Commercial Panel Maximum Demand

Jump to section

Overview

Calculates maximum demand for commercial and industrial electrical panels per AS/NZS 3000:2018 Appendix C (Tables C2 and C3). Supports two modes: a detailed mode with per-equipment diversity factors applied by load group, and a simple mode using a single user-specified diversity factor. For three-phase supplies the calculator tracks per-phase loading, reports phase imbalance, and selects a standard main switch rating.

Input Parameters

Installation Configuration

Parameter Type Default Range Description
installation_type Enum commercial_industrial — Installation type per AS/NZS 3000 Table C2 or C1. Options: residential_institution (col 2), commercial_industrial (col 3), blocks_of_units_2_5, blocks_of_units_6_20, blocks_of_units_21_plus
supply_type Enum three_phase_400v — Electrical supply configuration: single_phase_230v or three_phase_400v

Load Input Mode

Parameter Type Default Range Description
use_simple_load Boolean false — When true, uses a single total load and diversity factor instead of the detailed equipment list
equipment_list JSON string (see below) — JSON array of equipment objects (detailed mode). Each object requires: load_group, description, phase (A/B/C), rating_value, rating_unit (W/kW/A/points), quantity, power_factor. Optional: duty_cycle (0–100, for resistance welders)
simple_total_load_w Number 50,000 0 – 10,000,000 W Total connected load in watts (simple mode)
simple_diversity_factor Number 0.75 0.1 – 1.0 Overall diversity factor (simple mode)

Additional Parameters

Parameter Type Default Range Description
future_growth_factor Number 1.1 1.0 – 2.0 Multiplier for future load growth allowance

Voltage & Motor Parameters

Parameter Type Default Range Description
nominal_voltage_1ph Number 230 230 / 240 V Nominal single-phase voltage
nominal_voltage_3ph Number 400 400 / 415 V Nominal three-phase line-to-line voltage
motor_power_factor Number 0.86 0.5 – 1.0 Power factor applied to motor loads for VA conversion
motor_efficiency Number 0.95 0.5 – 1.0 Efficiency applied to motor loads for VA conversion

Load Groups (Table C2)

Each equipment item references a load_group that determines which diversity rule is applied. The supported groups are:

Load Group Key Code Name Column 2 Rule (Residential Inst.) Column 3 Rule (Commercial/Industrial)
lighting_general a Lighting, General 75% connected load 100% connected load
socket_10a_general bi Socket 10A, General (No HVAC) 1000W first + 400W each additional 1000W first + 750W each additional
socket_10a_hvac_room bii Socket 10A, General (HVAC Room) 1000W first + 100W each additional
socket_15a_plus biii Socket 15A and larger Largest 100%, remaining 50% Largest 100%, remaining 75%
cooking_range / cooking_other ci Cooking Largest 100%, remaining 50% Largest 100%, remaining 75%
air_conditioner / hw_instantaneous ci Air Conditioning / Instantaneous HW Largest 100%, remaining 50% Largest 100%, remaining 75%
ev_charger cii Electric Vehicle Charger Largest 100%, remaining 75%
motor_general d Motor, General Largest 100%, remaining 50% Largest 100%, next 75%, remaining 50%
motor_lift e Motor, Lift Largest 125%, next 75%, remaining 50%
motor_fuel_dispensing fi Motor, Fuel Dispensing Largest 100%, next 50%, remaining 25%
hw_storage / storage_heater / space_heater / pool_heater g Storage/Space/Pool Heaters, Storage HW 100% connected load
welder_arc hi Welder, Arc 2 largest 100%, next 85%, next 70%, remaining 60%
welder_resistance hii Welder, Resistance Each welder: rated VA × √(duty_cycle). Set duty_cycle per item (0–100%)
other_equipment / xray_equipment / fuel_dispensing_lights fii/i/j Other / X-Ray / Fuel Dispensing Lights 100% connected load

