA → sized on running; Sreq × m = 4,000.00 × 1.25 = 5,000.00 kVA → next standard rating ≥ 5,000.00 = 5,000 kVA PASS
UtilisationRunning = 4,000.00 / 5,000 = 80.0 %; peak = 4,000.00 / 5,000 = 80.0 %
FuelF = 5,000 × 0.8 × (4,000.00 / 5,000) × 0.25 = 800.00 L/h
Result1/1 checks pass → PASS; 5,000 kVA set, running utilisation 80.0 %; governing: running load
ReferenceHand calculation: S = 2000/1 × 2 = 4000.00 kVA; running = 4000.00 × 1 = 4000.00 kVA; 4000.00 × 1.25 = 5000.00 → 5000 kVA (running); running utilisation = 4000.00/5000 = 80.0 %; fuel = 0.25 × 5000 × 0.8 × 4000.00/5000 = 800.00 L/h (validation case c0014-largest-standard-rating)

Example 8 — Manufacturing workshop with VSD machines and welding

Two VSD-fed CNC machines, a 60 % duty welding bay, lighting and soft-started HVAC at manufacturing diversity; every motor-driven load (motor, pumps, hvac) enters the starting check, and the soft-started 25 kW HVAC (62.5 kVA) outweighs the VSD CNC drive (36 kVA).

Given: Loads: CNC Machine 30 kW × 2 (motor, typical pf, VSD starting); Welding Bay 15 kW (welding, typical pf, duty 0.6); Lighting 8 kW (lighting, typical pf); HVAC 25 kW (hvac, typical pf, soft-start starting). Manufacturing facility (typical diversity); safety margin 1.25, largest-motor starting checked.

Load kVASload = P × duty / pf × qty: CNC Machine: 30 / 0.87 × 2 = 68.97 kVA; Welding Bay: 15 × 0.6 / 0.7 = 12.86 kVA; Lighting: 8 / 0.95 = 8.42 kVA; HVAC: 25 / 0.88 = 28.41 kVA
ConnectedStotal = 68.97 + 12.86 + 8.42 + 28.41 = 118.65 kVA; Ptotal = 102.00 kW; overall pf = 102.00 / 118.65 = 0.860
Running loadSdiv = 118.65 × 0.75 (manufacturing) = 88.99 kVA (76.50 kW)
Starting demandLargest starting kVA: HVAC 25 kW soft-start → Sstart = 2.5 × 25 = 62.50 kVA; Ssd = 62.50 + 88.99 = 151.49 kVA
SizingSreq = max(88.99, 151.49) = 151.49 kVA → sized on starting; Sreq × m = 151.49 × 1.25 = 189.36 kVA → next standard rating ≥ 189.36 = 200 kVA PASS
UtilisationRunning = 88.99 / 200 = 44.5 %; peak = 151.49 / 200 = 75.8 %
FuelF = 200 × 0.8 × (88.99 / 200) × 0.25 = 17.80 L/h
Result1/1 checks pass → PASS; 200 kVA set, running utilisation 44.5 %; governing: motor starting
ReferenceHand calculation: S = 30/0.87 × 2 + 15 × 0.6/0.7 + 8/0.95 + 25/0.88 = 118.65 kVA; running = 118.65 × 0.75 = 88.99 kVA; start = 2.5 × 25 (HVAC, hvac) + 88.99 = 151.49 kVA; 151.49 × 1.25 = 189.36 → 200 kVA (starting); running utilisation = 88.99/200 = 44.5 %; peak = 151.49/200 = 75.7 %; fuel = 0.25 × 200 × 0.8 × 88.99/200 = 17.80 L/h (validation case c0014-manufacturing-workshop)

Example 9 — 400 kW heater bank with no safety margin

safety_margin 1.0 and a 400 kVA running load land exactly on the 400 kVA rating at 100 % utilisation, which triggers the high-utilisation warning.

Given: Loads: Heater bank 400 kW (resistive, typical pf). Essential services facility (typical diversity); safety margin 1, motor starting not checked.

Load kVASload = P × duty / pf × qty: Heater bank: 400 / 1 = 400.00 kVA
ConnectedStotal = 400.00 = 400.00 kVA; Ptotal = 400.00 kW; overall pf = 400.00 / 400.00 = 1.000
Running loadSdiv = 400.00 × 1 (essential services) = 400.00 kVA (400.00 kW)
Starting demandMotor starting not checked (include_motor_starting = no)
SizingSreq = Sdiv = 400.00 kVA → sized on running; Sreq × m = 400.00 × 1 = 400.00 kVA → next standard rating ≥ 400.00 = 400 kVA PASS
UtilisationRunning = 400.00 / 400 = 100.0 %; peak = 400.00 / 400 = 100.0 %
FuelF = 400 × 0.8 × (400.00 / 400) × 0.25 = 80.00 L/h
Result1/1 checks pass → PASS; 400 kVA set, running utilisation 100.0 %; governing: running load. High generator utilization: Limited margin for transients. Consider larger unit or load shedding strategy.
ReferenceHand calculation: S = 400/1 = 400.00 kVA; running = 400.00 × 1 = 400.00 kVA; 400.00 × 1 = 400.00 → 400 kVA (running); running utilisation = 400.00/400 = 100.0 %; fuel = 0.25 × 400 × 0.8 × 400.00/400 = 80.00 L/h (validation case c0014-margin-1p0-on-rating)

Example 10 — Hospital standby set with a 1.5 safety margin

A 75 kW DOL chiller at essential-services diversity with a 50 % margin and a 3000 L tank.