Output Results

Output Unit Description
total_connected_va VA Sum of all equipment ratings before diversity
total_diversified_va VA Total after diversity factors and future growth applied
overall_diversity_factor — Ratio of diversified to connected load (before growth factor)
max_demand_va VA Final maximum demand including growth factor
max_demand_a A Maximum demand current (highest loaded phase for 3-phase)
recommended_main_switch_a A Next standard switch rating ≥ calculated current
main_switch_utilization_percent % Ratio of demand current to selected switch rating
phase_a_diversified_va VA Diversified load on Phase A (three-phase only)
phase_b_diversified_va VA Diversified load on Phase B (three-phase only)
phase_c_diversified_va VA Diversified load on Phase C (three-phase only)
phase_imbalance_percent % Phase current imbalance percentage (three-phase only)
load_groups_summary list Per-group breakdown with connected VA, diversified VA, and diversity factor
compliant Boolean Calculation validity status

Formulas

Rating Conversion to VA

Load rated in watts:

\[ S = P \quad (\text{VA}) \]

Load rated in kilowatts:

\[ S = P \times 1000 \quad (\text{VA}) \]

Load rated in amperes:

\[ S = I \times V \quad (\text{VA}) \]

Motor load (W or kW input):

\[ S = \frac{P}{\cos\phi \times \eta} \quad (\text{VA}) \]

Where \(\cos\phi\) is the motor power factor and \(\eta\) is the motor efficiency.

Diversity — Lighting (Table C2, Row a)

Column 2 (Residential institutions):

\[ S_{\text{div}} = S_{\text{conn}} \times 0.75 \]

Column 3 (Commercial/industrial):

\[ S_{\text{div}} = S_{\text{conn}} \times 1.00 \]

Diversity — 10A Socket Outlets (Table C2, Row bi)

Column 2 (Residential institutions):

\[ S_{\text{div}} = 1000 + (n - 1) \times 400 \quad (\text{W}) \]

Column 3 (Commercial/industrial):

\[ S_{\text{div}} = 1000 + (n - 1) \times 750 \quad (\text{W}) \]

Where \(n\) is the number of socket outlet points.

Diversity — 10A Sockets in HVAC Rooms (Table C2, Row bii)

\[ S_{\text{div}} = 1000 + (n - 1) \times 100 \quad (\text{W}) \]

Diversity — Largest Plus Percentage (Table C2, Row biii/ci)

Applies to socket outlets ≥15A, cooking, air conditioning, and instantaneous hot water.

Column 2:

\[ S_{\text{div}} = S_1 \times 1.00 + \sum_{i=2}^{n} S_i \times 0.50 \]

Column 3:

\[ S_{\text{div}} = S_1 \times 1.00 + \sum_{i=2}^{n} S_i \times 0.75 \]

Where loads are sorted descending, \(S_1\) is the largest.

Diversity — General Motors (Table C2, Row d)

Column 2:

\[ S_{\text{div}} = S_1 \times 1.00 + \sum_{i=2}^{n} S_i \times 0.50 \]

Column 3:

\[ S_{\text{div}} = S_1 \times 1.00 + S_2 \times 0.75 + \sum_{i=3}^{n} S_i \times 0.50 \]

Diversity — Lift Motors (Table C2, Row e)

\[ S_{\text{div}} = S_1 \times 1.25 + S_2 \times 0.75 + \sum_{i=3}^{n} S_i \times 0.50 \]

Diversity — EV Chargers (Table C2, Row cii)

\[ S_{\text{div}} = S_1 \times 1.00 + \sum_{i=2}^{n} S_i \times 0.75 \]

Diversity — Fuel Dispensing Motors (Table C2, Row fi)

\[ S_{\text{div}} = S_1 \times 1.00 + S_2 \times 0.50 + \sum_{i=3}^{n} S_i \times 0.25 \]

Diversity — Arc Welders (Table C2, Row hi)

\[ S_{\text{div}} = S_1 \times 1.00 + S_2 \times 1.00 + S_3 \times 0.85 + S_4 \times 0.70 + \sum_{i=5}^{n} S_i \times 0.60 \]

Where loads are sorted descending by rated primary current.

Diversity — Resistance Welders (Table C2, Row hii)

\[ S_{\text{eff},i} = S_{\text{rated},i} \times \sqrt{\frac{d_i}{100}} \] \[ S_{\text{div}} = \sum_{i=1}^{n} S_{\text{eff},i} \times q_i \]

Where \(d_i\) is the duty cycle percentage (0–100%) for each welder and \(q_i\) is the quantity. Set the duty_cycle field per equipment item (default 100%).

Future Growth

\[ S_{\text{final}} = S_{\text{diversified}} \times k_{\text{growth}} \]

Where \(k_{\text{growth}}\) is the future growth factor (default 1.10).

Maximum Demand Current

Single-phase:

\[ I = \frac{S_{\text{final}}}{V_{1\phi}} \]

Three-phase (per-phase method):

\[ I_{\phi} = \frac{S_{\phi,\text{div}}}{V_{1\phi}} \] \[ I_{\text{max}} = \max(I_A,\; I_B,\; I_C) \]

Simple mode (three-phase):

\[ I = \frac{S_{\text{final}}}{\sqrt{3} \times V_{3\phi}} \]

Phase Imbalance

\[ \text{Imbalance} = \frac{I_{\max} - I_{\min}}{I_{\max}} \times 100\% \]

Main Switch Selection

The standard rating series used is:

25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000 A

\[ I_{\text{main}} = \min\{ I_{\text{std}} \;|\; I_{\text{std}} \geq I_{\text{max}} \} \]

Worked Examples

The 6 examples below are the validation cases for this calculation. Each one was produced by the calculation engine from the inputs shown, every figure was checked against the independent reference quoted at the end of the example, and the same cases are run against every engine build (see validation scorecard, tool fe_calc_max_demand; worked examples for every calculation).

#CaseMethodDemand (kVA)Current (A)Main switch / rating (A)Result
1Residential institution, single phaseTable C2 col. 2, 1φ16.1070.0080PASS
2Commercial premises, three phaseTable C2 col. 3, 3φ37.2555.43 (B)63PASS
3Office loads all on one phase, growth 1.1Table C2 col. 3, 3φ32.45141.09 (A)160PASS
4Three motors, column 3 tiersTable C2 col. 3, 3φ27.69120.40 (C)125PASS
5Hotel (column 2) with lifts and kitchenTable C2 col. 2, 3φ104.03157.23 (B)160PASS
6Fabrication workshop with weldersTable C2 col. 3, 3φ61.6399.98 (A)100PASS

Example 1 — Residential institution, single phase

Column 2 rules: lighting at 75 % and 10 A sockets at 1000 W for the first point plus 400 W for each further point.

Given: Single-phase 230 V supply, residential institution (column 2), AS/NZS 3000 Table C2. Loads: lighting 10 kW; 10 A socket outlets 20 points.

Lighting10 kW = 10,000 VA × 75 % = 7,500.0 VA
10 A socket outlets20 points → 1,000 + (20 − 1) × 400 = 8,600 W
TotalS = 7,500.0 + 8,600.0 = 16,100.0 VA = 16,100.0 VA; I = 16,100.0 / 230 = 70.00 A
Main switchnext standard rating ≥ 70.00 A → 80 A → 70.00 vs limit 80.00 A PASS
Result1/1 checks pass → PASS; maximum demand 70.00 A → 80 A main switch; governing: main switch
ReferenceHand calculation, AS/NZS 3000:2018 Table C2 column 2: lighting 10 kW × 75 % = 7500 W; 10 A sockets 20 points = 1000 W + 19 × 400 W = 8600 W; total 16 100 VA ÷ 230 V = 70.0 A (validation case c0023-non-domestic-col2-1ph)

Example 2 — Commercial premises, three phase

Column 3: two air conditioners take the largest in full plus 75 % of the other, and each group's diversity is shared back to phases by connected load.

Given: Three-phase 400/230 V supply, factory, shop or office (column 3), AS/NZS 3000 Table C2. Loads: lighting 4 kW on A; lighting 4 kW on B; lighting 4 kW on C; 10 A socket outlets 10 points on A; air conditioning 10 kW on B; air conditioning 10 kW on C.