Given: Loads: Chiller 75 kW (motor, pf 0.85, DOL starting); Lighting 30 kW (lighting, typical pf); Medical equipment 40 kW (control, typical pf); AHU 20 kW × 2 (hvac, typical pf, DOL starting). Essential services facility (typical diversity); safety margin 1.5, largest-motor starting checked, fuel tank 3,000 L.

Load kVASload = P × duty / pf × qty: Chiller: 75 / 0.85 = 88.24 kVA; Lighting: 30 / 0.95 = 31.58 kVA; Medical equipment: 40 / 1 = 40.00 kVA; AHU: 20 / 0.88 × 2 = 45.45 kVA
ConnectedStotal = 88.24 + 31.58 + 40.00 + 45.45 = 205.27 kVA; Ptotal = 185.00 kW; overall pf = 185.00 / 205.27 = 0.901
Running loadSdiv = 205.27 × 1 (essential services) = 205.27 kVA (185.00 kW)
Starting demandLargest starting kVA: Chiller 75 kW DOL → Sstart = 6 × 75 = 450.00 kVA; Ssd = 450.00 + 205.27 = 655.27 kVA
SizingSreq = max(205.27, 655.27) = 655.27 kVA → sized on starting; Sreq × m = 655.27 × 1.5 = 982.90 kVA → next standard rating ≥ 982.90 = 1,000 kVA PASS
UtilisationRunning = 205.27 / 1,000 = 20.5 %; peak = 655.27 / 1,000 = 65.5 %
FuelF = 1,000 × 0.8 × (205.27 / 1,000) × 0.25 = 41.05 L/h; autonomy = 3,000 / 41.05 = 73.1 h
Result1/1 checks pass → PASS; 1,000 kVA set, running utilisation 20.5 %; governing: motor starting. Install soft starter on Chiller: Reduce generator from 1000 kVA to 600 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 75/0.85 + 30/0.95 + 40/1 + 20/0.88 × 2 = 205.27 kVA; running = 205.27 × 1 = 205.27 kVA; start = 6 × 75 + 205.27 = 655.27 kVA; 655.27 × 1.5 = 982.90 → 1000 kVA (starting); running utilisation = 205.27/1000 = 20.5 %; peak = 655.27/1000 = 65.5 %; fuel = 0.25 × 1000 × 0.8 × 205.27/1000 = 41.05 L/h; autonomy = 3000/41.05 = 73.1 h (validation case c0014-margin-1p5-hospital)

Example 11 — Eight 22 kW motors with motor starting excluded

With include_motor_starting false the set is sized on the diversified running load alone, even though DOL motors are present.

Given: Loads: Conveyor motors 22 kW × 8 (motor, typical pf, DOL starting); Resistive heating 50 kW (resistive, typical pf). Manufacturing facility (typical diversity); safety margin 1.25, motor starting not checked.

Load kVASload = P × duty / pf × qty: Conveyor motors: 22 / 0.87 × 8 = 202.30 kVA; Resistive heating: 50 / 1 = 50.00 kVA
ConnectedStotal = 202.30 + 50.00 = 252.30 kVA; Ptotal = 226.00 kW; overall pf = 226.00 / 252.30 = 0.896
Running loadSdiv = 252.30 × 0.75 (manufacturing) = 189.23 kVA (169.50 kW)
Starting demandMotor starting not checked (include_motor_starting = no)
SizingSreq = Sdiv = 189.23 kVA → sized on running; Sreq × m = 189.23 × 1.25 = 236.54 kVA → next standard rating ≥ 236.54 = 250 kVA PASS
UtilisationRunning = 189.23 / 250 = 75.7 %; peak = 189.23 / 250 = 75.7 %
FuelF = 250 × 0.8 × (189.23 / 250) × 0.25 = 37.85 L/h
Result1/1 checks pass → PASS; 250 kVA set, running utilisation 75.7 %; governing: running load
ReferenceHand calculation: S = 22/0.87 × 8 + 50/1 = 252.30 kVA; running = 252.30 × 0.75 = 189.23 kVA; 189.23 × 1.25 = 236.54 → 250 kVA (running); running utilisation = 189.23/250 = 75.7 %; fuel = 0.25 × 250 × 0.8 × 189.23/250 = 37.85 L/h (validation case c0014-no-starting-check)

Example 12 — Cold store with three DOL compressors on four units

Four 350 kVA units fail the N−1 check against a 1166 kVA DOL starting demand; the tool also recommends a soft starter.

Given: Loads: Refrigeration compressor 110 kW × 3 (motor, pf 0.88, DOL starting); Evaporator fans 30 kW × 4 (hvac, typical pf, DOL starting); Lighting 20 kW (lighting, typical pf). Continuous process facility (typical diversity); safety margin 1.25, largest-motor starting checked, 4 identical units in parallel.

Load kVASload = P × duty / pf × qty: Refrigeration compressor: 110 / 0.88 × 3 = 375.00 kVA; Evaporator fans: 30 / 0.88 × 4 = 136.36 kVA; Lighting: 20 / 0.95 = 21.05 kVA
ConnectedStotal = 375.00 + 136.36 + 21.05 = 532.42 kVA; Ptotal = 470.00 kW; overall pf = 470.00 / 532.42 = 0.883
Running loadSdiv = 532.42 × 0.95 (continuous process) = 505.80 kVA (446.50 kW)
Starting demandLargest starting kVA: Refrigeration compressor 110 kW DOL → Sstart = 6 × 110 = 660.00 kVA; Ssd = 660.00 + 505.80 = 1,165.80 kVA
SizingSreq = max(505.80, 1,165.80) = 1,165.80 kVA → sized on starting; Sreq × m = 1,165.80 × 1.25 = 1,457.25 kVA → next standard rating ≥ 1,457.25 = 1,500 kVA PASS
UtilisationRunning = 505.80 / 1,500 = 33.7 %; peak = 1,165.80 / 1,500 = 77.7 %
FuelF = 1,500 × 0.8 × (505.80 / 1,500) × 0.25 = 101.16 L/h
Parallel setUnit = next standard ≥ 1.1 × 1,165.80 / 4 = 320.60 → 350 kVA; 4 × 350 = 1,400 kVA; N−1 = 3 × 350 = 1,050 kVA vs Sreq 1,165.80 kVA (111.0 %) FAIL
Result1/2 checks pass → FAIL; 1,500 kVA set, running utilisation 33.7 %; governing: motor starting. Install soft starter on Refrigeration compressor: Reduce generator from 1500 kVA to 1000 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 110/0.88 × 3 + 30/0.88 × 4 + 20/0.95 = 532.42 kVA; running = 532.42 × 0.95 = 505.80 kVA; start = 6 × 110 + 505.80 = 1165.80 kVA; 1165.80 × 1.25 = 1457.25 → 1500 kVA (starting); running utilisation = 505.80/1500 = 33.7 %; peak = 1165.80/1500 = 77.7 %; fuel = 0.25 × 1500 × 0.8 × 505.80/1500 = 101.16 L/h; parallel 4 units: 1.1 × 1165.80/4 = 320.60 → 350 kVA each, N−1 = 1050 kVA < 1165.80 kVA (validation case c0014-parallel-four-units-fail)

Example 13 — Four parallel units with a soft-started crusher

Four 250 kVA units give 750 kVA with one out, above the 735 kVA starting demand, so N−1 passes.

Given: Loads: Crusher 90 kW (motor, pf 0.9, soft-start starting); Process heaters 410 kW (resistive, typical pf). Essential services facility (typical diversity); safety margin 1.25, largest-motor starting checked, 4 identical units in parallel.

Load kVASload = P × duty / pf × qty: Crusher: 90 / 0.9 = 100.00 kVA; Process heaters: 410 / 1 = 410.00 kVA
ConnectedStotal = 100.00 + 410.00 = 510.00 kVA; Ptotal = 500.00 kW; overall pf = 500.00 / 510.00 = 0.980
Running loadSdiv = 510.00 × 1 (essential services) = 510.00 kVA (500.00 kW)
Starting demandLargest starting kVA: Crusher 90 kW soft-start → Sstart = 2.5 × 90 = 225.00 kVA; Ssd = 225.00 + 510.00 = 735.00 kVA
SizingSreq = max(510.00, 735.00) = 735.00 kVA → sized on starting; Sreq × m = 735.00 × 1.25 = 918.75 kVA → next standard rating ≥ 918.75 = 1,000 kVA PASS
UtilisationRunning = 510.00 / 1,000 = 51.0 %; peak = 735.00 / 1,000 = 73.5 %
FuelF = 1,000 × 0.8 × (510.00 / 1,000) × 0.25 = 102.00 L/h
Parallel setUnit = next standard ≥ 1.1 × 735.00 / 4 = 202.13 → 250 kVA; 4 × 250 = 1,000 kVA; N−1 = 3 × 250 = 750 kVA vs Sreq 735.00 kVA (98.0 %) PASS
Result2/2 checks pass → PASS; 1,000 kVA set, running utilisation 51.0 %; governing: motor starting
ReferenceHand calculation: S = 90/0.9 + 410/1 = 510.00 kVA; running = 510.00 × 1 = 510.00 kVA; start = 2.5 × 90 + 510.00 = 735.00 kVA; 735.00 × 1.25 = 918.75 → 1000 kVA (starting); running utilisation = 510.00/1000 = 51.0 %; peak = 735.00/1000 = 73.5 %; fuel = 0.25 × 1000 × 0.8 × 510.00/1000 = 102.00 L/h; parallel 4 units: 1.1 × 735.00/4 = 202.13 → 250 kVA each, N−1 = 750 kVA ≥ 735.00 kVA (validation case c0014-parallel-four-units-pass)

Example 14 — Three parallel units carrying the load with one out

Three 100 kVA units: the N−1 capacity equals the 200 kVA starting demand exactly, so the parallel check passes on the boundary.