Lighting (A/B/C)(4 kW + 4 kW + 4 kW) = 12,000 VA × 100 % = 12,000.0 VA
10 A socket outlets (A)10 points → 1,000 + (10 − 1) × 750 = 7,750 W
Air conditioning (B/C)largest 100 %, rest 75 %: 10,000.0 × 1 + 10,000.0 × 0.75 = 17,500.0 VA
Phase sharingGroup diversity shared back pro rata to connected VA: lighting A 4,000.0 / B 4,000.0 / C 4,000.0; air conditioning B 8,750.0 / C 8,750.0 VA
Per phaseA: 4,000.0 + 7,750.0 = 11,750.0 VA ÷ 230 V = 51.09 A; B: 4,000.0 + 8,750.0 = 12,750.0 VA ÷ 230 V = 55.43 A; C: 4,000.0 + 8,750.0 = 12,750.0 VA ÷ 230 V = 55.43 A → maximum demand = phase B, 55.43 A
TotalS = Σ phases = 37,250.0 VA (37.250 kVA)
Main switchnext standard rating ≥ 55.43 A → 63 A → 55.43 vs limit 63.00 A PASS
Phase imbalance(55.43 − 51.09) / 55.43 × 100 (informative; the component warns above 20 %) → 7.8 vs limit 20.0 % INFO
Result1/1 checks pass → PASS; maximum demand 55.43 A (B) → 63 A main switch; governing: main switch
ReferenceHand calculation, AS/NZS 3000:2018 Table C2 column 3: lighting 12 kW at 100 %; 10 A sockets 10 points = 1000 W + 9 × 750 W = 7750 W (phase A); air conditioners largest 10 kW at 100 % + 10 kW at 75 % = 17.5 kW shared B/C; A = 4000 + 7750 = 11 750 VA = 51.09 A; B = C = 4000 + 8750 = 12 750 VA = 55.43 A at 230 V (validation case c0023-non-domestic-col3-3ph)

Example 3 — Office loads all on one phase, growth 1.1

Column 3 counts lighting in full and sockets at 1000 W + 750 W per extra point; with everything on phase A the imbalance warning fires.

Given: Three-phase 400/230 V supply, factory, shop or office (column 3), AS/NZS 3000 Table C2. Loads: lighting 6,000 W on A; 10 A socket outlets 15 points on A; air conditioning 12,000 W on A. Growth factor 1.1.

Lighting (A)6,000 W = 6,000 VA × 100 % = 6,000.0 VA
10 A socket outlets (A)15 points → 1,000 + (15 − 1) × 750 = 11,500 W
Air conditioning (A)largest 100 %, rest 75 %: 12,000.0 × 1 = 12,000.0 VA
Per phaseA: 6,000.0 + 11,500.0 + 12,000.0 = 29,500.0 VA × 1.1 = 32,450.0 VA ÷ 230 V = 141.09 A; B: no load, 0 A; C: no load, 0 A → maximum demand = phase A, 141.09 A
TotalS = Σ phases = 32,450.0 VA (32.450 kVA)
Main switchnext standard rating ≥ 141.09 A → 160 A → 141.09 vs limit 160.00 A PASS
Phase imbalance(141.09 − 0.00) / 141.09 × 100 (informative; the component warns above 20 %) → 100.0 vs limit 20.0 % INFO
Result1/1 checks pass → PASS; maximum demand 141.09 A (A) → 160 A main switch; governing: main switch. Phase imbalance is high (100.0%)
ReferenceHand calculation, AS/NZS 3000:2018 Table C2 column 3: lighting 6 000 W × 100 % = 6 000 VA; 10 A sockets 15 points = 1 000 + 14 × 750 = 11 500 W; one air conditioner 12 000 W at 100 %; 29 500 VA × 1.10 = 32 450 VA, all on phase A: 32 450 ÷ 230 = 141.09 A → 160 A main switch; phases B and C carry nothing, imbalance 100 %. (Former hand-written help-page Example 1.) (validation case c0023-non-domestic-office-one-phase-loaded)

Example 4 — Three motors, column 3 tiers

Column 3 motors: largest 100 %, next 75 %, remainder 50 %, after converting kW to VA with pf 0.86 and η 0.95.

Given: Three-phase 400/230 V supply, factory, shop or office (column 3), AS/NZS 3000 Table C2. Loads: motors 15 kW (Motor 1) on C; motors 7.5 kW (Motor 2) on C; motors 4 kW (Motor 3) on C. Motor pf 0.86, η 0.95.

Motors (C)S = P/(0.86 × 0.95); largest 100 %, next 75 %, rest 50 %: 18,359.9 × 1 + 9,179.9 × 0.75 + 4,896.0 × 0.5 = 27,692.8 VA
Per phaseA: no load, 0 A; B: no load, 0 A; C: 27,692.8 VA ÷ 230 V = 120.40 A → maximum demand = phase C, 120.40 A
TotalS = Σ phases = 27,692.8 VA (27.693 kVA)
Main switchnext standard rating ≥ 120.40 A → 125 A → 120.40 vs limit 125.00 A PASS
Phase imbalance(120.40 − 0.00) / 120.40 × 100 (informative; the component warns above 20 %) → 100.0 vs limit 20.0 % INFO
Result1/1 checks pass → PASS; maximum demand 120.40 A (C) → 125 A main switch; governing: main switch. Phase imbalance is high (100.0%)
ReferenceHand calculation, AS/NZS 3000:2018 Table C2 column 3 row D: S = P/(0.86 × 0.95 = 0.817): 15 kW → 18 359.85 VA, 7.5 kW → 9 179.93 VA, 4 kW → 4 895.96 VA; 18 359.85 × 1.00 + 9 179.93 × 0.75 + 4 895.96 × 0.50 = 27 692.78 VA on phase C ÷ 230 = 120.40 A → 125 A. (Former hand-written help-page Example 3.) (validation case c0023-non-domestic-motors-col3)

Example 5 — Hotel (column 2) with lifts and kitchen

Column 2: lighting at 75 %, sockets at 1000 W + 400 W per extra point, lifts at 125 % / 75 %, ranges largest + 50 %; diversity shared back to phases by connected load.

Given: Three-phase 400/230 V supply, residential institution (column 2), AS/NZS 3000 Table C2. Loads: lighting 6 kW on A; lighting 6 kW on B; lighting 6 kW on C; 10 A socket outlets 20 points on A; 10 A socket outlets 20 points on B; 10 A socket outlets 20 points on C; lift motors 11 kW (Lift 1) on A; lift motors 11 kW (Lift 2) on B; ranges 3 × 10 kW (Kitchen ranges) on C; storage water heating 9 kW on A; storage water heating 10 kW on B. Motor pf 0.86, η 0.95; supply rating 200 A.