Given: Loads: Fan 20 kW (motor, pf 0.8, DOL starting); Heaters 55 kW (resistive, typical pf). Essential services facility (typical diversity); safety margin 1.25, largest-motor starting checked, 3 identical units in parallel.

Load kVASload = P × duty / pf × qty: Fan: 20 / 0.8 = 25.00 kVA; Heaters: 55 / 1 = 55.00 kVA
ConnectedStotal = 25.00 + 55.00 = 80.00 kVA; Ptotal = 75.00 kW; overall pf = 75.00 / 80.00 = 0.938
Running loadSdiv = 80.00 × 1 (essential services) = 80.00 kVA (75.00 kW)
Starting demandLargest starting kVA: Fan 20 kW DOL → Sstart = 6 × 20 = 120.00 kVA; Ssd = 120.00 + 80.00 = 200.00 kVA
SizingSreq = max(80.00, 200.00) = 200.00 kVA → sized on starting; Sreq × m = 200.00 × 1.25 = 250.00 kVA → next standard rating ≥ 250.00 = 250 kVA PASS
UtilisationRunning = 80.00 / 250 = 32.0 %; peak = 200.00 / 250 = 80.0 %
FuelF = 250 × 0.8 × (80.00 / 250) × 0.25 = 16.00 L/h
Parallel setUnit = next standard ≥ 1.1 × 200.00 / 3 = 73.33 → 100 kVA; 3 × 100 = 300 kVA; N−1 = 2 × 100 = 200 kVA vs Sreq 200.00 kVA (100.0 %) PASS
Result2/2 checks pass → PASS; 250 kVA set, running utilisation 32.0 %; governing: motor starting. Install soft starter on Fan: Reduce generator from 250 kVA to 175 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 20/0.8 + 55/1 = 80.00 kVA; running = 80.00 × 1 = 80.00 kVA; start = 6 × 20 + 80.00 = 200.00 kVA; 200.00 × 1.25 = 250.00 → 250 kVA (starting); running utilisation = 80.00/250 = 32.0 %; peak = 200.00/250 = 80.0 %; fuel = 0.25 × 250 × 0.8 × 80.00/250 = 16.00 L/h; parallel 3 units: 1.1 × 200.00/3 = 73.33 → 100 kVA each, N−1 = 200 kVA ≥ 200.00 kVA (validation case c0014-parallel-three-units-pass)

Example 15 — 500 kVA essential load on two parallel units

The help page's parallel example: a 500 kVA running load split over two units gives 300 kVA each, which cannot carry the load with one unit out.

Given: Loads: Process heaters 500 kW (resistive, typical pf). Essential services facility (typical diversity); safety margin 1.25, motor starting not checked, 2 identical units in parallel.

Load kVASload = P × duty / pf × qty: Process heaters: 500 / 1 = 500.00 kVA
ConnectedStotal = 500.00 = 500.00 kVA; Ptotal = 500.00 kW; overall pf = 500.00 / 500.00 = 1.000
Running loadSdiv = 500.00 × 1 (essential services) = 500.00 kVA (500.00 kW)
Starting demandMotor starting not checked (include_motor_starting = no)
SizingSreq = Sdiv = 500.00 kVA → sized on running; Sreq × m = 500.00 × 1.25 = 625.00 kVA → next standard rating ≥ 625.00 = 750 kVA PASS
UtilisationRunning = 500.00 / 750 = 66.7 %; peak = 500.00 / 750 = 66.7 %
FuelF = 750 × 0.8 × (500.00 / 750) × 0.25 = 100.00 L/h
Parallel setUnit = next standard ≥ 1.1 × 500.00 / 2 = 275.00 → 300 kVA; 2 × 300 = 600 kVA; N−1 = 1 × 300 = 300 kVA vs Sreq 500.00 kVA (166.7 %) FAIL
Result1/2 checks pass → FAIL; 750 kVA set, running utilisation 66.7 %; governing: running load
ReferenceHand calculation: S = 500/1 = 500.00 kVA; running = 500.00 × 1 = 500.00 kVA; 500.00 × 1.25 = 625.00 → 750 kVA (running); running utilisation = 500.00/750 = 66.7 %; fuel = 0.25 × 750 × 0.8 × 500.00/750 = 100.00 L/h; parallel 2 units: 1.1 × 500.00/2 = 275.00 → 300 kVA each, N−1 = 300 kVA < 500.00 kVA (validation case c0014-parallel-two-units-500kva)

Example 16 — Small shop on two 100 kVA units, no motors

With no motor-driven loads (motor, pumps, hvac) the starting demand equals the running load and sizing is on running; two 100 kVA units pass N−1 against 80 kVA.