Lighting (A/B/C)(6 kW + 6 kW + 6 kW) = 18,000 VA × 75 % = 13,500.0 VA
10 A socket outlets (A/B/C)60 points → 1,000 + (60 − 1) × 400 = 24,600 W
Lift motors (A/B)S = P/(0.86 × 0.95); largest 125 %, next 75 %, rest 50 %: 13,463.9 × 1.25 + 13,463.9 × 0.75 = 26,927.8 VA
Ranges (C)largest 100 %, rest 50 %: 10,000.0 × 1 + 10,000.0 × 0.5 + 10,000.0 × 0.5 = 20,000.0 VA
Storage water heating (A/B)(9 kW + 10 kW) = 19,000 VA × 100 % = 19,000.0 VA
Phase sharingGroup diversity shared back pro rata to connected VA: lighting A 4,500.0 / B 4,500.0 / C 4,500.0; 10 A socket outlets A 8,200.0 / B 8,200.0 / C 8,200.0; lift motors A 13,463.9 / B 13,463.9; storage water heating A 9,000.0 / B 10,000.0 VA
Per phaseA: 4,500.0 + 8,200.0 + 13,463.9 + 9,000.0 = 35,163.9 VA ÷ 230 V = 152.89 A; B: 4,500.0 + 8,200.0 + 13,463.9 + 10,000.0 = 36,163.9 VA ÷ 230 V = 157.23 A; C: 4,500.0 + 8,200.0 + 20,000.0 = 32,700.0 VA ÷ 230 V = 142.17 A → maximum demand = phase B, 157.23 A
TotalS = Σ phases = 104,027.8 VA (104.028 kVA)
Main switchnext standard rating ≥ 157.23 A → 160 A → 157.23 vs limit 160.00 A PASS
Supply ratingI = 157.23 A against the given supply rating → 157.23 vs limit 200.00 A PASS
Phase imbalance(157.23 − 142.17) / 157.23 × 100 (informative; the component warns above 20 %) → 9.6 vs limit 20.0 % INFO
Result2/2 checks pass → PASS; maximum demand 157.23 A (B) → 160 A main switch; governing: supply rating
ReferenceHand calculation, AS/NZS 3000:2018 Table C2 column 2 at 230 V: lighting 18 kW × 75 % = 13 500 VA (4 500 per phase); 10 A sockets 60 points = 1 000 + 59 × 400 = 24 600 W (8 200 per phase); lifts 11 000/0.817 = 13 463.89 VA each → 13 463.89 × 1.25 + 13 463.89 × 0.75 = 26 927.78 VA (half to A, half to B); ranges 3 × 10 kW → 10 000 + 2 × 5 000 = 20 000 VA (C); storage HW 9 kW (A) and 10 kW (B) at 100 %. A = 4 500 + 8 200 + 13 463.89 + 9 000 = 35 163.89 VA = 152.89 A; B = 36 163.89 VA = 157.23 A; C = 32 700 VA = 142.17 A → 160 A main switch, 200 A supply passes. (validation case c0023-non-domestic-hotel-col2)

Example 6 — Fabrication workshop with welders

Arc welders take 100/100/85/70/60 %, a resistance welder its rating × √duty cycle, plant-room sockets 1000 W + 100 W per point; each group is shared back to phases by connected load.

Given: Three-phase 400/230 V supply, factory, shop or office (column 3), AS/NZS 3000 Table C2. Loads: lighting 3 kW on A; lighting 3 kW on B; lighting 3 kW on C; arc welders 2 × 32 A × 230 V (MIG 1-2) on A; arc welders 32 A × 230 V (MIG 3) on B; arc welders 25 A × 230 V (Stick welder) on B; arc welders 32 A × 230 V (MIG 4) on C; resistance welders 80 A × 230 V (Spot welder) at 25 % duty on C; 10 A sockets, plant rooms 12 points on A; motors 5.5 kW (Compressor) on A; motors 4 kW (Saw) on B; motors 2.2 kW (Drill) on C. Motor pf 0.86, η 0.95; supply rating 160 A.