Given: Loads: Shop lighting 28.5 kW (lighting, typical pf); IT and control 22 kW (control, pf 0.88); Office 45 kW (resistive, typical pf). Commercial facility (typical diversity); safety margin 1.25, largest-motor starting checked, 2 identical units in parallel.

Load kVASload = P × duty / pf × qty: Shop lighting: 28.5 / 0.95 = 30.00 kVA; IT and control: 22 / 0.88 = 25.00 kVA; Office: 45 / 1 = 45.00 kVA
ConnectedStotal = 30.00 + 25.00 + 45.00 = 100.00 kVA; Ptotal = 95.50 kW; overall pf = 95.50 / 100.00 = 0.955
Running loadSdiv = 100.00 × 0.8 (commercial) = 80.00 kVA (76.40 kW)
Starting demandNo motor-driven loads (motor, pumps, hvac) → Ssd = 0 + 80.00 = 80.00 kVA
SizingSreq = max(80.00, 80.00) = 80.00 kVA → sized on running; Sreq × m = 80.00 × 1.25 = 100.00 kVA → next standard rating ≥ 100.00 = 100 kVA PASS
UtilisationRunning = 80.00 / 100 = 80.0 %; peak = 80.00 / 100 = 80.0 %
FuelF = 100 × 0.8 × (80.00 / 100) × 0.25 = 16.00 L/h
Parallel setUnit = next standard ≥ 1.1 × 80.00 / 2 = 44.00 → 100 kVA; 2 × 100 = 200 kVA; N−1 = 1 × 100 = 100 kVA vs Sreq 80.00 kVA (80.0 %) PASS
Result2/2 checks pass → PASS; 100 kVA set, running utilisation 80.0 %; governing: running load
ReferenceHand calculation: S = 28.5/0.95 + 22/0.88 + 45/1 = 100.00 kVA; running = 100.00 × 0.8 = 80.00 kVA; no motor-driven (motor/pumps/hvac) loads, so starting demand = running load; 80.00 × 1.25 = 100.00 → 100 kVA (running); running utilisation = 80.00/100 = 80.0 %; fuel = 0.25 × 100 × 0.8 × 80.00/100 = 16.00 L/h; parallel 2 units: 1.1 × 80.00/2 = 44.00 → 100 kVA each, N−1 = 100 kVA ≥ 80.00 kVA (validation case c0014-parallel-two-units-small-shop)

Example 17 — Smaller DOL agitator out-starts a larger star-delta mixer

The starting check takes the largest starting kVA, not the largest motor: 45 kW DOL (270 kVA) beats 90 kW star-delta (180 kVA).

Given: Loads: Mixer 90 kW (motor, pf 0.88, star-delta starting); Agitator 45 kW (motor, pf 0.85, DOL starting); Heater 30 kW (resistive, typical pf). Continuous process facility (typical diversity); safety margin 1.25, largest-motor starting checked.

Load kVASload = P × duty / pf × qty: Mixer: 90 / 0.88 = 102.27 kVA; Agitator: 45 / 0.85 = 52.94 kVA; Heater: 30 / 1 = 30.00 kVA
ConnectedStotal = 102.27 + 52.94 + 30.00 = 185.21 kVA; Ptotal = 165.00 kW; overall pf = 165.00 / 185.21 = 0.891
Running loadSdiv = 185.21 × 0.95 (continuous process) = 175.95 kVA (156.75 kW)
Starting demandLargest starting kVA: Agitator 45 kW DOL → Sstart = 6 × 45 = 270.00 kVA; Ssd = 270.00 + 175.95 = 445.95 kVA
SizingSreq = max(175.95, 445.95) = 445.95 kVA → sized on starting; Sreq × m = 445.95 × 1.25 = 557.44 kVA → next standard rating ≥ 557.44 = 600 kVA PASS
UtilisationRunning = 175.95 / 600 = 29.3 %; peak = 445.95 / 600 = 74.3 %
FuelF = 600 × 0.8 × (175.95 / 600) × 0.25 = 35.19 L/h
Result1/1 checks pass → PASS; 600 kVA set, running utilisation 29.3 %; governing: motor starting. Install soft starter on Agitator: Reduce generator from 600 kVA to 400 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 90/0.88 + 45/0.85 + 30/1 = 185.21 kVA; running = 185.21 × 0.95 = 175.95 kVA; start = 6 × 45 + 175.95 = 445.95 kVA; 445.95 × 1.25 = 557.44 → 600 kVA (starting); running utilisation = 175.95/600 = 29.3 %; peak = 445.95/600 = 74.3 %; fuel = 0.25 × 600 × 0.8 × 175.95/600 = 35.19 L/h (validation case c0014-smaller-dol-motor-governs)

Example 18 — 160 kW soft-started borehole pump

A soft starter (2.5 × kW) on the largest motor keeps the starting demand within a 750 kVA set for an essential-services site.

Given: Loads: Borehole pump 160 kW (motor, pf 0.9, soft-start starting); Dosing pump 7.5 kW (motor, typical pf, DOL starting); Lighting 4 kW (lighting, typical pf); Control 3 kW (control, typical pf). Essential services facility (typical diversity); safety margin 1.25, largest-motor starting checked.