Lighting (A/B/C)(3 kW + 3 kW + 3 kW) = 9,000 VA × 100 % = 9,000.0 VA
Arc welders (A/B/C)two largest 100 %, then 85 %, 70 %, rest 60 %: 7,360.0 × 1 + 7,360.0 × 1 + 7,360.0 × 0.85 + 7,360.0 × 0.7 + 5,750.0 × 0.6 = 29,578.0 VA
Resistance welders (C)Seff = S × √(duty): 80 A × 230 V × √(25/100) = 9,200.0 VA
10 A sockets, plant rooms (A)12 points → 1,000 + (12 − 1) × 100 = 2,100 W
Motors (A/B/C)S = P/(0.86 × 0.95); largest 100 %, next 75 %, rest 50 %: 6,731.9 × 1 + 4,896.0 × 0.75 + 2,692.8 × 0.5 = 11,750.3 VA
Phase sharingGroup diversity shared back pro rata to connected VA: lighting A 3,000.0 / B 3,000.0 / C 3,000.0; arc welders A 12,372.5 / B 11,019.3 / C 6,186.2; motors A 5,523.6 / B 4,017.2 / C 2,209.5 VA
Per phaseA: 3,000.0 + 12,372.5 + 2,100.0 + 5,523.6 = 22,996.1 VA ÷ 230 V = 99.98 A; B: 3,000.0 + 11,019.3 + 4,017.2 = 18,036.5 VA ÷ 230 V = 78.42 A; C: 3,000.0 + 6,186.2 + 9,200.0 + 2,209.5 = 20,595.7 VA ÷ 230 V = 89.55 A → maximum demand = phase A, 99.98 A
TotalS = Σ phases = 61,628.3 VA (61.628 kVA)
Main switchnext standard rating ≥ 99.98 A → 100 A → 99.98 vs limit 100.00 A PASS
Supply ratingI = 99.98 A against the given supply rating → 99.98 vs limit 160.00 A PASS
Phase imbalance(99.98 − 78.42) / 99.98 × 100 (informative; the component warns above 20 %) → 21.6 vs limit 20.0 % INFO
Result2/2 checks pass → PASS; maximum demand 99.98 A (A) → 100 A main switch; governing: supply rating. Phase imbalance is high (21.6%)
ReferenceHand calculation, AS/NZS 3000:2018 Table C2 column 3 at 230 V: arc welders 4 × 32 A (7 360 VA) + 25 A (5 750 VA) → 7 360 × (1 + 1 + 0.85 + 0.70) + 5 750 × 0.60 = 29 578.00 VA of 35 190 VA connected; spot welder 80 A × 230 × √0.25 = 9 200 VA; plant-room sockets 12 points = 1 000 + 11 × 100 = 2 100 W; motors (5 500 + 0.75 × 4 000 + 0.5 × 2 200)/0.817 = 11 750.31 VA; lighting 3 kW per phase at 100 %. Shared pro rata: welders A 14 720/35 190, B 13 110/35 190, C 7 360/35 190; motors by kW 5.5/4/2.2 of 11.7. A 99.98 A, B 78.42 A, C 89.55 A → maximum A 99.98 A, 100 A main switch; 160 A supply passes. (validation case c0023-non-domestic-workshop-welders)

Standards & References

  • AS/NZS 3000:2018 — Electrical installations (known as the Wiring Rules)
  • Appendix C — Maximum demand assessment
  • Table C1 — Diversity for blocks of units (residential)
  • Table C2 (Column 2) — Diversity for residential institutions, hotels, hospitals, boarding houses
  • Table C2 (Column 3) — Diversity for factories, shops, offices, schools, churches
  • Table C3 — Energy-demand method (alternative)
  • AS/NZS 3008.1.1:2017 — Cable selection (for downstream cable sizing)

Tips & Limitations

Tips
  • Distribute loads evenly across phases to minimise imbalance — aim for <10% imbalance.
  • The future growth factor of 1.10 (10%) is a common allowance. Increase for installations where expansion is planned.
  • 10A socket outlets are entered as points, not watts. The diversity rule is point-count based, not load based.
  • For motor loads, the calculator automatically converts from kW to VA using the specified power factor and efficiency.
  • Use the detailed mode for formal design submissions — the simple mode is intended for preliminary estimates only.
  • Column 2 (residential institution) applies more aggressive diversity than Column 3 (commercial/industrial) for most load groups.
Limitations
  • Appendix C only — Table C2/C3 diversity factors are for guidance. The local distribution network service provider (DNSP) may impose different requirements.
  • Arc welders — Implemented per Table C2 row hi (2 largest 100%, next 85%, next 70%, remaining 60% of rated primary current).
  • Resistance welders — Implemented using sqrt(duty_cycle) method per Table C2 row hii. Set the duty_cycle field (0–100%) on each equipment item.
  • No harmonic derating — The calculation does not apply neutral harmonic derating for non-linear loads (e.g., LED lighting, VFDs).
  • Phase assignment is manual — The calculator does not automatically balance loads across phases. Three-phase loads should be split manually by the user.
  • Blocks of units — Table C1 diversity factors are loaded from the database (webcalcs StandardTable system). The factors must be populated via admin before blocks-of-units calculations will apply additional diversity beyond Table C2 base rules. A warning is shown when table data is missing.
  • Large loads over 200 A should be coordinated with the DNSP for supply upgrade and metering requirements.

Developer Guide

Architecture

File layout:

  • components/c0023_commercial_panel/component.py — Component registration, parameter schema, LOAD_GROUPS_C2 definitions, SVG generators, summary cards builder
  • components/c0023_commercial_panel/calculations.py — Pure calculation functions and diversity logic (no Django dependencies)
  • components/c0023_commercial_panel/equations.py — LaTeX equation builder for step-by-step output
  • components/c0023_commercial_panel/excel_generator.py — Excel export for panel schedule

The calculator class is CommercialPanelCalculator (extends ElectricalCalculator). It delegates to the pure function calculate_commercial_panel_demand() in calculations.py.

Key data structures:

  • LOAD_GROUPS_C2 — dict mapping load group keys to metadata (code, name, description, diversity rules)
  • Equipment list items — JSON objects with fields: load_group, description, phase, rating_value, rating_unit, quantity, power_factor
  • Results dict — flat dictionary with per-phase totals, overall demand, and load_groups_summary list

Code Paths

Key functions in calculations.py:

Function Purpose
calculate_commercial_panel_demand(data) Main entry point — orchestrates simple or detailed calculation
convert_rating_to_va(rating_value, rating_unit, voltage) Convert equipment ratings (W, kW, A, points) to VA
apply_diversity_lighting_c2(loads, voltage, inst_type) Table C2 row a — 75%/100% lighting diversity
apply_diversity_socket_10a_general(loads, voltage, inst_type) Table C2 row bi — 10A socket point-based diversity
apply_diversity_socket_10a_hvac(loads, voltage) Table C2 row bii — HVAC room socket diversity
apply_diversity_largest_plus_percentage(loads, voltage, inst_type) Generic largest 100% + remaining X% pattern (rows biii, ci)
apply_diversity_motors_general_c2(loads, voltage, inst_type, pf, eff) Table C2 row d — general motor three-tier diversity
apply_diversity_motors_lift(loads, voltage, pf, eff) Table C2 row e — lift motor diversity (125%/75%/50%)
apply_diversity_ev_chargers(loads, voltage) Table C2 row cii — EV charger diversity
apply_diversity_fuel_dispensing_motors(loads, voltage, pf, eff) Table C2 row fi — fuel dispensing motor diversity (100/50/25%)
apply_diversity_welder_arc(loads, voltage) Table C2 row hi — arc welder diversity (100/100/85/70/60%)
apply_diversity_welder_resistance(loads, voltage) Table C2 row hii — resistance welder sqrt(duty_cycle) method
get_table_c1_diversity(block_tier, load_group) Look up Table C1 diversity factor from DB
calculate_diversity_for_load_group_c2(load_group, loads, ...) Dispatcher — routes to the correct diversity function by load group
select_standard_main_switch_rating(current_a) Select next standard switch rating from series

Key functions in component.py:

Function Purpose
build_summary_cards(results) Build summary card data (max demand, load summary, phase balance)
generate_load_breakdown_svg(params, results) SVG pie chart of diversified load by group
generate_phase_balance_svg(params, results) SVG bar chart of three-phase loading with imbalance indicator
register_component(registry) Register calc type, schema, SVG generators, and builders

Testing

Running tests:

pytest calcs/test_c0023_commercial.py -v

Worked examples: the examples above are generated from the validation corpus (mcp_public/validation/cases/fe_calc_max_demand/) by python manage.py generate_help_examples --tool fe_calc_max_demand, which writes _commercial_panel_examples.html. Add or change a case there, then regenerate; the fragment is never edited by hand.

How to extend:

  1. Add new load groups by extending the LOAD_GROUPS_C2 dict in component.py and adding a corresponding diversity function or branch in calculate_diversity_for_load_group_c2().
  2. To implement Table C1 (blocks of units) diversity, add dedicated functions in calculations.py and route via the installation_type parameter.
  3. Add new standard switch ratings by extending the standard_ratings list in select_standard_main_switch_rating().
  4. For welder diversity (rows hi/hii), implement duty-cycle-based calculation and add test cases covering the rated primary current method.
  5. Write tests covering each diversity rule with known inputs and expected outputs from AS/NZS 3000 Table C2.