Load kVASload = P × duty / pf × qty: Borehole pump: 160 / 0.9 = 177.78 kVA; Dosing pump: 7.5 / 0.87 = 8.62 kVA; Lighting: 4 / 0.95 = 4.21 kVA; Control: 3 / 1 = 3.00 kVA
ConnectedStotal = 177.78 + 8.62 + 4.21 + 3.00 = 193.61 kVA; Ptotal = 174.50 kW; overall pf = 174.50 / 193.61 = 0.901
Running loadSdiv = 193.61 × 1 (essential services) = 193.61 kVA (174.50 kW)
Starting demandLargest starting kVA: Borehole pump 160 kW soft-start → Sstart = 2.5 × 160 = 400.00 kVA; Ssd = 400.00 + 193.61 = 593.61 kVA
SizingSreq = max(193.61, 593.61) = 593.61 kVA → sized on starting; Sreq × m = 593.61 × 1.25 = 742.01 kVA → next standard rating ≥ 742.01 = 750 kVA PASS
UtilisationRunning = 193.61 / 750 = 25.8 %; peak = 593.61 / 750 = 79.2 %
FuelF = 750 × 0.8 × (193.61 / 750) × 0.25 = 38.72 L/h
Result1/1 checks pass → PASS; 750 kVA set, running utilisation 25.8 %; governing: motor starting. Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 160/0.9 + 7.5/0.87 + 4/0.95 + 3/1 = 193.61 kVA; running = 193.61 × 1 = 193.61 kVA; start = 2.5 × 160 + 193.61 = 593.61 kVA; 593.61 × 1.25 = 742.01 → 750 kVA (starting); running utilisation = 193.61/750 = 25.8 %; peak = 593.61/750 = 79.2 %; fuel = 0.25 × 750 × 0.8 × 193.61/750 = 38.72 L/h (validation case c0014-soft-start-borehole-pump)

Example 19 — 132 kW star-delta compressor governs starting

A star-delta compressor (2 × kW) still out-starts a 30 kW DOL conveyor; the oversized set runs below 40 % and the tool warns of wet stacking.

Given: Loads: Compressor 132 kW (motor, pf 0.9, star-delta starting); Conveyor 30 kW (motor, typical pf, DOL starting); Lighting 10 kW (lighting, typical pf). Manufacturing facility (typical diversity); safety margin 1.25, largest-motor starting checked.

Load kVASload = P × duty / pf × qty: Compressor: 132 / 0.9 = 146.67 kVA; Conveyor: 30 / 0.87 = 34.48 kVA; Lighting: 10 / 0.95 = 10.53 kVA
ConnectedStotal = 146.67 + 34.48 + 10.53 = 191.68 kVA; Ptotal = 172.00 kW; overall pf = 172.00 / 191.68 = 0.897
Running loadSdiv = 191.68 × 0.75 (manufacturing) = 143.76 kVA (129.00 kW)
Starting demandLargest starting kVA: Compressor 132 kW star-delta → Sstart = 2 × 132 = 264.00 kVA; Ssd = 264.00 + 143.76 = 407.76 kVA
SizingSreq = max(143.76, 407.76) = 407.76 kVA → sized on starting; Sreq × m = 407.76 × 1.25 = 509.70 kVA → next standard rating ≥ 509.70 = 600 kVA PASS
UtilisationRunning = 143.76 / 600 = 24.0 %; peak = 407.76 / 600 = 68.0 %
FuelF = 600 × 0.8 × (143.76 / 600) × 0.25 = 28.75 L/h
Result1/1 checks pass → PASS; 600 kVA set, running utilisation 24.0 %; governing: motor starting. Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 132/0.9 + 30/0.87 + 10/0.95 = 191.68 kVA; running = 191.68 × 0.75 = 143.76 kVA; start = 2 × 132 + 143.76 = 407.76 kVA; 407.76 × 1.25 = 509.70 → 600 kVA (starting); running utilisation = 143.76/600 = 24.0 %; peak = 407.76/600 = 68.0 %; fuel = 0.25 × 600 × 0.8 × 143.76/600 = 28.75 L/h (validation case c0014-star-delta-compressor-governs)

Example 20 — Water pumping station (continuous process)

The help page's pumping-station example: a 110 kW DOL main pump beside a star-delta jockey pump, control and lighting, with a 2000 L tank.

Given: Loads: Main Pump 110 kW (motor, pf 0.89, DOL starting); Jockey Pump 22 kW (motor, pf 0.86, star-delta starting); Control Panel 3 kW (control, typical pf); Lighting 5 kW (lighting, typical pf). Continuous process facility (typical diversity); safety margin 1.25, largest-motor starting checked, fuel tank 2,000 L.

Load kVASload = P × duty / pf × qty: Main Pump: 110 / 0.89 = 123.60 kVA; Jockey Pump: 22 / 0.86 = 25.58 kVA; Control Panel: 3 / 1 = 3.00 kVA; Lighting: 5 / 0.95 = 5.26 kVA
ConnectedStotal = 123.60 + 25.58 + 3.00 + 5.26 = 157.44 kVA; Ptotal = 140.00 kW; overall pf = 140.00 / 157.44 = 0.889
Running loadSdiv = 157.44 × 0.95 (continuous process) = 149.57 kVA (133.00 kW)
Starting demandLargest starting kVA: Main Pump 110 kW DOL → Sstart = 6 × 110 = 660.00 kVA; Ssd = 660.00 + 149.57 = 809.57 kVA
SizingSreq = max(149.57, 809.57) = 809.57 kVA → sized on starting; Sreq × m = 809.57 × 1.25 = 1,011.96 kVA → next standard rating ≥ 1,011.96 = 1,250 kVA PASS
UtilisationRunning = 149.57 / 1,250 = 12.0 %; peak = 809.57 / 1,250 = 64.8 %
FuelF = 1,250 × 0.8 × (149.57 / 1,250) × 0.25 = 29.91 L/h; autonomy = 2,000 / 29.91 = 66.9 h
Result1/1 checks pass → PASS; 1,250 kVA set, running utilisation 12.0 %; governing: motor starting. Install soft starter on Main Pump: Reduce generator from 1250 kVA to 600 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 110/0.89 + 22/0.86 + 3/1 + 5/0.95 = 157.44 kVA; running = 157.44 × 0.95 = 149.57 kVA; start = 6 × 110 + 149.57 = 809.57 kVA; 809.57 × 1.25 = 1011.96 → 1250 kVA (starting); running utilisation = 149.57/1250 = 12.0 %; peak = 809.57/1250 = 64.8 %; fuel = 0.25 × 1250 × 0.8 × 149.57/1250 = 29.91 L/h; autonomy = 2000/29.91 = 66.9 h (validation case c0014-water-pumping-station)

Example 21 — Welding shop with 50 % duty welders and pump loads

Four welders at 50 % duty and pf 0.7, a pumps-type load (not starting-checked) and a 15 kW DOL compressor that governs starting.

Given: Loads: Welders 25 kW × 4 (welding, typical pf, duty 0.5); Compressor 15 kW (motor, typical pf, DOL starting); Cooling pumps 5.5 kW × 2 (pumps, typical pf, DOL starting); Lighting 6 kW (lighting, typical pf). Manufacturing facility (typical diversity); safety margin 1.25, largest-motor starting checked.

Load kVASload = P × duty / pf × qty: Welders: 25 × 0.5 / 0.7 × 4 = 71.43 kVA; Compressor: 15 / 0.87 = 17.24 kVA; Cooling pumps: 5.5 / 0.88 × 2 = 12.50 kVA; Lighting: 6 / 0.95 = 6.32 kVA
ConnectedStotal = 71.43 + 17.24 + 12.50 + 6.32 = 107.49 kVA; Ptotal = 82.00 kW; overall pf = 82.00 / 107.49 = 0.763
Running loadSdiv = 107.49 × 0.75 (manufacturing) = 80.62 kVA (61.50 kW)
Starting demandLargest starting kVA: Compressor 15 kW DOL → Sstart = 6 × 15 = 90.00 kVA; Ssd = 90.00 + 80.62 = 170.62 kVA
SizingSreq = max(80.62, 170.62) = 170.62 kVA → sized on starting; Sreq × m = 170.62 × 1.25 = 213.28 kVA → next standard rating ≥ 213.28 = 250 kVA PASS
UtilisationRunning = 80.62 / 250 = 32.2 %; peak = 170.62 / 250 = 68.2 %
FuelF = 250 × 0.8 × (80.62 / 250) × 0.25 = 16.12 L/h
Result1/1 checks pass → PASS; 250 kVA set, running utilisation 32.2 %; governing: motor starting. Install soft starter on Compressor: Reduce generator from 250 kVA to 150 kVA Low generator utilization: Risk of wet stacking in diesel engines. Consider smaller unit or load management.
ReferenceHand calculation: S = 25 × 0.5/0.7 × 4 + 15/0.87 + 5.5/0.88 × 2 + 6/0.95 = 107.49 kVA; running = 107.49 × 0.75 = 80.62 kVA; start = 6 × 15 + 80.62 = 170.62 kVA; 170.62 × 1.25 = 213.28 → 250 kVA (starting); running utilisation = 80.62/250 = 32.2 %; peak = 170.62/250 = 68.2 %; fuel = 0.25 × 250 × 0.8 × 80.62/250 = 16.12 L/h (validation case c0014-welding-shop-duty-cycle)

Standards & References

  • IEC 60034 — Rotating electrical machines — motor starting characteristics and ratings
  • ISO 8528 — Reciprocating internal combustion engine driven alternating current generating sets
  • Manufacturer guidelines — Caterpillar, Cummins, FG Wilson generator sizing application guides
  • Industry practice — diversity factors and safety margins based on engineering handbooks and real-world project experience
  • Fuel consumption — based on typical diesel generator specific fuel consumption of 0.25 L/kWh at rated load

Tips & Limitations

Tips
  • DOL-started motors often drive generator sizing far beyond the running load. Adding a soft starter on the largest motor can reduce the required generator size significantly.
  • Optimal generator utilization is 60–80%. This provides adequate margin for transients while avoiding wet stacking in diesel engines.
  • If the power factor of a load is not known, the calculator uses typical values (e.g., 0.87 for motors, 0.70 for welding). These are conservative — actual values may be higher.
  • For intermittent loads (e.g., welding at 60% duty cycle), set the duty cycle to reduce the effective running load contribution.
  • Fuel autonomy calculations assume a constant load. In practice, load variation will extend actual autonomy somewhat.
  • Essential services (hospitals, fire systems) should use a diversity factor of 1.0 — assume all loads run simultaneously.
  • For parallel generator configurations, consider N+1 redundancy so one unit can be taken offline for maintenance.
Limitations
  • Steady-state analysis — the calculator does not model transient voltage dip or frequency recovery during motor starting events.
  • No harmonic derating — VSD and other non-linear loads may require generator derating for harmonics, which is not modelled.
  • No altitude/temperature derating — generators at high altitude or elevated ambient temperatures require capacity derating per manufacturer data.
  • Simplified fuel model — actual fuel consumption varies with load profile, generator efficiency, altitude, and fuel quality. The 0.25 L/kWh figure is approximate.
  • Single starting event — only the motor-driven load (motor, pumps or hvac) with the largest starting kVA is considered. Simultaneous starting of multiple motors is not analysed.
  • No load sequencing — the calculator does not model sequential load application (block loading) on generator startup.
  • Generator sizes above 5000 kVA are rounded up to the nearest 100 kVA rather than matched to a standard catalogue size.

Developer Guide

Architecture

File layout:

  • components/c0014_generator_sizing/component.py — Component registration, parameter schema, calculator class, equation builder, summary cards builder
  • components/c0014_generator_sizing/calculations.py — Pure calculation functions, constants, and data tables (no Django dependencies)
  • components/c0014_generator_sizing/equations.py — Builds the unified article structure for report output

The calculator class is GeneratorSizingCalculator, inheriting from ElectricalCalculator. It delegates all math to the pure functions in calculations.py.

Key constants are defined as Python dicts in calculations.py:

  • STARTING_MULTIPLIERS — motor starting kVA multipliers by method
  • TYPICAL_POWER_FACTORS — default power factors by load type
  • DIVERSITY_FACTORS — diversity factors by facility type
  • STANDARD_GENERATOR_SIZES — list of standard generator sizes (100–5000 kVA)

Code Paths

Key functions in calculations.py:

Function Purpose
calculate_load_kva(power_kw, pf, duty_cycle) Convert kW to kVA with duty cycle
calculate_motor_starting_kva(power_kw, starting_method) Calculate motor starting kVA demand
analyze_load_inventory(loads) Sum all connected loads and calculate totals
calculate_running_load(loads, diversity_factor) Apply diversity factor to total connected load
calculate_starting_load(loads, background_kva) Find worst-case motor starting scenario
select_standard_generator_size(required_kva, margin) Select next standard size with safety margin
calculate_fuel_consumption(generator_kva, load_factor) Estimate diesel fuel consumption (L/hr)
calculate_fuel_autonomy(generator_kva, load_factor, tank) Calculate hours of fuel autonomy
calculate_parallel_generators(total_kva, num_generators) Evaluate parallel generator configuration
calculate_generator_sizing(data) Main orchestration function — calls all of the above

Key methods in component.py:

Function / Method Purpose
GeneratorSizingCalculator.validate_parameters() Validate loads array, safety margin, custom diversity
GeneratorSizingCalculator.calculate() Orchestrate calculation with fuel and parallel analysis
equation_builder(results) Build unified article structure for report generation
summary_cards_builder(results) Build dashboard summary cards (generator size, utilization, fuel)

Testing

Running tests:

pytest calcs/components/c0014_generator_sizing/ -v
pytest calcs/test_c0014* -v

Worked examples: the examples above are generated from the validation corpus in mcp_public/validation/cases/fe_calc_generator/ by python manage.py generate_help_examples --tool fe_calc_generator (renderer calcs/core/help_examples/generator.py). Do not edit _generator_sizing_examples.html by hand; add or change a case and regenerate.

How to extend:

  1. Add new load types by extending the TYPICAL_POWER_FACTORS dict and adding the new value to the load_type enum in the parameter schema.
  2. Add new starting methods by extending STARTING_MULTIPLIERS and the starting_method enum.
  3. Add new facility types by extending DIVERSITY_FACTORS and the facility_type enum.
  4. Extend standard sizes by adding values to STANDARD_GENERATOR_SIZES (keep sorted).
  5. For temperature/altitude derating, add a derating factor to select_standard_generator_size() and expose new input parameters in the schema.
  6. Write tests covering new constants, edge cases (empty loads, single load, all-motor loads), and boundary conditions (utilization near 40% and 90% thresholds).